Home›Engines›Cummins/Onan C33 D5

Cummins/Onan C33 D5 Engine

The Cummins/Onan C33 D5 is a 3.3 L naturally aspirated engine. It powers generator sets from Cummins/Onan.

Also known as: Cummins C33 D5

3.3 L
Displacement

Engine specifications

Displacement3.3 L
Aspirationnaturally aspirated

Troubleshooting

80

Fault codes

CodeMeaningCauseRemedy
1HIGH COOLANT TEMP — Lamp: Shutdown; Indicates engine has overheated (coolant temperature has risen above the shutdown trip point)Allow engine to cool down completely before proceeding with the following checks: Check coolant level and replenish if low. Look for possible coolant leakage points and repair if necessary; Check for obstructions to cooling airflow and correct as necessary; Check fan belt and repair or tighten if necessary; Check blower fan and circulation pumps on remote radiator installations; Reset control and restart after locating and correcting problem.
2LOW OIL PRESSURE — Lamp: Shutdown; Indicates engine oil pressure has dropped below the shutdown trip pointCheck oil level, lines and filters. If oil system is OK but oil level is low, replenish. Reset control and restart. If oil switch is used, check switch performance.
12HIGH AC VOLTAGE — Lamp: Shutdown; Indicates that one or more of the phase voltages has exceeded 130% of nominal for 0 second, or has exceeded high ac voltage threshold of nominal for time delay seconds
13LOW AC VOLTAGE — Lamp: Shutdown; Indicates that one or more of the phase voltages has dropped below low ac voltage threshold for time delay seconds
14OVER FREQUENCY — Lamp: Shutdown; Indicates frequency is 10% above base frequency for approximately 10 seconds
15UNDER FREQUENCY — Lamp: Shutdown; Indicates that engine speed has dropped below 90% of nominal for approximately 10 secondsCheck fuel supply, intake air supply and load.
27EXCITATION FAULT — Lamp: Shutdown; Indicates a loss of all three voltage sense leads or failure in excitation circuitCheck field wiring (X1 and X2) for shorts or opens. (Refer to Section 7.)
38FIELD OVERLOAD — Lamp: Shutdown; Indicates that the Field AVR Duty Cycle has been at the maximum for at least 15 seconds
45SPEED SIGNAL LOST — Lamp: Shutdown; Indicates that no magnetic pickup pulses are sensed for a Loss of Speed delay. If a magnetic pickup is not installed, then speed sensing is performed by monitoring AC line frequency, this fault cannot occur
46HIGH AC CURRENT — Lamp: Shutdown; Indicates that an individual phase of alternator output current has exceeded high current threshold of the rated output current continuously for more than time delay secondsCheck load and load lead connections.
61EMERGENCY STOP — Lamp: Shutdown; Indicates remote Emergency StopTo reset the remote Emergency Stop button: Open (disable) remote emergency stop button; Move the rocker switch to the OFF position or press the OFF button; Select the desired operating mode (manual or remote).
71SPEED HZ MATCH — Lamp: Shutdown; Indicates that measured speed and measured AC output frequency do not agreeCheck genset setup for number of flywheel teeth.
72FAIL TO CRANK — Lamp: Shutdown; The genset has failed to sense rotation for two start attempts. Indicates possible fault with control, speed sensing or starting system. Can only occur in gensets with magnetic pickup installed and enabled
73FAIL TO START — Lamp: Shutdown; Indicates possible fuel system or air induction problem. (Engine cranks but fails to start)Check for empty fuel tank, fuel leaks, or plugged fuel lines and correct as required; Check for dirty fuel filter and replace if necessary; Check for dirty or plugged air filter and replace if necessary; Reset the control and restart after correcting the problem.
74FAIL TO STOP — Lamp: Shutdown; Genset continues to run after receiving shutdown command from the controller
77SHUTDOWN AFTER BS — Lamp: Shutdown; A shutdown fault occurred while the Battle Short mode was enabledCheck fault history for faults that may have been bypassed.
92 - 95AUX I/O MODULE INPUT 9 – 12 — Lamp: Shutdown; The nature of the Aux I/O Module fault is an optional customer selection. Example inputs: Low Fuel Day Tank, Water In Fuel, Ground Fault, etcEach of the fault functions can be programmed (using InPower service tool or access to Setup menu), as follows: Warning, Shutdown or Event (Default = Warning) (See fault code 234–237 for Warning and code 171–174 for Event); Change display name using up to 32 characters.
96OIL TEMP HIGH — Lamp: Shutdown; Indicates that the engine oil temperature is above normal and has reached the shutdown trip point. (I/O Module option.)
98AMBIENT TEMP HIGH — Lamp: Shutdown; Indicates ambient temperature is above normal and has reached the shutdown trip point. (I/O Module option.)
99FUEL LEVEL LOW — Lamp: Shutdown; Indicates that fuel level has reached the shutdown trip point. (I/O Module option.)
102VOLTAGE BIAS OOR — Lamp: Shutdown; Indicates the voltage bias circuit output is out of range (OOR), high or low. (I/O Module option.)
103SPEED BIAS OOR — Lamp: Shutdown; Indicates the speed bias circuit output is out of range (OOR), high or low. (I/O Module option.)
106I/O MODULE LOST — Lamp: Shutdown; Indicates the data link between the I/O module and the Base board is lost
163 - 170BASE I/O MODULE INPUT 1 – 8 — Lamp: None; The nature of the Base I/O Module event is an optional customer selectionEach event function can be programmed (using InPower service tool or access to Setup menu), as follows: Change display name using up to 32 characters; Select active low or high input.
171 - 174AUX I/O MODULE INPUT 9 – 12 — Lamp: None; The nature of the Aux I/O Module event is an optional customer selectionEach event function can be programmed (using InPower service tool or access to Setup menu), as follows: Change display name using up to 32 characters; Select active low or high input.
202PRE-HIGH COOL TMP — Lamp: Warning; Indicates engine is operating near cooling system capacity. Increase in load or higher ambient temperature may cause High Coolant Temp (1) shutdownReview code 1 correction list for other possible causes.
203LOW COOLANT TEMP — Lamp: Warning; Set is not operating. Warning occurs when engine coolant temperature is 70F (21C) or lower. NOTE: In applications where the ambient temperature falls below 40F (4C), Low Coolant Temp may be indicated even though the coolant heaters are operatingIndicates engine coolant heater is not operating or is not circulating coolant; Coolant heater not connected to power supply; Low coolant level; Open heater elementCheck for the following conditions: Coolant heater not connected to power supply. Check for blown fuse or disconnected heater cord and correct as required; Check for low coolant level and replenish if required. Look for possible coolant leakage points and repair as required; Open heater element. Check current draw of heater. Coolant temperature must be below 70F (default setting) for one minute to activate warning and be above 70F for five minutes before the warning can be cleared.
212COOL SENSOR OOR — Lamp: Warning; Indicates that the control has sensed that the engine coolant temperature sensor output is out of range (high or low). This fault will only occur if water temperature sensor is equipped on the gensetCheck sender/connectors/wires.
213LOW BATTERY — Lamp: Warning; Indicates battery voltage supply to the control is approaching a low level at which unpredictable operation will occurDischarged or defective battery; Poor battery cable connections; Battery wiring/calibration; Engine DC alternator; Battery charge voltage float levelCheck the battery charger fuse. Recharge or replace the battery; Clean the battery cable terminals and tighten all connections; Check battery wiring/calibration; Check engine DC alternator. Replace engine DC alternator if normal battery charging voltage is not obtained; Check battery charge voltage float level if applicable (raise float level).
214HIGH BATTERY — Lamp: Warning; Indicates battery voltage supply to the control is approaching a high level at which damage to the control can occurCheck float level on battery charger if applicable (lower float level); Check battery wiring/calibration.
215PRE-LOW OIL PRESSURE — Lamp: Warning; Indicates engine oil pressure has dropped below the warning trip point. This warning will only occur if genset is equipped with an oil pressure senderIf generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow code 2 procedure.
216HIGH AC CURRENT — Lamp: Warning; Indicates that one or more of the phase currents has exceeded high ac warning threshold for time delay secondsCheck load and load lead connections.
217OIL PRESS SENSOR OOR — Lamp: Warning; Indicates that the control has sensed that the engine oil pressure sensor output is out of range (high or low). This warning will only occur if genset is equipped with an oil pressure senderCheck sender/connectors/wires.
218BATTLE SHORT ACTIVE — Lamp: Warning; Indicates that the control is in Battle Short mode - used to bypass several fault shutdowns for genset operation during emergencies
219CHARGER FAILURE — Lamp: Warning; Indicates the battery charging alternator has not reached an acceptable voltage range within the selected period (default = 120 seconds)Refer to engine service manual if this fault occurs. If not failed, check wiring.
220FAIL TO SHUTDOWN — Lamp: Warning; Genset continues to run after receiving shutdown command from the controller. Battle Short feature enabled - used to bypass several critical fault shutdowns for genset operation during emergencies
221WEAK BATTERY — Lamp: Warning; Indicates that during cranking, the battery voltage is at or below the weak battery warning trip point for a time greater than or equal to the weak battery set timeSee code 213 for corrective action.
225ANNUNCIATOR OUTPUT CONFIGURATION ERROR — Lamp: Warning; Indicates a mismatch in the configuration of one of the annunciator relay outputs
226 - 233Base I/O Module Input 1 — 8 — Lamp: Warning; The nature of the Base I/O Module fault is an optional customer selection. Example inputs: Low Fuel Day Tank, Water in Fuel, Ground Fault, etcEach of the fault functions can be programmed (using InPower service tool or access to Setup menu), as follows: Warning, Shutdown or Event (Default = Warning) (See fault code 84–91 for shutdown and code 163–170 for Event); Change display name using up to 32 characters.
234-237AUX I/O MODULE INPUT 9–12 — Lamp: Warning; The nature of the Aux I/O Module fault is an optional customer selection. Example inputs: Low Fuel Day Tank, Water in Fuel, Ground Fault, etcEach of the fault functions can be programmed (using InPower service tool or access to Setup menu), as follows: Warning, Shutdown or Event (Default = Warning) (See fault code 92–95 for shutdown and code 171–174 for Event); Change display name using up to 32 characters.
238OIL TEMP HIGH — Lamp: Warning; Indicates engine has begun to overheat (oil temperature has risen to an unacceptable level). Increase in load or higher ambient temperature may cause High Oil Temp (code 96) shutdown. (I/O Module Option.)
239OIL TEMP OOR — Lamp: Warning; Indicates the oil temperature sensor output is out of range (OOR), high or low. (I/O Module option.)
242AMBIENT TEMP HIGH — Lamp: Warning; Indicates the ambient temperature has exceeded the warning threshold for genset room temperature. Increase in load may cause Ambient Temp High (code 98) shutdown. (I/O Module Option.)
243AMBIENT TEMP OOR — Lamp: Warning; Indicates the ambient temperature sensor output is out of range (OOR), high or low. (I/O Module Option)
244FUEL LEVEL LOW — Lamp: Warning; Indicates that the fuel has dropped below the low fuel level trip point. Allows time to refill before fuel level low (code 99) shutdown occurs. (I/O Module Option)
245FUEL LEVEL OOR — Lamp: Warning; Indicates the fuel level sensor output is out of range (OOR), high or low. (I/O Module Option)
252I/O MODULE LOST — Lamp: Warning; Indicates an intermittent data link between the I/O module and the Base board
1/202HIGH OR PRE-HIGH COOLANT TEMPERATURE (SHUTDOWN/SHUTDOWN) — Calibration-dependent. No action is taken by the Control for code 202. Engine will shut down for code 1Fault simulation was enabled with a PC based service toolWith a PC based service tool, verify that the fault simulation is not enabled for the coolant sensor. If you do not have a PC based service tool, remove battery power from the control to disable fault simulation overrides.
1/202HIGH OR PRE-HIGH COOLANT TEMPERATURE (SHUTDOWN/SHUTDOWN) — Calibration-dependent. No action is taken by the Control for code 202. Engine will shut down for code 1Engine or sensor circuitry problemCheck the sensor accuracy with a thermocouple or similar temperature probe. If the coolant temperature reading is accurate, the engine may be overheating. Refer to the engine service manual. If the coolant temperature reading is not accurate, go to next step.
1/202HIGH OR PRE-HIGH COOLANT TEMPERATURE (SHUTDOWN/SHUTDOWN) — Calibration-dependent. No action is taken by the Control for code 202. Engine will shut down for code 1The sensor could be badDisconnect the sensor and connect a coolant temperature sensor simulator to the harness. If the control responds to the simulator, replace the sensor. If control does not respond, go to next step.
1/202HIGH OR PRE-HIGH COOLANT TEMPERATURE (SHUTDOWN/SHUTDOWN) — Calibration-dependent. No action is taken by the Control for code 202. Engine will shut down for code 1The harness or Base board could be badMeasure the resistance of the coolant sensor and reconnect harness to sensor. Remove connector P11 from Base board and check resistance between pins P11-18 (H20) and P11-6 (H20 COM). If resistance is not the same, harness is bad. If resistance is the same, Base board is bad.
2/215LOW OIL OR PRE-LOW PRESSURE (WARNING/SHUTDOWN) OIL PRESSURE SENSOR TYPE : SENDER — Calibration-dependent. No action is taken by the Control for code 215. Engine will shut down for code 2Fault simulation was enabled with a PC based service toolWith a PC based service tool, verify that the fault simulation is not enabled for the oil pressure sensor. If you do not have a PC based service tool, remove battery power from the control to disable fault simulation overrides.
2/215LOW OIL OR PRE-LOW PRESSURE (WARNING/SHUTDOWN) OIL PRESSURE SENSOR TYPE : SENDER — Calibration-dependent. No action is taken by the Control for code 215. Engine will shut down for code 2Low oil level. Clogged lines or filtersCheck oil level, lines and filters. If oil system is OK but oil level is low, replenish.
2/215LOW OIL OR PRE-LOW PRESSURE (WARNING/SHUTDOWN) OIL PRESSURE SENSOR TYPE : SENDER — Calibration-dependent. No action is taken by the Control for code 215. Engine will shut down for code 2Sensor or oil pump could be bad. Or the generator set may be shutting down on another faultDisconnect the oil pressure sensor leads, and connect an oil pressure sensor simulator to the harness. If the control responds to the simulator, reconnect the sensor, disconnect the + signal wire at the fuel solenoid, and crank the engine. Check the oil pressure reading on the digital display. If the display shows an acceptable oil pressure, the problem may not be in the oil or oil sensing system. The genset may be shutting down on another fault (out of fuel, intermittent connector). Restart the genset and monitor the display panel for other faults. If the display does not show an acceptable oil pressure, replace the sensor. If the Control still doesn't display an oil pressure while cranking, the oil pump may be bad. Refer to the engine service manual. If the control does not respond to the simulator, go to next step.
2/215LOW OIL OR PRE-LOW PRESSURE (WARNING/SHUTDOWN) OIL PRESSURE SENSOR TYPE : SENDER — Calibration-dependent. No action is taken by the Control for code 215. Engine will shut down for code 2Harness or Base board could be badIf the control does not respond to the simulator, the Base board or the harness is bad. Check for +5 VDC at the sensor (lead marked S1). If there is no 5 VDC at the sensor: Check for 5 VDC at P11-17. If yes, harness is bad. If no, Base board is bad. If there is 5 VDC at the sensor, use the sensor simulator to generate a signal to P11-17 (OP OUT) and P11-5 (OP COMM). If the pressure signal (.5 to 4.5 VDC) does not get to P11, isolate to the harness. If the pressure signal does go to P11, the Base board is bad.
2/215LOW OIL OR PRE-LOW PRESSURE (WARNING/SHUTDOWN) OIL PRESSURE SENSOR TYPE : SENDER — Calibration-dependent. No action is taken by the Control for code 215. Engine will shut down for code 2Low Oil Pressure fault set points could be incorrectVerify set points against the normal operating pressures of the engine. Refer to engine manual.
12HIGH AC VOLTAGE (SHUTDOWN) — Engine will shut downFault simulation was enabled with a PC based service toolWith a PC based service tool, verify that the related fault simulation is not enabled. If you do not have a PC based service tool, remove battery power from the control to disable fault simulation overrides.
12HIGH AC VOLTAGE (SHUTDOWN) — Engine will shut downSingle step large block load removalClear fault and restart genset.
12HIGH AC VOLTAGE (SHUTDOWN) — Engine will shut downFault threshold is not set correctly with PC based service toolReset the threshold to the highest allowable setting. Determine the required operating range before adjusting the threshold.
12HIGH AC VOLTAGE (SHUTDOWN) — Engine will shut downBase board or generator is badRefer to Generator/Base Board Isolation Procedure in Section 7 to determine if the Base board is causing the high AC voltage shutdown fault.
12HIGH AC VOLTAGE (SHUTDOWN) — Engine will shut downVoltage sense connections/set up could be incorrectSee Section 17 for proper corrective actions.
13LOW ACE VOLTAGE (SHUTDOWN) — Engine will shut downFault simulation was enabled with a PC based service toolWith a PC based service tool, verify that the related fault simulation is not enabled. If you do not have a PC based service tool, remove battery power from the control to disable fault simulation overrides.
13LOW ACE VOLTAGE (SHUTDOWN) — Engine will shut downFault threshold is not set correctly with a PC based service toolReset the threshold to the lowest allowable setting. Determine the required operating range before adjusting the threshold.
13LOW ACE VOLTAGE (SHUTDOWN) — Engine will shut downOverloadCheck the load and correct any overload. Check operation by disconnecting load and restarting generator set.
13LOW ACE VOLTAGE (SHUTDOWN) — Engine will shut downImproper connections have been made at the generator output terminalsReconnect according to the appropriate reconnection diagram. See Section 9.
13LOW ACE VOLTAGE (SHUTDOWN) — Engine will shut downVoltage sense or setup wiring connection could be incorrectCheck that excitation inputs P13-5 and P13-6 are connected to the correct voltage.
13LOW ACE VOLTAGE (SHUTDOWN) — Engine will shut downThe rotating rectifier assembly (diodes CR1 through CR6) is faultyCheck each diode. See genset service manual
13LOW ACE VOLTAGE (SHUTDOWN) — Engine will shut downLoose connector or Base board is badRepair connections (P13) or replace the Base board if necessary.
13LOW ACE VOLTAGE (SHUTDOWN) — Engine will shut downVoltage sense connections/setup could be incorrectSee section 17 for proper connections

Symptoms & remedies

SymptomCauseRemedy
Engine does not crank in manual mode (no fault message) — Engine will not startNo power supplied to control; Poor battery cable connectionsClean the battery cable terminals and tighten all connections; Remove connector P11 and check for B+ at P11-3 & 15 and GND at P11-9 & 10. If B+ or ground missing, isolate to harness and TB BAT terminal mounted on engine block. If B+ and ground check OK, cycle power to base board by reconnecting P11 and retry operation.
Engine does not crank in manual mode (no fault message) — Engine will not startNo power supplied to front membrane panelCheck for B+ at TB1-1 and GND at TB1-4. If B+ or ground missing, the base board is bad. If B+ and ground check OK, remove P1 from back of front membrane panel. Check for B+ at P1-3 and ground at P1-5. If B+ or ground missing, repair harness.
Engine does not crank in manual mode (no fault message) — Engine will not startBase board not properly calibrated or corrupt calibrationConfirm that the installed calibration part number matches the serial plate information. Re-enter calibration file if necessary.
Engine does not crank in manual mode (no fault message) — Engine will not startThe Emergency Stop switch or wiring is defectiveWith Emergency Stop push button not activated (switch closed), remove configurable leads from TB1-15 and TB1-16 and check for continuity between these two leads. If circuit is open, isolate to Emergency Stop switch and wiring. If there is continuity, go to next step.
Engine does not crank in manual mode (no fault message) — Engine will not startThe menu display manual Run button, harness or the Base board is badCheck for continuity between P11-4 (RUN) to P11-8 (GND). If no continuity when pressing the manual Run button, isolate to front membrane panel and wiring. If there is continuity, the Base board is bad.
Engine does not crank in manual mode (no fault message) — Engine will not startOil Pressure switch or wiring is defectiveRemove P11 connection and check wiring between P11-6 and P11-7 to the switch; Verify control is configured for the type of switch installed; Verify proper operation of the switch
Engine does not crank in manual mode (no fault message) — Engine will not startOil Pressure sender, setup on wiring is defectiveRemove P11 connection and check wiring between P11-6, P11-17 and P11-5 (for 3-wire sender) to the sender; Verify control is configured for the type of sender; Verify operation of the sender
Engine does not crank in remote mode (no fault message) — Engine will not start in remote mode, but starts in manual modeThe remote start switch or configurable wiring is faultyReset the control. Attempt to start, and check for ground at TB1-11. If ground level is not present, isolate to the remote switch or configurable wiring. Repair as necessary. If ground is present, go to next step.
Engine does not crank in remote mode (no fault message) — Engine will not start in remote mode, but starts in manual modeThe menu display Auto button, harness or the Base board is badCheck for continuity between P11-16 (AUTO) to P11-8 (GND). If no continuity when pressing the menu display Auto button, isolate to front membrane panel or wiring harness. If there is continuity, the Base board is bad.
CONFIGURABLE INPUT #1 & #2 — Lamp: Shutdown; The nature of the fault is an optional configurable selection. Example inputs: Low Fuel Day Tank, Water In Fuel, Ground Fault, etcEach of the fault functions can be programmed (using service tool or operator panel), as follows: Warning or Shutdown (Default: Warning) (See fault code 204/205 for Warning); Change display name using up to 32 characters.
CONFIGURABLE INPUT #1, #2 — Lamp: Warning; The nature of the fault is an optional configurable selection. Example inputs: Low Fuel Day Tank, Water In Fuel, Ground Fault, etcEach of the fault functions can be programmed (using service tool), as follows: Warning or Shutdown (Default: Warning) (See fault code 75/76 for Shutdown); Change display name using up to 32 characters.

Fault codes and symptom→remedy steps extracted from this engine’s service/owner documentation; verify against the official manual before servicing. Showing the first 80 of 109 entries.

Common problems

15
  • LOW ACE VOLTAGE (SHUTDOWN) — Engine will shut down 13
    Cause: Fault simulation was enabled with a PC based service tool
    Fix: With a PC based service tool, verify that the related fault simulation is not enabled. If you do not have a PC based service tool, remove battery power from the control to disable fault simulation overrides.
  • Engine does not crank in manual mode (no fault message) — Engine will not start
    Cause: No power supplied to control; Poor battery cable connections
    Fix: Clean the battery cable terminals and tighten all connections; Remove connector P11 and check for B+ at P11-3 & 15 and GND at P11-9 & 10. If B+ or ground missing, isolate to harness and TB BAT terminal mounted on engine block. If B+ and ground check OK, cycle power to base board by reconnecting P11 and retry operation.
  • LOW OIL OR PRE-LOW PRESSURE (WARNING/SHUTDOWN) OIL PRESSURE SENSOR TYPE : SENDER — Calibration-dependent. No action is taken by the Control for code 215. Engine will shut down for code 2 2/215
    Cause: Fault simulation was enabled with a PC based service tool
    Fix: With a PC based service tool, verify that the fault simulation is not enabled for the oil pressure sensor. If you do not have a PC based service tool, remove battery power from the control to disable fault simulation overrides.
  • HIGH AC VOLTAGE (SHUTDOWN) — Engine will shut down 12
    Cause: Fault simulation was enabled with a PC based service tool
    Fix: With a PC based service tool, verify that the related fault simulation is not enabled. If you do not have a PC based service tool, remove battery power from the control to disable fault simulation overrides.
  • HIGH OR PRE-HIGH COOLANT TEMPERATURE (SHUTDOWN/SHUTDOWN) — Calibration-dependent. No action is taken by the Control for code 202. Engine will shut down for code 1 1/202
    Cause: Fault simulation was enabled with a PC based service tool
    Fix: With a PC based service tool, verify that the fault simulation is not enabled for the coolant sensor. If you do not have a PC based service tool, remove battery power from the control to disable fault simulation overrides.
  • Generator set output frequency cannot be maintained. 81 u
  • Engine does not crank in remote mode (no fault message) — Engine will not start in remote mode, but starts in manual mode
    Cause: The remote start switch or configurable wiring is faulty
    Fix: Reset the control. Attempt to start, and check for ground at TB1-11. If ground level is not present, isolate to the remote switch or configurable wiring. Repair as necessary. If ground is present, go to next step.
  • Configurable Input (Warning) — Warning. 204/205
    Cause: If there is no actual fault, the problem may be an external wiring problem
    Fix: Disconnect the signal lead from TB1 and reset the control. Check the following pins. CUST_IN1 - TB1-14 CUST_IN2 - TB1-12 If the message drops out, the external wiring has a short circuit. Grounding of either input activates fault
  • WEAK BATTERY — Lamp: Warning; Indicates that during cranking, the battery voltage is at or below the weak battery warning trip point for a time greater than or equal to the weak battery set time 221
    Fix: See code 213 for corrective action.
  • Weak Battery (Warning) 221
    Cause: Refer to code 213
    Fix: Refer to code 213
  • Voltage on any phase has dropped below a preset value.
    Fix: Adjustable over a range of 50-95% of voltage, time delay 2-20 seconds. Default value is 90% for 5 seconds.
  • VOLTAGE BIAS OOR — Lamp: Shutdown; Indicates the voltage bias circuit output is out of range (OOR), high or low. (I/O Module option.) 102
  • UNDER FREQUENCY — Lamp: Shutdown; Indicates that engine speed has dropped below 90% of nominal for approximately 10 seconds 15
    Fix: Check fuel supply, intake air supply and load.
  • Under Frequency (Shutdown) — Generator set will shut down. 15
    Cause: Fault threshold is not set correctly with PC based service tool; Overload; Fuel or air delivery problem; Governor fault; Loose connector or Base board is bad
    Fix: Reset the threshold to the lowest allowable setting. Determine the required operating range before adjusting the threshold; Check the load and correct any overload. Check operation by disconnecting load and restarting generator set; Refer to the engine service manual; Check fuel shutoff solenoid adjustment; Repair connections (P13) or replace the Base board if necessary
  • SPEED SIGNAL LOST — Lamp: Shutdown; Indicates that no magnetic pickup pulses are sensed for a Loss of Speed delay. If a magnetic pickup is not installed, then speed sensing is performed by monitoring AC line frequency, this fault cannot occur 45

Compiled from service & troubleshooting documentation across every generator set that uses the Cummins/Onan C33 D5.

Service specifications

55
TypeItemValueUnitCondition
ResistanceCoolant heater coil resistance10 to 60ohmsclosed heater
ResistanceInjection pump actuator resistance2.3ohms
ResistanceMain rotor resistance0.415Ohmswithin 10% of value
ResistanceMain rotor resistance0.437Ohmswithin 10% of value
ResistanceMain rotor resistance0.465Ohmswithin 10% of value
ResistanceMain rotor resistance0.545Ohmswithin 10% of value
ResistanceMain rotor resistance0.551Ohmswithin 10% of value
ResistanceMain rotor resistance0.657Ohmswithin 10% of value
ResistanceMain rotor resistance0.67Ohmswithin 10% of value
ResistanceMain rotor resistance0.708Ohmswithin 10% of value
ResistanceMain rotor resistance0.857Ohmswithin 10% of value
ResistanceMain rotor resistance0.89Ohmswithin 10% of value
ResistanceMain rotor resistance0.983Ohmswithin 10% of value
ResistanceMain rotor resistance0.99Ohmswithin 10% of value
ResistanceMain stator winding resistance0.3Ohms
ResistanceMain stator winding resistance0.353Ohms
ResistanceMain stator winding resistance0.51Ohms
ResistanceMain stator winding resistance0.625Ohms
ResistanceMain stator winding resistance0.95Ohms
ResistanceMain stator winding resistance1.33Ohms
ResistanceMain stator winding resistance1.908Ohms
ResistanceStator insulation resistance1.0Meg-Ohmminimum to Earth (Ground)
TorqueAVR cover to NDE bracket5Nm
TorqueAVR to NDE bracket5Nm
TorqueAxial air inlet cover to NDE bracket5Nm
TorqueClamping spacer to rectifier hub2.8/3.6Nm
TorqueCoupling disc to flywheel51Nm
TorqueCoupling disc to shaft75Nm
TorqueDE Adaptor to Flywheel housing51Nm
TorqueDE Adaptor to frame blocks26Nm
TorqueDE Air outlet cover6.5Nm
TorqueDiode fitting2.8/3.6Nm
TorqueDiode fitting torque36 to 42in-lbs (4 to 4.8 Nm)
TorqueEBG Housing cover to housing6.5Nm
TorqueEBG Rtr to shaft50Nm
TorqueEBG Str Hsg to NDE bracket10Nm
TorqueEBG Str to EBG Str Hsg10Nm
TorqueEarth lead to NDE bracket6Nm
TorqueExcitor stator to NDE bracket10Nm
TorqueFan to fan hub 290 and 3445Nm
TorqueMain rotor terminals24in-lbs (2.7 Nm)
TorqueNDE bracket to Frame blocks26Nm
TorquePigtail terminals24in-lbs (2.7 Nm)
TorqueRadial Inlet cover to Nde bracket5Nm
TorqueRectifier hub to excitor rotor2.8/3.6Nm
TorqueRotor leads to Clamping spacer2.8/3.6Nm
TorqueSmall Terminal box to NDE bracket5Nm
TorqueStator Lead to terminal studs6.5Nm
TorqueSurge suppresser terminals24in-lbs (2.7 Nm)
TorqueTerminal block to NDE bracket5Nm
TorqueTerminal box lid to terminal box5Nm
TorqueVaristor to rectifier hub2.8/3.6Nm
VoltageMPU output while cranking3.5 to 15VACwhile cranking
VoltageOil pressure sender output0.5VDCat 0 psi
VoltageOil pressure sender output4.5VDCat 100 psi

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
FuelNumber 2 diesel fuelDirect injection

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

59
CodeNameMeaningSeverityAction
1HIGH COOLANT TEMPEngine has overheated; coolant temperature has risen above shutdown trip point.ShutdownAllow engine to cool. Check coolant level, airflow obstructions, fan belt, blower and circulation pumps. Reset and restart.
2LOW OIL PRESSUREEngine oil pressure has dropped below shutdown trip point.ShutdownCheck oil level, lines and filters; replenish if low; reset and restart; check oil switch.
12HIGH AC VOLTAGEOne or more phase voltages exceeded 130% of nominal for 0 second, or exceeded high AC voltage threshold for time delay.ShutdownCheck fault simulation, block load removal, threshold setting, Base board or generator, voltage sense connections.
13LOW AC VOLTAGEOne or more phase voltages dropped below low AC voltage threshold for time delay.ShutdownCheck fault simulation, threshold, overload, output connections, excitation inputs, rotating rectifier diodes, connector or Base board.
14OVER FREQUENCYFrequency is 10% above base frequency for approximately 10 seconds.ShutdownCheck threshold, fuel or air delivery, governor, connector or Base board.
15UNDER FREQUENCYEngine speed dropped below 90% of nominal for approximately 10 seconds.ShutdownCheck fuel supply, intake air supply, load, threshold, governor, connector or Base board.
27EXCITATION FAULTLoss of all three voltage sense leads or failure in excitation circuit.ShutdownCheck field wiring (X1 and X2) for shorts or opens.
31OVERSPEEDEngine exceeded normal operating speed; default thresholds 1725 RPM (50 Hz) or 2075 RPM (60 Hz).ShutdownCheck cold engine, single step large block load removal, fault simulation, threshold, MPU, governor, flywheel teeth, fuel stop settings.
38FIELD OVERLOADField AVR Duty Cycle has been at maximum for at least 15 seconds.Shutdown
45SPEED SIGNAL LOSTNo magnetic pickup pulses are sensed for Loss of Speed delay; if no MPU, speed sensing is by AC line frequency and fault cannot occur.ShutdownInspect MPU wires/connector pins; test MPU for 3.5 to 15 VAC while cranking; check P11-12 to P11-24; replace Base board if needed.
46HIGH AC CURRENTIndividual phase alternator output current exceeded high current threshold continuously for more than time delay.ShutdownCheck load and load lead connections.
61EMERGENCY STOPRemote Emergency Stop.ShutdownOpen (disable) remote emergency stop button; move rocker switch to OFF or press OFF; select desired operating mode.
71SPEED HZ MATCHMeasured speed and measured AC output frequency do not agree.ShutdownCheck genset setup for number of flywheel teeth.
72FAIL TO CRANKGenset failed to sense rotation for two start attempts; possible control, speed sensing or starting system fault.ShutdownCheck starter, K7 starter relay, Emergency Stop switch/wiring, MPU circuit or Base board.
73FAIL TO STARTEngine cranks but fails to start; possible fuel system or air induction problem.ShutdownCheck fuel tank, leaks, plugged fuel lines, fuel filter, air filter; reset and restart; check glow plugs and governor linkage.
74FAIL TO STOPGenset continues to run after receiving shutdown command from controller.Shutdown
75,76CONFIGURABLE INPUT #1 & #2Optional configurable input fault.ShutdownDisconnect signal lead from TB1 and reset control; check CUST_IN1 TB1-14 and CUST_IN2 TB1-12.
77SHUTDOWN AFTER BSA shutdown fault occurred while Battle Short mode was enabled.ShutdownCheck fault history for faults that may have been bypassed.
81,82,83ANNUNCIATOR FAULT 1,2,3Optional configurable annunciator fault.Shutdown
121Speed Signal Lost - ShutdownShutdown
135/141Oil Pressure Sensor OOR - WarningWarning
143Pre-Low Oil Pressure - WarningWarning
145Coolant Sensor OOR - WarningWarning
146Pre-High Coolant Temp - WarningWarning
151High Coolant Temp - ShutdownShutdown
202PRE-HIGH COOL TMPEngine is operating near cooling system capacity.WarningReview code 1 correction list.
203LOW COOLANT TEMPEngine coolant temperature is 70F (21C) or lower.WarningCheck coolant heater power, low coolant level, heater element; check current draw.
204,205CONFIGURABLE INPUT #1,#2Optional configurable input warning.WarningDisconnect signal lead from TB1 and reset control; check CUST_IN1 TB1-14 and CUST_IN2 TB1-12.
212COOL SENSOR OORCoolant temperature sensor output is out of range (high or low).WarningCheck sender, connectors and wires.
213LOW BATTERYBattery voltage supply to control is approaching a low level.WarningCheck battery charger fuse; recharge or replace battery; clean connections; check wiring/calibration, engine DC alternator, float level.
214HIGH BATTERYBattery voltage supply to control is approaching a high level.WarningCheck float level on battery charger; check battery wiring/calibration.
215PRE-LOW OIL PRESSUREEngine oil pressure dropped below warning trip point.WarningFollow code 2 procedure.
216HIGH AC CURRENTOne or more phase currents exceeded high AC warning threshold for time delay.WarningCheck load and load lead connections.
217OIL PRESS SENSOR OOREngine oil pressure sensor output is out of range (high or low).WarningCheck sender, connectors and wires.
218BATTLE SHORT ACTIVEControl is in Battle Short mode; bypasses several fault shutdowns for emergency operation.Warning
219CHARGER FAILUREBattery charging alternator has not reached acceptable voltage range within selected period (default 120 seconds).WarningRefer to engine service manual if fault occurs; check wiring if not failed.
220FAIL TO SHUTDOWNGenset continues to run after shutdown command; Battle Short feature enabled.Warning
221WEAK BATTERYDuring cranking, battery voltage is at or below weak battery warning trip point for time >= weak battery set time.WarningSee code 213 for corrective action.
222,223,224ANNUNCIATOR FAULT 1,2,3Optional configurable annunciator fault.Warning
225ANNUNCIATOR OUTPUT CONFIGURATION ERRORMismatch in configuration of one of the annunciator relay outputs.WarningCheck network setup for duplicate use of same annunciator relay output; troubleshoot network devices.
234Overspeed - ShutdownShutdown
359Fail to Start - ShutdownShutdown
415Low Oil Pressure - ShutdownShutdown
441Low Battery - WarningWarning
442High Battery - WarningWarning
1311CUST_FAULT #1 - WarningWarning
1312CUST_FAULT #2 - WarningWarning
1317CUST_FAULT #3 - WarningWarning
1438Fail to Crank - ShutdownShutdown
1442Weak Battery - WarningWarning
1446High AC Voltage - ShutdownShutdown
1447Low AC Voltage - ShutdownShutdown
1448Under Frequency - ShutdownShutdown
1449Over Frequency - ShutdownShutdown
1471High AC Current - WarningWarning
1472High AC Current - ShutdownShutdown
1944Annunciator Error - WarningWarning
2335Excitation Fault - ShutdownShutdown
2677Fail to Stop - ShutdownShutdown

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Valves - Adjust, All adjustment
  1. Disconnect battery cables
  2. Remove valve cover
  3. Adjust valve lash
  4. Test run unit
Generator/Base Board Isolation Procedure diagnostic

⚠ Hazardous voltage

⚠ Test involves unregulated excitation; disconnect loads

Tools: 12 volt battery, Jumper leads, Voltmeter

  1. Throw line circuit breaker OFF and shutdown set.
  2. Disconnect X and XX exciter stator leads from AC harness.
  3. Prepare to measure output voltage across generator terminals.
  4. Bring two jumpers from 12V battery to X (Field +) and XX (Field -).
  5. Check polarity; correct or test inconclusive.
  6. Start set and connect battery negative to XX.
  7. If rated output voltage or higher and balanced, generator OK; troubleshoot control.
  8. If unbalanced, troubleshoot main stator; if uniformly low, troubleshoot exciter and field.
Testing Diodes diagnostic

⚠ Layers of dust can cause diodes to overheat and fail.

Tools: Ohmmeter

  1. Disconnect diode pigtails from terminal posts.
  2. Measure resistance between each diode pigtail and its plate.
  3. Reverse meter probes and repeat.
  4. Replace diode if resistance high or low in both directions.
Testing Exciter Rotor diagnostic

Tools: Wheatstone bridge, Ohmmeter

  1. Disconnect six rotor winding leads from rectifier terminal posts.
  2. Measure resistance across each pair of rotor windings U-V, V-W, W-U.
  3. Replace whole rotor shaft assembly if any winding resistance not per Table 6-1.
  4. Measure insulation resistance between winding lead and rotor laminations.
  5. Replace rotor shaft assembly if insulation resistance less than 1 megohm.
Testing Exciter Stator diagnostic

Tools: Wheatstone bridge, Digital ohmmeter, Insulation resistance meter

  1. Measure winding resistance with Wheatstone bridge or digital ohmmeter.
  2. Replace stator if resistance not as specified in Table 6-1.
  3. Disconnect X and XX leads and isolate from ground.
  4. Measure resistance between either lead and stator laminations.
  5. Replace stator if insulation resistance less than 1 megohm.
Testing Main Rotor diagnostic

Tools: Wheatstone bridge, Digital ohmmeter, Torque wrench

  1. Disconnect two main rotor leads from rotating rectifier terminals.
  2. Measure resistance between two leads with Wheatstone bridge or digital ohmmeter.
  3. Replace rotor if resistance not as specified in Table 6-1.
  4. Measure resistance between either lead and main rotor laminations.
  5. Replace rotor if insulation resistance less than 1 megohm.
  6. Torque terminals to 24 in-lbs (2.7 Nm) when reassembling.
Testing Main Stator diagnostic

Tools: Wheatstone bridge, Insulation tester

  1. Measure resistance across each pair of stator leads U1-U2, U5-U6, V1-V2, V5-V6, W1-W2, W5-W6.
  2. Use Wheatstone bridge or ohmmeter with at least 0.001 ohm precision.
  3. Replace stator if any winding resistance not as specified in Table 6-1.
  4. Disconnect AVR completely before insulation test.
  5. Disconnect Neutral to Earth and any connections.
  6. Use 500 or 1000 V insulation tester for low voltage generators up to 690V.
  7. Minimum insulation value is 1.0 Meg-Ohm to Earth; dry windings if below.
Genset, Standby - Remove and Install installation
  1. Disconnect and connect battery cables
  2. Disconnect and connect output leads
  3. Disconnect and connect fuel lines
  4. Disconnect and connect exhaust system
  5. Remove and install genset
  6. Test run unit
Magnetic Speed Pickup Unit (MPU) Installation installation

⚠ Do not use fan blade to bar over engine.

Tools: MPU sensor, Lock nut

  1. Bar engine until a flywheel gear tooth lines up in center of mounting hole.
  2. Thread sensor in gently by hand until it just touches gear tooth.
  3. Back it out one quarter turn and set lock nut.
Air Cleaner Element - Replace maintenance
  1. Remove and install cover and gasket
  2. Remove and install filter element
  3. Test run unit
Circuit Board Removal/Replacement maintenance

⚠ Electrostatic discharge will damage circuit boards.

Tools: Grounding wrist strap, InPower Service Tool, PCC1301 Interface Kit

  1. Turn off AC power to battery charger.
  2. Remove negative battery cable from starting battery.
  3. Wear grounding wrist strap; attach clip to chassis ground.
  4. Create capture file of genset parameters using InPower before replacing Base board.
  5. Remove circuit board connectors and board.
  6. After replacement, write previous settings to new Base board using capture file.
Fuel Filter, Spin-on Type - Replace maintenance
  1. Remove and install fuel filter
  2. Prime fuel system
  3. Test run unit

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
above 300 volts L-LX1 & X2CT secondariesCTs have dual secondaries (3 pins marked X1, X2 & X3).
below 300 volts L-LX1 & X3CT secondariesCTs have dual secondaries (3 pins marked X1, X2 & X3).

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What is the displacement of the Cummins/Onan C33 D5?

The Cummins/Onan C33 D5 has a displacement of 3.3 liters.

Which generators use the Cummins/Onan C33 D5 engine?

The Cummins/Onan C33 D5 powers 1 generator set(s), including Cummins/Onan C33 D5.

What is a common problem with the Cummins/Onan C33 D5 engine?

A commonly reported issue on generators using the Cummins/Onan C33 D5 is: LOW ACE VOLTAGE (SHUTDOWN) — Engine will shut down. Cause: Fault simulation was enabled with a PC based service tool. Fix: With a PC based service tool, verify that the related fault simulation is not enabled. If you do not have a PC based service tool, remove battery power from the control to disable fault simulation overrides..