Specifications
| Fuel | Liquid Propane, Natural Gas |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 100 kW |
| Standby kVA | 123 |
| Emissions | EPA |
| Controller | Enovations 4G LDI, PC 1.1, PC 2.3, PowerCommand 1.1 |
| Oil capacity | 15.1 L |
| Voltage options | 120/240 V, 227/480 V, 347/600 V, 120/208 V, 127/220 V |
| Phase | 1-phase,3-phase |
| Battery group | 34 |
| Battery cranking | 850 CCA |
| Battery voltage | 12 V |
| Coolant capacity | 16 L |
| Max ambient | 40 °C |
| Dimensions (L×W×H) | 2489×1016×1473 mm |
| Dry weight | 1233 kg |
Engine
| Oil capacity | 15.1 L |
|---|---|
| Coolant capacity | 16.0 L |
| Displacement | 5.88 L |
| Aspiration | Naturally aspirated or turbocharged (varies by generator set model) |
| Rated speed | 1800 rpm |
Maintenance & consumables
for the Cummins/Onan QSJ5.9G| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | — | 250 hr | |||
| Fuel filter | Check fuel lines and hoses: Visually check for leaks, worn or damaged hoses. To replace, contact your authorized distributor. | — | 24 hr | ||
| Oil filter | Replace engine oil and filters. Refer to the Engine Oil section for the procedure. | — | 250 hr | ||
| Battery | Check battery for general condition. Remove any corrosion on terminals with wire brush. | — | 50 hr | ||
| Belt | Checking drive belt condition and tension: Visually check belt for evidence of wear or slippage. To replace, contact your authorized distributor. | — | 24 hr | ||
| Coolant | Starts to open within 2 °F (1 °C) of 180 °F (82 °C); Fully open within 2 °F (1 °C) of 203 °F (95 °C); Flow valve and flange clearance (minimum): 0.26 in (6.6 mm) | — | 500 hr | ||
| Oil | Replace engine oil and filters. Refer to the Engine Oil section for the procedure. | — | 250 hr | ||
| Spark plug | 38 Nm (28 lb-ft) | — | 500 hr |
Common questions
How many kW is the Cummins/Onan C100 N6?
The Cummins/Onan C100 N6 is rated 100 kW standby (123.3 kVA).
Which engine powers the Cummins/Onan C100 N6?
The Cummins/Onan C100 N6 is powered by the Cummins/Onan QSJ5.9G engine.
What kind of fuel does the Cummins/Onan C100 N6 run on?
The Cummins/Onan C100 N6 runs on Liquid Propane, Natural Gas.
What is the oil capacity of the Cummins/Onan C100 N6?
The Cummins/Onan QSJ5.9G engine in the Cummins/Onan C100 N6 has an oil capacity of 15.1 liters.
What is the cooling system capacity of the Cummins/Onan C100 N6?
The Cummins/Onan C100 N6 cooling system holds 16 liters (4.2 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the dry weight of the Cummins/Onan C100 N6?
The Cummins/Onan C100 N6 has a dry weight of 1233 kg (2718 lb).
What voltages is the Cummins/Onan C100 N6 available in?
The Cummins/Onan C100 N6 is offered in 120/240 V, 227/480 V, 347/600 V, 120/208 V, 127/220 V, 1-phase,3-phase-phase.
What battery does the Cummins/Onan C100 N6 use?
The Cummins/Onan C100 N6 uses 12 V each, 850 CCA, group 34, per the manufacturer specification sheet.
Troubleshooting
6Symptoms & remedies
| Symptom | Cause | Remedy |
|---|---|---|
| Low AC Voltage at Startup | Loss of residual magnetism in the exciter stator lamination | Restore magnetism: attach leads to a 12VDC battery with a diode in one lead; run the generator at rated speed, no load; briefly (maximum one second) connect positive lead to control board terminal F1: P17-1 and negative lead to control board terminal F2: P17-2 |
| Unstable Voltage (No Load) | Engine governing unstable | Check for engine governor hunting with a frequency meter or tachometer, or cyclic irregularities in the engine with InPower; if any engine DTC fault codes are present, troubleshoot them using the E-Controls manual; check fuel supply pressure to ensure that it is consistent; ensure that the throttle assembly moves freely, clean it if necessary; check the spark plugs for buildup, ensure that a spark is present at each cylinder, repair or replace them if necessary; check for any exhaust restriction, clean or replace components as necessary; check for an intake leak, repair or replace components as necessary; check for proper function of the crankshaft and camshaft position sensors, and the wiring to the ECM from the sensors, repair or replace components as necessary; check the fuel mix control valve for proper operation, such that it can move freely and easily, clean or replace the valve if necessary |
| Unstable Voltage (No Load) | Loose or corroded connections | Check electrical connectors on terminals on the control board; check auxiliary terminals for loose connections; repair or replace as necessary |
| Unstable Voltage (No Load) | Intermittent ground on machine | Megger test all the windings, including the exciter stator; low insulation resistance can affect the PCC (disconnect the PCC before megger test) |
| Unbalanced Voltage (With Load) | Alternator loads unbalanced | Check that loads are balanced on each leg of alternator output (L1, L2, L3) |
| Unbalanced Voltage (With Load) | Engine governing unstable | Check for engine governor hunting with a frequency meter or tachometer, or cyclic irregularities in the engine with InPower; if any engine DTC fault codes are present, troubleshoot them using the E-Controls manual; check fuel supply pressure to ensure that it is consistent; ensure that the throttle assembly moves freely, clean it if necessary; check the spark plugs for buildup, ensure that a spark is present at each cylinder, repair or replace components as necessary; check for any exhaust restriction, clean or replace components as necessary; check for an intake leak, repair or replace components as necessary; check for proper function of the crankshaft and camshaft position sensors, and the wiring to the ECM from the sensors, repair or replace components as necessary; check the fuel mix control valve for proper operation, such that it can move freely and easily, clean or replace the valve if necessary |
Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing. Full Cummins/Onan C100 N6 troubleshooting guide (145 entries) →
Parts
4| Part # | Description | Qty | System | |
|---|---|---|---|---|
| A026M166 | accessory seal kit | Seal | Amazon eBay | |
| B180313494 | Onan C50N6 March Inspection | 1 | Service type | Amazon eBay |
| 3824510 | Cummins electronic cleaner | 1 | Service part / kit | Amazon eBay |
| A047A982 | EControls GCP E-Com USB interface cable | Service part / kit | Amazon eBay |
Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 100% | 7.77 | 2.05 |
Available documents
This page was generated from the 8 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.