Cummins/Onan QSJ5.9G Engine

The Cummins/Onan QSJ5.9G is a 5.88 L 6-cylinder naturally aspirated or turbocharged (varies by generator set model) engine rated at 1800 rpm. It powers generator sets from Cummins/Onan, including the C100 N6, C45 N6, C50 N6 and C60 N6. It holds 15.1 L (4.0 gal) of oil and 16 L (4.2 gal) of coolant.

Also known as: Cummins QSJ5.9G

Part of the Cummins/Onan QSJ5.9 engine family — 4 variants share parts & fitment.

5.88 L
Displacement
6
Cylinders
1800 rpm
Rated speed
15.1 L
Oil capacity

Engine specifications

Oil capacity15.1 L
Coolant capacity16.0 L
Displacement5.88 L
Cylinders6
AspirationNaturally aspirated or turbocharged (varies by generator set model)
Rated speed1800 rpm

Common problems

15
  • Engine Oil Pressure Low (Shutdown) — Engine oil pressure is below the low oil pressure shutdown threshold (less than 10 psig for more than 2 seconds) 415
    Cause: Lubricating oil level is low
    Fix: Check the oil level; add or drain oil, if necessary
  • Engine Coolant Temperature Above Normal (Warning) — Engine coolant temperature has exceeded the warning threshold (220 °F [105 °C]) for high coolant temperature 146
    Cause: High ambient temperature
    Fix: Measure the air temperature entering the air intake louver of the generator set enclosure if enclosed, or cooling air to the radiator if not enclosed; verify the expected cooling system ambient temperature capability; inspect for recirculation of cooling discharge air into the generator set enclosure air inlet or the area surrounding the radiator cooling air inlet
  • Mechanical or internal component wear or damage
    Cause: Internal engine damage
    Fix: Analyze the oil and inspect the filters to locate an area of probable damage; inspect and further investigate area of probable damage
  • Fuel Consumption Is Excessive
    Cause: Excessive loads
    Fix: Make sure that the load on the generator set does not exceed the generator set kW rating; re-visit the generator set sizing process to make sure that the generator set is correctly sized for the application, especially if new loads have been introduced into the system; refer to the T-030 manual for proper generator set sizing and application
  • Fuel Pressure Low — This fault is used when an optional low fuel pressure switch is installed 2118
    Cause: Low fuel pressure
    Fix: Check fuel supply and change as required
  • Engine Shuts Off Unexpectedly or Dies during Deceleration
    Cause: Emergency Stop (if used)
    Fix: Make sure that the Emergency Stop circuit is not energized
  • Engine Is Difficult to Start or Does Not Start
    Cause: Battery voltage is low, interrupted, or open
    Fix: Check the battery connections, unswitched battery supply circuit, and fuses; correct or replace if necessary
  • Engine Experiences Low Power, Poor Acceleration, or Poor Response
    Cause: Excessive load
    Fix: Ensure that the load on the generator set does not exceed the generator set kW rating; revisit the generator set sizing process to ensure that the generator set is correctly sized for the application, especially if new loads have been introduced into the system
  • Unstable Voltage (With Load)
    Cause: Engine governing unstable
    Fix: Refer to the engine service manual (if applicable) or E-Controls service manual
  • Poor Voltage Regulation (With Load)
    Cause: Unbalanced load
    Fix: Check voltage and load current on all phases; if unbalanced, redistribute the load more evenly across the phases
  • Low Fuel (Warning or Shutdown) — This fault is used when an optional low fuel level switch is installed 1318
    Cause: Low fuel pressure
    Fix: Measure the fuel pressure at the fuel pump inlet
  • Engine Starts but Will Not Keep Running
    Cause: Battery voltage is low, interrupted, or open
    Fix: Check the battery connections, unswitched battery supply circuit, and fuses; correct or replace if necessary
  • Engine Runs Rough or Misfires
    Cause: Ignition system issues
    Fix: Inspect the spark plugs, clean or replace the spark plugs if necessary; test the ignition coils using a coil on a plug tester (or in-line spark tester) to isolate the faulty coil, replace the faulty coil if necessary; check the coil wiring, inspect connectors and wires for breaks, and test continuity
  • Unstable Voltage (No Load)
    Cause: Engine governing unstable
    Fix: Check for engine governor hunting with a frequency meter or tachometer, or cyclic irregularities in the engine with InPower; if any engine DTC fault codes are present, troubleshoot them using the E-Controls manual; check fuel supply pressure to ensure that it is consistent; ensure that the throttle assembly moves freely, clean it if necessary; check the spark plugs for buildup, ensure that a spark is present at each cylinder, repair or replace them if necessary; check for any exhaust restriction, clean or replace components as necessary; check for an intake leak, repair or replace components as necessary; check for proper function of the crankshaft and camshaft position sensors, and the wiring to the ECM from the sensors, repair or replace components as necessary; check the fuel mix control valve for proper operation, such that it can move freely and easily, clean or replace the valve if necessary
  • Remote E-Stop — The state of the Remote Emergency Stop has been changed 1434
    Cause: The Remote Emergency Stop button has been activated
    Fix: Reset the Remote Emergency Stop

Compiled from service & troubleshooting documentation across every generator set that uses the Cummins/Onan QSJ5.9G.

Maintenance schedule

ItemSpecCapacityPart #Interval
Air filterReplace air cleaner.—250 hr
Fuel filterCheck fuel lines and hoses: Visually check for leaks, worn or damaged hoses. To replace, contact your authorized distributor.—24 hr
Oil filterReplace engine oil and filters. Refer to the Engine Oil section for the procedure.—250 hr
BatteryCheck battery: Check connections to verify that they are secure.—50 hr
BeltChecking drive belt condition and tension: Visually check belt for evidence of wear or slippage. To replace, contact your authorized distributor.—24 hr
CoolantReplace cooling system coolant. Check coolant sensor for damage and debris.—500 hr
OilReplace engine oil and filters. Refer to the Engine Oil section for the procedure.—250 hr
Spark plugReplace spark plugs and spark plug wires.—500 hr

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Service intervals

3
ItemActionHoursMonthsNotes
External load bank testTest2 hrLoad generator to 100% of rated load for a period of two (2) hours; provide complete report with recommendations
Generator transfer switch testingTest6 moTesting of the generator transfer switch to be completed bi-annually on each generator
Preventative maintenanceOther6 moRequired semi-annually for: Ingersol-Rand Trailer; Kohler Trailer; Service Center - PW; South WWTP; North WWTP; Pine Street Water Well; Water Well 5 & 6

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Coolant50/50 mixturebelow 50°CEngine coolant – 50/50 mixture; generator set cooling capability 50 oC

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

2
Preventative Maintenance Tasks (Quarterly and Semi-Annual) maintenance
  1. Replace oil, air, water, and fuel filters with new filters, if needed
  2. Check and tighten all electrical connections on generators
  3. Check and clean battery connections; check and record battery charge rates
  4. Start and load generator; while running check and record coolant temperature
  5. Check function of day tank pump
  6. Check voltage and hertz; adjust if needed
  7. Check for exhaust leaks
  8. Check fuel level
  9. Check all fluid levels
  10. Check for fluid leaks
  11. Check and tighten all belts; replace if necessary
  12. Provide report listing conditions of all systems
  13. Tighten all electrical connections in transfer switches; may require non-business hours at no additional charge
  14. Provide one (1) external load bank test to 100% of rated load for two (2) hours; provide complete report with recommendations
  15. Test the generator transfer switch bi-annually on each generator
Scheduled Maintenance Tasks (Requested) maintenance
  1. Start and run generator unloaded
  2. Check voltage and frequency; adjust if necessary
  3. Check all fluid levels
  4. Check for fluid leaks
  5. Check and adjust all belts, if necessary
  6. Oil changes based on run times/month
  7. Provide report listing conditions of all systems

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Parts cataloged across the Cummins/Onan QSJ5.9 family

4
Part #DescriptionCategory
3824510Cummins electronic cleanerService part / kit
A047A982EControls GCP E-Com USB interface cableService part / kit
A026M166accessory seal kitSeal
B180313494Onan C50N6 March InspectionService type

Parts cataloged across all variants of this engine family — verify the exact part fits your specific variant and serial number before ordering.

Common questions

What is the oil capacity of the Cummins/Onan QSJ5.9G?

The Cummins/Onan QSJ5.9G engine has an oil capacity of 15.1 liters.

What is the displacement of the Cummins/Onan QSJ5.9G?

The Cummins/Onan QSJ5.9G has a displacement of 5.88 liters with 6 cylinders.

Which generators use the Cummins/Onan QSJ5.9G engine?

The Cummins/Onan QSJ5.9G powers 6 generator set(s), including Cummins/Onan C100 N6, Cummins/Onan C45 N6, Cummins/Onan C50 N6, Cummins/Onan C60 N6, Cummins/Onan C70 N6.

How often should you change the oil in the Cummins/Onan QSJ5.9G?

The Cummins/Onan QSJ5.9G oil change interval is every 250 hours.

What is a common problem with the Cummins/Onan QSJ5.9G engine?

A commonly reported issue on generators using the Cummins/Onan QSJ5.9G is: Engine Oil Pressure Low (Shutdown) — Engine oil pressure is below the low oil pressure shutdown threshold (less than 10 psig for more than 2 seconds). Cause: Lubricating oil level is low. Fix: Check the oil level; add or drain oil, if necessary.