Cummins/Onan — AC Load Connections (Circuit Breaker)

Installation · Circuit breaker box

From a Cummins/Onan service manual covering: C25 D6, C30 D6, C35 D6, C40 D6, C50 D6, C60 D6. Check it applies to your exact model before use.

Applies to: Cummins/Onan C25 D6, Cummins/Onan C30 D6, Cummins/Onan C35 D6, Cummins/Onan C40 D6, Cummins/Onan C50 D6, Cummins/Onan C60 D6, Cummins/Onan 4BT3.3 engine

Before you start

  • Improper installation can lead to electrocution and property damage.

Procedure

  1. Shut down and disable the generator set (Off then E-Stop, cool down).
  2. Turn off battery charger AC and disconnect negative battery cable.
  3. Remove enclosure side panel to access main circuit breaker box.
  4. Place circuit breaker handle in OFF position.
  5. Remove four bolts holding circuit breaker cover.
  6. Connect conductors to load-side terminals, neutral lug, and grounding lug.
  7. Torque circuit breaker terminals per breaker label.
  8. Torque neutral lug to 31.1 Nm (275 in-lb).
  9. Torque equipment grounding lug to 13.8 Nm (120 in-lb).
  10. Fill stub-up openings with duct seal or mastic tape.
  11. Install circuit breaker cover.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Neutral lug 31.1 Nm (275 in-lb)
  • Ground lug 13.8 Nm (120 in-lb)

Full service-parts list: Cummins/Onan C25 D6 →, Cummins/Onan C35 D6 →, Cummins/Onan C50 D6 →, Cummins/Onan C60 D6 →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.