PC 1.1 Controller

The PC 1.1 is a generator-set controller. It is used on generator sets from Cummins/Onan, including the C10 D6, C100 N6, C15 D6 and C20 D6.

16
Generator sets
Cummins/Onan
Brand
10–100 kW
Power range
2
Fuel types

Troubleshooting

19

Fault codes

CodeMeaning
2972Field Overload (Shutdown)
5134Unknown Shutdown at Idle
5365Fault Code on Secondary Source (Information that the Fueling Has Been Shifted to Secondary Source)
5669Engine Combustion (Shutdown)
6518Cold Start Idle Active (Event)
Code 141- Oil pressure sensor output out of range low
Code 143- Engine oil pressure low (warning)
Code 144- Engine coolant temperature out of range low (warning)

Symptoms & remedies

SymptomRemedy
Emergency stop signal is receivedThe generator set immediately shuts down and cannot run or crank with the E-stop switch engaged.
High coolant temperature warning/shutdownLevel is pre-set to match the capabilities of the engine used. Control includes time delays to prevent nuisance shutdown signals.
Low coolant temperature warningIndicates that engine temperature may not be high enough for 1 min. and start or proper load acceptance.
Low lube oil pressure warning/shutdownLevel is pre-set to match the capabilities of the engine used. Control includes time delays to prevent nuisance shutdown signals.
Over/under frequency sensor overfrequency sensing dropout adjustable from 105-115% of nominalDropout adjustable delay from 0.1-15 sec.
Over/under frequency sensor underfrequency sensing pickup and dropout adjustable from 85-100% and 70-85%Dropout adjustable delay from 0.1-15 sec.
Overvoltage sensor dropout adjustable from 105-135% of nominalDropout adjustable delay from 0.5-120 sec.
Sensor failure indicationLogic is provided on the base control to detect analog sensor or interconnecting wiring failures.
Time delay of 0-600 seconds prior to shutdown after signal to stop in normal operation modesDefault for both time delay periods is 0 seconds.
Time delay start and stop (cooldown) configurable for time delay of 0-300 seconds prior to starting after receiving a remote start signalControl provides retransfer time delays including time delay emergency to normal (0-1800 sec), programmed transition delay (0-600 sec), and time delay engine cooldown (0-3600 sec).
Undervoltage sensor pickup and dropout adjustable from 85-100% and 75-98%Dropout adjustable delay from 0.1-30 sec.

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.