Home›Repair guides›Cummins/Onan›Generator/Base Board Isolation Procedure

Cummins/Onan — Generator/Base Board Isolation Procedure

Testing & diagnosis · Generator and Base board

From a Cummins/Onan service manual covering: C30 D6, C33 D5, C35 D6, C38 D5. Check it applies to your exact model before use.

Applies to: Cummins/Onan C30 D6, Cummins/Onan C33 D5, Cummins/Onan C35 D6, Cummins/Onan C38 D5

Before you start

  • Hazardous voltage
  • Test involves unregulated excitation; disconnect loads

Procedure

  1. Throw line circuit breaker OFF and shutdown set.
  2. Disconnect X and XX exciter stator leads from AC harness.
  3. Prepare to measure output voltage across generator terminals.
  4. Bring two jumpers from 12V battery to X (Field +) and XX (Field -).
  5. Check polarity; correct or test inconclusive.
  6. Start set and connect battery negative to XX.
  7. If rated output voltage or higher and balanced, generator OK; troubleshoot control.
  8. If unbalanced, troubleshoot main stator; if uniformly low, troubleshoot exciter and field.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Normal excitation voltage approximately 10 VDC no-load to 40 VDC full-load

Full service-parts list: Cummins/Onan C35 D6 →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Cummins/Onan repair guides →