Home›Controllers›Enovations 4G LDI

Enovations 4G LDI Controller

The Enovations 4G LDI is a generator-set controller. It is used on generator sets from Cummins/Onan, including the C100 N6, C70 N6 and C80 N6.

5
Generator sets
Cummins/Onan
Brand
70–100 kW
Power range
Bi-Fuel (NG/LP)
Fuel

Engines paired with this controller

2

Troubleshooting

60

Fault codes

CodeMeaningCauseRemedy
1117ECM Power Lost — "keyswitch" to the Engine Control Module (ECM) was not removed for 30 seconds before removing battery power to the ECM (removing connectors or battery cable)ECM power lostTo reset, press the Off button, press the Emergency Stop button, and wait 30 seconds
1244Engine Normal Shutdown — The engine has received a normal shutdown requestThe generator set is going through a normal shutdownThe generator set is going through a normal shutdown and there are no active shutdown fault(s) in the ECM for at least 2 seconds
1245Engine Shutdown Fault — An engine shutdown fault has occurred in the Engine Control Module (ECM), and no other active shutdown faults exist on the PCCEvent/fault code 1245 is activated by another active shutdown fault in the ECMConnect to the ECM with E-Controls GCP Display or 4G Display to determine the actual shutdown fault that is generating event/fault code 1245; troubleshoot the shutdown fault(s)
1246CAN Unknown Engine Fault — The PCC received an unknown message from the ECMECM/engine faultRefer to the E-Controls service tool
1248Engine Warning — An engine warning fault has occurred in the Engine Control Module (ECM), and there are no active warning faults on the PCCAnother active warning fault in the ECM activates event/fault code 1248Connect to the ECM with E-Controls GCP Display or 4G Display to determine the actual warning fault that is generating event/fault code 1248; troubleshoot the shutdown fault(s)
1311Customer Input #1 (Warning or Shutdown) — The nature of the fault is an optional customer selectionProgram the fault function using the InPower service tool: enable/disable input (default: enable); status, warning, or shutdown (default: #1-None, #2-Warning and #3-Warning); active closed or open (default: closed [ground])
1312Customer Input #2 (Warning or Shutdown) — The nature of the fault is an optional customer selectionProgram the fault function using the InPower service tool: enable/disable input (default: enable); status, warning, or shutdown (default: #1-None, #2-Warning and #3-Warning); active closed or open (default: closed [ground])
1318Low Fuel (Warning or Shutdown) — This fault is used when an optional low fuel level switch is installedLow fuel pressureMeasure the fuel pressure at the fuel pump inlet
135Oil Pressure Sensor OOR - High — Engine oil pressure sensor signal is out of range – shorted highFaulty oil pressure sensor and/or circuit; Faulty ECM; Faulty ECM connection or harness
1417Power Down Failure — The PCC has failed to go to sleepIncorrect calibrations in PowerCommand controlsUsing the display or the InPower Service tool, verify the calibration in the PCC; if the calibration in the PCC matches the latest calibration on the InCal website, then the calibration is correct, if it does not, update the calibration to the latest
1433Local E-Stop — The state of the Local Emergency Stop (E-Stop) has been changedThe local E-Stop button has been activatedReset the Local E-Stop: pull the Local E-Stop button out; press the Off button; press the Reset button; select Manual or Auto as required
1434Remote E-Stop — The state of the Remote Emergency Stop has been changedThe Remote Emergency Stop button has been activatedReset the Remote Emergency Stop
144Engine Coolant Temperature OOR Low (Warning) — Engine coolant temperature signal voltage is out of range - shorted lowFor the troubleshooting procedure, refer to DTC 118 in the E-Controls Service Manual
145Engine Coolant Temperature OOR High (Warning) — Engine coolant temperature signal voltage is out of range - shorted highFor the troubleshooting procedure, refer to DTC 117 in the E-Controls Manual
146Engine Coolant Temperature Above Normal (Warning) — Engine coolant temperature has exceeded the warning threshold (220 °F [105 °C]) for high coolant temperatureHigh ambient temperatureMeasure the air temperature entering the air intake louver of the generator set enclosure if enclosed, or cooling air to the radiator if not enclosed; verify the expected cooling system ambient temperature capability; inspect for recirculation of cooling discharge air into the generator set enclosure air inlet or the area surrounding the radiator cooling air inlet
151Engine Coolant Temperature High (Shutdown) — The engine coolant temperature has exceeded the alarm (shutdown) threshold for high coolant temperatureFor the troubleshooting procedure, refer to DTC 217 in the E-Controls Manual
153Intake Manifold Temperature OOR High (Warning) — Engine intake manifold temperature sensor signal is out of range – shorted highFor the troubleshooting procedure, refer to DTC 113 in the E-Controls Manual
154Intake Manifold Temperature OOR Low (Warning) — Engine intake manifold temperature sensor signal is out of range – shorted lowFor the troubleshooting procedure, refer to DTC 112 in the E-Controls Manual
155Intake Manifold Temperature High (Shutdown) — The engine intake manifold temperature has exceeded 95 °C (203 °F) for greater than 10 secondsFor the troubleshooting procedure, refer to DTC 127 in the E-Controls Manual
1855Customer Input 3 — Event/fault code 1855 (customer input 3) becomes active when there is a ground input at TB1-3 on the back of the universal annunciatorIncorrect annunciator configuration or wiring; Faulty sender, relay, or device activating Input 3; Faulty annunciatorMake sure that the universal annunciator is correctly configured; check the wiring at TB1-3 and make sure that customer input 3 is wired correctly, make sure that there is not a short or open circuit at the TB1-3 connection; check the sender, relay, or device that is activating Input 3 on the universal annunciator, replace if faulty; if the wiring and configuration is satisfactory, replace the universal annunciator
1944Annunciator Configuration Error (Warning) — More than one network device is configured to activate one of the annunciator output relaysBad network configurationCheck the setup of devices on the network against duplicate use of the same annunciator relay output
2118Fuel Pressure Low — This fault is used when an optional low fuel pressure switch is installedLow fuel pressureCheck fuel supply and change as required
2335Excitation Fault (Loss of AC Sense) — The control has lost voltage sensing or has lost zero cross sensingIncorrect configuration; Bad fuse; Bad wire harness or wrong connections; Low resistance
234Engine Speed High (Shutdown) — Engine speed signals indicate an engine speed greater than the shutdown thresholdFaulty Hall Effect (HE) sensor connections and wiring; Faulty HE sensor; Fault simulation feature is enabled; Incorrect threshold setting; Incorrect settings on the E-controls
2677Fail to Stop (Shutdown) — The generator set continues to run after receiving shutdown command from the controllerStuck fuel shutoff (FSO) valveCheck keyswitch operation and make sure it is not stuck closed (use a multimeter and check continuity across the relay K3-1 and K3-4; with the Emergency stop pressed, the relay should be open); check for a stuck FSO valve, check the FSO relay and related wiring, check that the FSO is not mechanically stuck; if issue persists, consult DTC 1181 in the E-Controls manual
2729IO Module Lost (Warning) — There is an intermittent data link between the I/O module and the PCC control (Aux 101 I/O Module option) and no input fault levels were set to ShutdownIncorrect wiringThe connection between AUX 101 and PCC 1302 is incorrect; make sure there is proper wiring: PCC 1302 TB1-1 – PCC Net A (+) to AUX 101 J1-3; PCC 1302 TB1-2 – PCC Net B (-) to AUX 101 J1-4; PCC 1302 TB1-3 – B+ Return to AUX 101 J14-2; PCC 1302 TB1-5 – Customer Fused B+ to AUX 101 J14-1; PCC 1302 TB15-5 – System Wake-up to AUX 101 J1-5
2731IO Module Lost (Shutdown) — Indicates an intermittent data link between the I/O module and the PCC control (Aux 101 I/O Module option) and at least one input fault level was set to ShutdownIncorrect wiringThe connection between AUX 101 and PCC 1302 is incorrect; make sure there is proper wiring: PCC 1302 TB1-1 – PCC Net A (+) to AUX 101 J1-3; PCC 1302 TB1-2 – PCC Net B (-) to AUX 101 J1-4; PCC 1302 TB1-3 – B+ Return to AUX 101 J14-2; PCC 1302 TB1-5 – Customer Fused B+ to AUX 101 J14-1; PCC 1302 TB15-5 – System Wake-up to AUX 101 J1-5
286CAN Address Conflict Failure (Warning) — There are two or more devices on the network use the same source addressFor the troubleshooting procedure, refer to DTC 1628 in the E-Controls Manual; if another Cummins device is found to have the same slave address, refer to that service manual for that device to change the slave address
2897Factory Memory Block Corrupt — The control has detected a corrupted memory blockDefective memory blockConnect to device using InPower version 10.0 or greater; in InPower, right click on the device, and select Initial Calibration (Recover Device) from the menu that appears; if the capture file for the device is available, select "overlay capture file", if not, select feature codes (feature codes can be found on the nameplate of the device, located on the alternator housing); if the problem persists, contact the factory for support
2898Periodic or Fault Memory Block Corrupt — The control has detected a corrupted memory blockDefective memory blockConnect to the device using InPower version 10.0 or greater; in InPower, right click on the device, and select Initial Calibration (Recover Device) from the menu that appears; if the capture file for the device is available, select "overlay capture file", if not, select feature codes (feature codes can be found on the nameplate of the device, located on the alternator housing); if the problem persists, contact the factory for support
2899User Memory Block Corrupt — The control has detected a corrupted memory blockDefective memory blockConnect to the device using InPower version 10.0 or greater; in InPower, right click on the device, and select Initial Calibration (Recover Device) from the menu that appears; if the capture file for the device is available, select "overlay capture file", if not, select feature codes (feature codes can be found on the nameplate of the device, located on the alternator housing); if the problem persists, contact the factory for support
2911Trim Memory Block Corrupt — The control has detected a corrupted memory block
2964Intake Air Temperature Higher than Expected — The manifold air temperature exceeds 94 °C (200 °F) for more than 60 seconds, while the engine is running (DTC 111 active).Exhaust air entering intakeInspect the exhaust system for leaks. Check the exhaust manifold gaskets, turbo gasket (if equipped), and exhaust tubing for holes or escaping exhaust. Replace the faulty component(s) if necessary; The unit is not properly ventilated. Make sure that the unit is greater than 5 feet from any obstruction. For units located inside of a structure, make sure that exhaust gases do not exit within 5 feet of the intake for the structure or generator set. For enclosed sets, make sure that there are no objects blocking the exhaust opening on the top of the enclosure, or objects that may redirect exiting airflow towards the intake end of the unit.
2972Field Overload (Shutdown) — If the time that the Field AVR Duty Cycle is operating at maximum output is longer than the time in the "Max Field Time" parameter, event/fault code 2972 will become active.Voltage sensing into the baseboard is too low, or there is an open/short circuit
359Fail to Start — The engine failed to start after the expiration of crank timeFuel system issuesInspect fuel lines and fuel connections for leaks; repair if leaks are found; the manual fuel shutoff (FSO) valve is closed - open the valve; the FSO valve solenoids or circuit are malfunctioning - check the FSO valve solenoids and circuit, correct or replace as necessary
415Engine Oil Pressure Low (Shutdown) — Engine oil pressure is below the low oil pressure shutdown threshold (less than 10 psig for more than 2 seconds)Lubricating oil level is lowCheck the oil level; add or drain oil, if necessary
5134Unknown Shutdown at Idle
5365Fault Code on Secondary Source (Information that the Fueling Has Been Shifted to Secondary Source)
5669Engine Combustion (Shutdown)
6518Cold Start Idle Active (Event)
Code 141- Oil pressure sensor output out of range low
Code 143- Engine oil pressure low (warning)
Code 144- Engine coolant temperature out of range low (warning)

Symptoms & remedies

SymptomCauseRemedy
Alternator output (amps) not within 10% of rated outputRepair or replace the alternator; refer to the alternator manufacturer's instructions for repair procedures
Defective memory blockConnect to the device using InPower version 10.0 or greater; In InPower, right click on the device, and select Initial Calibration (Recover Device) from the menu that appears; If the capture file for the device is available, select "overlay capture file". If not, select feature codes. Feature codes can be found on the nameplate of the device, located on the alternator housing; If the problem persists, contact the factory for support.
Engine Does Not Crank in Remote Mode (No Fault Message)Faulty remote start customer wiringReset the control; attempt to start and check for wiring connections; if ground is not present, isolate to the remote switch or customer wiring, repair if necessary
Engine Experiences Low Power, Poor Acceleration, or Poor ResponseExcessive loadEnsure that the load on the generator set does not exceed the generator set kW rating; revisit the generator set sizing process to ensure that the generator set is correctly sized for the application, especially if new loads have been introduced into the system
Engine Is Difficult to Start or Does Not StartBattery voltage is low, interrupted, or openCheck the battery connections, unswitched battery supply circuit, and fuses; correct or replace if necessary
Engine Noise Is ExcessiveAir intake or exhaust leaksInspect the air intake and exhaust systems for air leaks; replace the muffler if necessary
Engine Runs Rough or MisfiresIgnition system issuesInspect the spark plugs, clean or replace the spark plugs if necessary; test the ignition coils using a coil on a plug tester (or in-line spark tester) to isolate the faulty coil, replace the faulty coil if necessary; check the coil wiring, inspect connectors and wires for breaks, and test continuity
Engine Shuts Off Unexpectedly or Dies during DecelerationEmergency Stop (if used)Make sure that the Emergency Stop circuit is not energized
Engine Speed Surges Under Load or in Operating RangeFuel system issuesInspect fuel lines and connections for leaks (spray soapy water along the lines and at connection, bubbling indicates a likely leak location), repair if leaks are found; check for fault codes using the E-Controls tool and troubleshoot as specified in the E-Controls manual, inspect the bore of the throttle body, clean if necessary or replace if worn; inspect the pressure regulator and EPR assembly for damage, the valve located inside the assembly should move freely, clean or replace if necessary
Engine Starts but Will Not Keep RunningBattery voltage is low, interrupted, or openCheck the battery connections, unswitched battery supply circuit, and fuses; correct or replace if necessary
Engine Will Not Shut OffRun/Stop circuit issueCheck the alternator Run/Stop circuit; correct or replace if necessary
Fuel Consumption Is ExcessiveExcessive loadsMake sure that the load on the generator set does not exceed the generator set kW rating; re-visit the generator set sizing process to make sure that the generator set is correctly sized for the application, especially if new loads have been introduced into the system; refer to the T-030 manual for proper generator set sizing and application
Low AC Voltage at StartupLoss of residual magnetism in the exciter stator laminationRestore magnetism: attach leads to a 12VDC battery with a diode in one lead; run the generator at rated speed, no load; briefly (maximum one second) connect positive lead to control board terminal F1: P17-1 and negative lead to control board terminal F2: P17-2
Low compression on a single cylinderExternal cylinder head gasket leakPerform a wet compression test with liquid soap to determine if there is an external cylinder head gasket leak; if so, replace the gasket with a new one
Low compression on adjacent cylinders with no external cylinder head gasket leakHead gasket is probably leaking between the cylindersOil the rings to increase the pressure; re-check the pressure; if the pressure has still not increased, replace the gasket with a new one
Mechanical or internal component wear or damageInternal engine damageAnalyze the oil and inspect the filters to locate an area of probable damage; inspect and further investigate area of probable damage
Poor Engine Transient ResponseExcessive loadsMake sure that the load on the generator set does not exceed the generator set kW rating; re-visit the generator set sizing process to make sure that the generator set is correctly sized for the application, especially if new loads have been introduced into the system

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.