Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 150 kW |
| Standby kVA | 188 |
| Prime power | 135 kW |
| Emissions | EPA NSPS Stationary Emergency Tier 3 |
| Controller | PowerCommand 1.1, PowerCommand 1.1 (optional PowerCommand 2.2) |
| Oil capacity | 17.5 L |
| Voltage options | 120/208 V, 127/220 V, 139/240 V, 220/380 V, 240/416 V, 254/440 V, 277/480 V, 347/600 V, 120/240 V |
| Phase | Three phase |
| Power factor | 0.8 |
| Battery cranking | 1100 amps minimum at ambient temperature of -18 °C to 0 °C (0 °F to 32 °F) CCA |
| Battery voltage | 12 volt, negative ground V |
| Coolant capacity | 23 L |
| Max ambient | 50 °C |
| Dimensions (L×W×H) | 2656×1100×1549 mm |
| Dry weight | 1263 kg |
| Wet weight | 1263 kg |
Engine
| Oil capacity | 17.5 L |
|---|---|
| Coolant capacity | 23.0 L |
| Displacement | 6.7 L |
| Aspiration | Turbocharged and air-to-air after-cooled |
| Rated speed | 1800 rpm |
Maintenance & consumables
for the Cummins/Onan qsb7g5nr3| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Battery | 12 | — | |||
| Coolant | -45 | — |
Service specifications
21| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Other | AC waveform Total Harmonic Distortion (THDV) | < 5% no load to full linear load, < 3% for any single harmonic | ||
| Other | AC waveform total harmonic distortion | < 5% no load to full linear load, < 3% for any single harmonic | % | |
| Other | Compression ratio | 17.2:1 | ||
| Other | Governor regulation class | ISO 8528 Part 1 Class G3 | ||
| Other | Telephone harmonic factor (THF) | < 3 | ||
| Other | Telephone influence factor (TIF) | < 50 per NEMA MG1-22.43 | ||
| Pressure | Maximum air cleaner restriction | 3.7 | kPa | |
| Pressure | Maximum back pressure | 10 | kPa | |
| Pressure | Maximum cooling air flow static restriction | 0.12 | kPa | |
| Pressure | Maximum fuel inlet restriction with clean filter | 127 | mm Hg | with clean filter |
| Pressure | Maximum return restriction | 152 | mm Hg | |
| Speed | Frequency regulation | Isochronous | ||
| Speed | Governor regulation class | ISO8528 Part 1 Class G3 | ||
| Speed | Overspeed limit | 2100 | rpm | |
| Speed | Random frequency variation | ± 0.25 | % | |
| Speed | Random frequency variation | ± 0.25% | % | |
| Temperature | Standard temperature rise | 150 | °C | Standby at 40 °C ambient |
| Voltage | Random voltage variation | ± 0.5 | % | |
| Voltage | Random voltage variation | ± 0.5% | % | |
| Voltage | Voltage regulation, no load to full load | ± 1% | % | |
| Voltage | Voltage regulation, no load to full load | ± 1.0 | % | no load to full load |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Recommended fluids
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Fuel | Number 2 diesel fuel | Direct injection; single element, 10 micron filtration, spin-on fuel filter with water separator; automatic electric fuel shutoff |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
How many kW is the Cummins/Onan DSGAC?
The Cummins/Onan DSGAC is rated 150 kW standby (188.0 kVA).
What engine is in the Cummins/Onan DSGAC?
The Cummins/Onan DSGAC is powered by the Cummins/Onan qsb7g5nr3 engine.
What kind of fuel does the Cummins/Onan DSGAC run on?
The Cummins/Onan DSGAC runs on Diesel.
What is the oil capacity of the Cummins/Onan DSGAC?
The Cummins/Onan qsb7g5nr3 engine in the Cummins/Onan DSGAC has an oil capacity of 17.5 liters.
How much coolant does the Cummins/Onan DSGAC hold?
The Cummins/Onan DSGAC cooling system holds 23 liters (6.1 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the continuous rating of the Cummins/Onan DSGAC?
The Cummins/Onan DSGAC is rated 135 kW prime (169 kVA), against 150 kW standby.
How much does the Cummins/Onan DSGAC weigh?
The Cummins/Onan DSGAC has a dry weight of 1263 kg (2784 lb).
What voltage does the Cummins/Onan DSGAC produce?
The Cummins/Onan DSGAC is offered in 120/208 V, 127/220 V, 139/240 V, 220/380 V, 240/416 V, 254/440 V, Three phase-phase.
How many cold cranking amps does the Cummins/Onan DSGAC require?
The Cummins/Onan DSGAC uses 12 volt, negative ground V each, 1100 amps minimum at ambient temperature of -18 °C to 0 °C (0 °F to 32 °F) CCA, per the manufacturer specification sheet.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 25% | 17.7 | 3.88 |
| Prime | 50% | 23.9 | 6.32 |
| Prime | 75% | 33.2 | 8.77 |
| Prime | 100% | 40.9 | 10.81 |
| Standby | 25% | 15.4 | 4.08 |
| Standby | 50% | 26.3 | 6.94 |
| Standby | 75% | 35.9 | 9.49 |
| Standby | 100% | 44.4 | 11.73 |
Available documents
This page was generated from the 7 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.