Generac Fault Codes

402 Generac generator fault/alarm codes with symptom, cause and remedy — compiled from Generac service and controller documentation.

Fault / alarm codes

402
CodeMeaning / symptomCauseRemedy Models affected
0Utility failureCrank and start engine, transfer load to Generator if Utility returns above 75% nominal for 15 secondsGenerac 10 KW, Generac 13 kW, Generac 14 kW, Generac 15 kW, Generac 16 kW, Generac 17 kW
0F9677Engine won’t crank.Replace fuse.Generac 2.4L 45kW, Generac 2.4L 60kW, Generac 45 KW, Generac 60 KW
0G0008Engine cranks but won't startTighten, clean or replace battery cables; replace starter contactor or motor; replace battery if dead.Generac 2.4L 45kW, Generac 2.4L 60kW, Generac 45 KW, Generac 60 KW
0G0056Engine cranks but won't startTighten, clean or replace battery cables; replace starter contactor or motor; replace battery if dead.Generac 2.4L 45kW, Generac 2.4L 60kW, Generac 45 KW, Generac 60 KW
1Ignition cannot initialize — LED is ON continuously during crankingGenerac 35 KW, Generac 4.2L, Generac 45 KW
1Engine won’t crank.1. Replace fuse. 2. Tighten, clean or replace battery cables as necessary. 3. Replace contactor.* 4. Replace starter motor.* 5. Remove, change or replace battery. 6. Replace fuse.*Generac 22 kW, Generac 22/27 kW, Generac 25 kW, Generac 27 kW, Generac 30 KW, Generac OMASPFY025-030S-01
1-1CO MonitorMove generator outside. Contact IASD.Generac 15,5 / 18,0 kW**, Generac GP Series Portable Generator, Generac GP18000EFI, Generac Portables
1-2Battery VoltageBattery voltage above normal operating rangeContact IASDGenerac 15,5 / 18,0 kW**, Generac GP Series Portable Generator, Generac GP18000EFI, Generac Portables
1-3Battery VoltageBattery voltage below normal operating rangeCharge battery to correct levelGenerac 15,5 / 18,0 kW**, Generac GP Series Portable Generator, Generac GP18000EFI, Generac Portables
2Engine Overspeed — LED blinks four (4) times, is OFF for three (3) seconds and then repeatsGenerac 35 KW, Generac 4.2L, Generac 45 KW
2TPS FailureGenerac XT8000E
2Engine cranks but won't start1. Replenish fuel. 2. Replace solenoid.* 3. Reconnect wire. 4. Clean, regap or replace plugs. 5. Close door on tank.Generac 22 kW, Generac 22/27 kW, Generac 25 kW, Generac 27 kW, Generac 30 KW, Generac OMASPFY025-030S-01
2 flashes of LEDOVERCRANK — 2 flashes of LEDNo fuel to the engineMake sure that the tanks are full and the valves are openedGenerac Centurion 3500
3No Crank Signal — LED blinks two (2) times, is OFF for three (3) seconds and then repeatsGenerac 35 KW, Generac 4.2L, Generac 45 KW
3Cylinder Temp. FailureGenerac XT8000E
3Engine starts hard, runs rough.Generac 22 kW, Generac 22/27 kW, Generac 25 kW, Generac 27 kW, Generac 30 KW, Generac OMASPFY025-030S-01
3Engine fault code present.See Fault Code Example or contact IASD.Generac 15,5 / 18,0 kW**, Generac GP Series Portable Generator, Generac GP18000EFI, Generac Portables
3 flashes of LEDOVERSPEED — 3 flashes of LEDGovernor spring is disconnectedReconnect spring. Spring should be in the second hole from the bottom (shaft end) of the governor armGenerac Centurion 3500
4No Cam Signal — LED blinks three (3) times, is OFF for three (3) seconds and then repeatsGenerac 35 KW, Generac 4.2L, Generac 45 KW
4Air Temp. FailureGenerac XT8000E
4Engine oil level is low.Generac 22 kW, Generac 22/27 kW, Generac 25 kW, Generac 27 kW, Generac 30 KW, Generac OMASPFY025-030S-01
4 flashes of LEDLOW OIL PRESSURE — 4 flashes of LEDEngine oil is lowCheck and fill engine oil. Check generator compartment for leaksGenerac Centurion 3500
5System Voltage LowGenerac XT8000E
5Engine is overheated.Generac 22 kW, Generac 22/27 kW, Generac 25 kW, Generac 27 kW, Generac 30 KW, Generac OMASPFY025-030S-01
5 flashes of LEDHIGH TEMPERATURE — 5 Flashes of LEDEngine oil is lowCheck and fill engine oilGenerac Centurion 3500
5-2Engine SpeedNo or low fuel; Engine speed below normal operating rangeFill fuel tank; Contact IASDGenerac 15,5 / 18,0 kW**, Generac GP Series Portable Generator, Generac GP18000EFI, Generac Portables
6System Voltage HighGenerac XT8000E
6Defective Low Oil Pressure SwitchGenerac 22 kW, Generac 22/27 kW, Generac 25 kW, Generac 27 kW, Generac 30 KW, Generac OMASPFY025-030S-01
6 flashes of LEDUNDERSPEED — 6 flashes of LEDFuel supply is lowCheck and replenish fuel supplyGenerac Centurion 3500
6-1Engine Oil PressureLow oil pressure; Switch voltage not detectedFill crankcase to correct level; Contact IASDGenerac 15,5 / 18,0 kW**, Generac GP Series Portable Generator, Generac GP18000EFI, Generac Portables
7Cylinder High Temp.Generac XT8000E
7Defective Coolant Temperature SwitchGenerac 22 kW, Generac 22/27 kW, Generac 25 kW, Generac 27 kW, Generac 30 KW, Generac OMASPFY025-030S-01
7 kWEngine will not crank.Replace 15A fuse in generator control panel.Generac 0E8012, Generac Models:, Generac Number, Generac YEAR
7.5 AMP (F1) FUSE BLOWINGENGINE WILL NOT CRANKGenerac QUIETPACT 75, Generac QuietPact 55, Generac QuietPact 65
8Barometric Pressure Sensor FailureGenerac XT8000E
8Defective Control Module circuit boardGenerac 22 kW, Generac 22/27 kW, Generac 25 kW, Generac 27 kW, Generac 30 KW, Generac OMASPFY025-030S-01
8 kWEngine cranks but will not start.Tighten, clean or replace as necessary.Generac 0E8012, Generac Models:, Generac Number, Generac YEAR
9Oil Pressure AnomalyGenerac XT8000E
9Coolant Level is Low.Generac 22 kW, Generac 22/27 kW, Generac 25 kW, Generac 27 kW, Generac 30 KW, Generac OMASPFY025-030S-01
9 kWEngine starts hard and runs rough.Generac 0E8012, Generac Models:, Generac Number, Generac YEAR
10Defective Low Coolant Level SwitchGenerac 22 kW, Generac 22/27 kW, Generac 25 kW, Generac 27 kW, Generac 30 KW, Generac OMASPFY025-030S-01
10Engine fault code present.See Fault Code Example or contact IASD.Generac 15,5 / 18,0 kW**, Generac GP Series Portable Generator, Generac GP18000EFI, Generac Portables
10 kWAuto/Off/Manual switch is set to OFF, but the engine continues to run.Generac 0E8012, Generac Models:, Generac Number, Generac YEAR
11Fuel Injector FailureGenerac XT8000E
11Defective AUTO/OFF/MANUAL switchGenerac 22 kW, Generac 22/27 kW, Generac 27 kW
11AUTO/OFF/MANUAL Switch at OFF, engine continues to run.Generac 25 kW, Generac 30 KW, Generac OMASPFY025-030S-01
11Engine fault code present.See Fault Code Example or contact IASD.Generac 15,5 / 18,0 kW**, Generac GP Series Portable Generator, Generac GP18000EFI, Generac Portables
11 kWThere is no AC output from the generator.Reset circuit breaker to ON (or closed).Generac 0E8012, Generac Models:, Generac Number, Generac YEAR
12Open/disconnected wire #15A between AUTO/OFF/MANUAL switch and Control Module circuit board.Generac 22 kW, Generac 22/27 kW, Generac 27 kW
12No AC output from generator.Generac 25 kW, Generac 30 KW, Generac OMASPFY025-030S-01
12Engine fault code present.See Fault Code Example or contact IASD.Generac 15,5 / 18,0 kW**, Generac GP Series Portable Generator, Generac GP18000EFI, Generac Portables
12 kWThere is no transfer to standby after utility source failure.Generac 0E8012, Generac Models:, Generac Number, Generac YEAR
12-1No AC output from generatorMain line circuit breaker is tripped/open. Generator internal failure. Thermal circuit breaker open.Generac 36kW Models
13Fuel Pump FailureGenerac XT8000E
13Engine starts then shuts down.Generac 22 kW, Generac 22/27 kW, Generac 27 kW
13 kWUnit consumes large amounts of oil.Generac 0E8012, Generac Models:, Generac Number, Generac YEAR
14Output FaultGenerac IQ3500
15Engine won't crank.Generac QT 6.8L 100kW
15Ignition FailureGenerac XT8000E
17ECU Internal FailureGenerac XT8000E
18Crankshaft Position Sensor FailureGenerac XT8000E
18Oil Level LowAdd oil to the specified level before restarting.Generac IQ3500
19ECU ResetGenerac XT8000E
19OverloadReduce load or check if the generator is overloaded.Generac IQ3500
22Engine Overspeed FailureGenerac XT8000E
22Oil Level LowAdd oil to the specified level before restarting.Generac IQ3500
23Electrical TripCheck the system for any faults and correct them before restarting.Generac IQ3500
24Load Stability Sensor FailureGenerac XT8000E
27Stepper Motor StuckGenerac XT8000E
28Engine Starting FailureGenerac XT8000E
057-243Generator Under Volts gives a warning alarm in the event of the generator output falling below the configured Under Volts Pre-Alarm Trip value for longer than the Activation Delay.DSE7310 MKII controller
057-243Under Speed AlarmDSE7310 MKII controller
057-243Over Speed Pre-AlarmDSE7310 MKII controller
057-243Run Away Shutdown alarm is immediately triggered.DSE7310 MKII controller
99Maintenance RequiredGenerac 2.4L 45kW, Generac 2.4L 60kW, Generac 45 KW, Generac 60 KW
180Internal Harness Loop Broken—External display board is not able to communicate with main board. This alarm is internal to the display board and is not logged (the main board is not aware of this E-Code).Generac Not explicitly stated
180Controller — Internal Harness Loop Broken—External display board is not able to communicate with main board. This alarm is internal to the display board and is not logged (the main board is not aware of this E-Code).Generac Not explicitly stated
801Engine will not crankCorrect short circuit condition, replace 7.5A fuse in generator control panel. Tighten, clean or replace battery cables as necessary. Replace defective starter contactor or motor.Generac 10 KW, Generac 13 kW, Generac 14 kW, Generac 16 kW, Generac 17 kW, Generac 18 kW NG
802Engine cranks but will not startReplenish fuel/Turn on fuel valve. Replace defective fuel solenoid or open #14 wire from engine control board. Clean, re-gap or replace spark plugs as necessary. Reset valve lash. Verify choke plate moves freely.Generac 10 KW, Generac 13 kW, Generac 14 kW, Generac 16 kW, Generac 17 kW, Generac 18 kW NG
803Engine starts hard and runs roughCheck, replace air cleaner as necessary. Clean, re-gap or replace spark plugs as necessary. Confirm fuel pressure to regulator is 10-12” water column (0.36-0.43 psi) for LP, and 5-7” water column (0.18-0.25 psi) for natural gas. Move selector to correct position. Verify choke plate moves freely.Generac 10 KW, Generac 13 kW, Generac 14 kW, Generac 16 kW, Generac 17 kW, Generac 18 kW NG
804AUTO/OFF/MANUAL switch is set to OFF, but the engine continues to runGenerac 10 KW, Generac 13 kW, Generac 14 kW, Generac 16 kW, Generac 17 kW, Generac 18 kW NG
805There is no AC output from the generatorReset circuit breaker to ON (or CLOSED). Contact nearest Dealer for assistance.Generac 10 KW, Generac 13 kW, Generac 14 kW, Generac 16 kW, Generac 17 kW, Generac 18 kW NG
806There is no transfer to standby after utility source failureGenerac 10 KW, Generac 13 kW, Generac 14 kW, Generac 16 kW, Generac 17 kW, Generac 18 kW NG
807Unit consumes large amounts of oilAdjust oil to proper level. See 'Engine Oil Recommendations'. Check for oil leaks.Generac 10 KW, Generac 13 kW, Generac 14 kW, Generac 16 kW, Generac 17 kW, Generac 18 kW NG
1001Internal Harness Loop Broken—Internal harness connecting external display board to main board has become disconnected. Triggered when main board does not see communication from display board.Generac Not explicitly stated
1001Controller — Internal Harness Loop Broken—Internal harness connecting external display board to main board has become disconnected. Triggered when main board does not see communication from display board.Generac Not explicitly stated
1048VSCF Overload — Unit shuts down during operation. LED redAlternator, AVR or wiring is damagedContact servicing dealer.Generac 15 kW EcoGen, Generac MMG25IF4, Generac MMG35DF4, Generac MMG45IF4, Generac MMG55DF4
1049VSCF Overload — Unit shuts down during operation. LED redGenerator output is shorted or severely overloadedIdentify and clear the overload, and then restart.Generac 15 kW EcoGen, Generac MMG25IF4, Generac MMG35DF4, Generac MMG45IF4, Generac MMG55DF4
1049 VSCFOverload RED Unit shuts down during operation.Check the LEDs/Screen for alarms. Generator output is shorted or severely overloaded. Identify and clear the overload, and then restart.Generac MMG25IF4, Generac MMG35DF4, Generac MMG45IF4, Generac MMG55DF4
1051VSCF High Battery — Yellow LED illuminated in any stateVoltage supply to the AVR is highIf an external battery charger is in use, contact installing dealer to correct installation. If an external battery charger is NOT in use, contact servicing dealer.Generac 15 kW EcoGen, Generac MMG25IF4, Generac MMG35DF4, Generac MMG45IF4, Generac MMG55DF4
1051 VSCFHigh Battery YELLOW LED illuminated in any state.Check the LEDs/Screen for alarms. Voltage supply to the AVR is high. If an external battery charger is in use, contact installing dealer to correct installation. If an external battery charger is NOT in use, contact Independent Authorized Servicing Dealer.Generac MMG25IF4, Generac MMG35DF4, Generac MMG45IF4, Generac MMG55DF4
1052VSCF DC Overvoltage — Unit shuts down during operation. LED redThe generator was temporarily overloaded; The output was temporarily shortedTry to restart the unit.Generac 15 kW EcoGen, Generac MMG25IF4, Generac MMG35DF4, Generac MMG45IF4, Generac MMG55DF4
1052 VSCFDC Overvoltage RED Unit shuts down during operation.Check the LEDs/Screen for alarms. Probable causes are: 1) The generator was temporarily overloaded. 2) The output was temporarily shorted. Try to restart the unit.Generac MMG25IF4, Generac MMG35DF4, Generac MMG45IF4, Generac MMG55DF4
1053VSCF Gate Fault — Unit shuts down during operation or starting. LED redAVR is damagedContact servicing dealer.Generac 15 kW EcoGen, Generac MMG25IF4, Generac MMG35DF4, Generac MMG45IF4, Generac MMG55DF4
1053 VSCFGate Fault RED Unit shuts down during operation or starting.Check the LEDs/Screen for alarms. AVR is damaged. Contact Independent Authorized Servicing Dealer.Generac MMG25IF4, Generac MMG35DF4, Generac MMG45IF4, Generac MMG55DF4
1054VSCF IGBT Overtemp. — Unit shuts down during operation or starting.Replace AVR filter. Inspect fan.Replace AVR filter. Inspect fan.Generac MMG25IF4, Generac MMG35DF4, Generac MMG45IF4, Generac MMG55DF4
1055VSCF Phase Error — Unit shuts down during starting. LED redAn incorrect voltage and frequency has been detected during starting. Alternator damage. Contact servicing dealer; Generator has started into a severe load. Manually operate generator breaker and try to restart unit. If problem persists, remove load and attempt to restart unit again; The engine may not be reaching its prescribed speedContact servicing dealer; Manually operate generator breaker and try to restart unit. If problem persists, remove load and attempt to restart unit again; Verify stepper motor is moving and linkage is free; Verify stepper motor is plugged in; Verify gas pressure is within specified limitsGenerac 15 kW EcoGen, Generac MMG25IF4, Generac MMG35DF4, Generac MMG45IF4, Generac MMG55DF4
1055 VSCFPhase Error RED Unit shuts down during starting.Check the LEDs/Screen for alarms. An incorrect voltage and frequency has been detected during starting. Probable causes are: 1) Alternator damage. Contact Independent Authorized Servicing Dealer. 2) Generator has started into a severe load. Manually operate generator breaker and try to restart unit. If problem persists, remove load and attempt to restart unit again. 3) The engine may not be reaching its prescribed speed. Proceed as follows: •Verify stepper motor is moving and linkage is free. •Verify stepper motor is plugged in. •Verify gas pressure is within specified limits.Generac MMG25IF4, Generac MMG35DF4, Generac MMG45IF4, Generac MMG55DF4
1055 VSCF Phase ErrorUnit shuts down during starting.Check the LEDs/Screen for alarms. An incorrect voltage and frequency has been detected during starting. Probable causes are: 1) Alternator damage. Contact servicing dealer. 2) Generator has started into a severe load. Manually operate generator breaker and try to restart unit. If problem persists, remove load and attempt to restart unit again. 3) The engine may not be reaching its prescribed speed. Proceed as follows: • Verify stepper motor is moving and linkage is free. • Verify stepper motor is plugged in. • Verify gas pressure is within specified limits.Generac 15 kW EcoGen
1056VSCF Undervoltage — Unit shuts down during operation or starting. LED redThe generator output voltage is too low. The load is too large. Remove load and attempt to restart unit; Alternator or AVR damage. Contact servicing dealerRemove load and attempt to restart unit; Contact servicing dealerGenerac 15 kW EcoGen, Generac MMG25IF4, Generac MMG35DF4, Generac MMG45IF4, Generac MMG55DF4
1056 VSCFUndervoltage RED Unit shuts down during operation or starting.Check the LEDs/Screen for alarms. The generator output voltage is too low. Probable causes are: 1) The load is too large. Remove load and attempt to restart unit. 2) Alternator or AVR damage. Contact Independent Authorized Servicing Dealer.Generac MMG25IF4, Generac MMG35DF4, Generac MMG45IF4, Generac MMG55DF4
1057VSCF Overvoltage — Unit shuts down during operation or starting. LED redThe generator has been overloaded. Remove load and attempt to restart unit; Generator has started into a severe load. Manually operate generator breaker and try to restart unit. If problem persists, remove load and attempt to restart unit againRemove load and attempt to restart unit; Manually operate generator breaker and try to restart unit. If problem persists, remove load and attempt to restart unit againGenerac 15 kW EcoGen, Generac MMG25IF4, Generac MMG35DF4, Generac MMG45IF4, Generac MMG55DF4
1057 VSCFOvervoltage RED Unit shuts down during operation or starting.Check the LEDs/Screen for alarms. Probable causes are: 1) The generator has been overloaded. Remove load and attempt to restart unit. 2) Generator has started into a severe load. Manually operate generator breaker and try to restart unit. If problem persists, remove load and attempt to restart unit again.Generac MMG25IF4, Generac MMG35DF4, Generac MMG45IF4, Generac MMG55DF4
1058VSCF DC Undervoltage — Unit shuts down during operation or starting. LED redThe DPE winding supplies this voltage. Alternator damage. Contact servicing dealerContact servicing dealer.Generac 15 kW EcoGen, Generac MMG25IF4, Generac MMG35DF4, Generac MMG45IF4, Generac MMG55DF4
1058 VSCFDC Undervoltage RED Unit shuts down during operation or starting.Check the LEDs/Screen for alarms. The DPE winding supplies this voltage. 1) Alternator damage. Contact Independent Authorized Servicing Dealer.Generac MMG25IF4, Generac MMG35DF4, Generac MMG45IF4, Generac MMG55DF4
1059VSCF Field Loss — Unit shuts down during starting. LED redUnit detects no output voltage while starting. Alternator damage. Contact servicing dealerContact servicing dealer.Generac 15 kW EcoGen, Generac MMG25IF4, Generac MMG35DF4, Generac MMG45IF4, Generac MMG55DF4
1059 VSCFField Loss RED Unit shuts down during starting.Check the LEDs/Screen for alarms. Unit detects no output voltage while starting. 1) Alternator damage. Contact Independent Authorized Servicing Dealer.Generac MMG25IF4, Generac MMG35DF4, Generac MMG45IF4, Generac MMG55DF4
1060Big Fan Failure — Unit shuts down during operation.This alarm occurs when the AVR electronics temperature exceeds 70 C. AVR filter faulty.Replace AVR filter.Generac MMG25IF4, Generac MMG35DF4, Generac MMG45IF4, Generac MMG55DF4
1061VSCF Field Loss — Unit shuts down during operation. LED redUnit detects loss of output voltage while running. Alternator damage. Contact servicing dealerContact servicing dealer.Generac 15 kW EcoGen, Generac MMG25IF4, Generac MMG35DF4, Generac MMG45IF4, Generac MMG55DF4
1061 VSCFField Loss RED Unit shuts down during operation.Check the LEDs/Screen for alarms. Unit detects loss of output voltage while running. 1) Alternator damage. Contact Independent Authorized Servicing Dealer.Generac MMG25IF4, Generac MMG35DF4, Generac MMG45IF4, Generac MMG55DF4
1061 VSCF Field LossUnit shuts down during operation.Check the LEDs/Screen for alarms. Unit detects loss of output voltage while running. Probable causes are: 1) Alternator damage. Contact servicing dealer.Generac 15 kW EcoGen
1065Overfrequency — Unit shuts down during operation. LED redOverload. Remove load and attempt to restart unit; RPM sensor has failed. Contact servicing dealer; Stepper motor problem. Contact servicing dealerRemove load and attempt to restart unit; Contact servicing dealerGenerac 15 kW EcoGen, Generac MMG25IF4, Generac MMG35DF4, Generac MMG45IF4, Generac MMG55DF4
1066VSCF Speed mismatch — Unit shuts down during Operation or starting. LED redFuel problem (pressure loss). Check fuel supply and attempt to restart unit; Large overload. Remove load and attempt to restart unit; Throttle or engine problem. Contact servicing dealerCheck fuel supply and attempt to restart unit; Remove load and attempt to restart unit; Contact servicing dealerGenerac 15 kW EcoGen, Generac MMG25IF4, Generac MMG35DF4, Generac MMG45IF4, Generac MMG55DF4
1066 VSCFSpeed mismatch RED Unit shuts down during Operation or starting.Check the LEDs/Screen for alarms. Probable causes are: 1) Fuel problem (pressure loss). Check fuel supply and attempt to restart unit. 2) Large overload. Remove load and attempt to restart unit. 3) Throttle or engine problem. Contact Independent Authorized Servicing Dealer.Generac MMG25IF4, Generac MMG35DF4, Generac MMG45IF4, Generac MMG55DF4
1070Small fan failure — "Small fan failure" is displayed. If unit was running in AUTO, it will continue to run for one hour to cool electronics without fan.Small fan current incorrect. Fan wiring or mechanical problem.Contact Independent Authorized Servicing Dealer.Generac MMG25IF4, Generac MMG35DF4, Generac MMG45IF4, Generac MMG55DF4
1100Overcrank — Condition - Engine Cranks but will not Start (5 crank attempts). Unit turns over but will not start. Controller is receiving signal on Wire 18.Unit turns over but will not start. Controller is receiving signal on Wire 18.Problem 17Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10 KVA
1101Overcrank — Engine/Starter Problem. Limiting number of cranking cycles to protect the starter motor.Limiting number of cranking cycles to protect the starter motor. If the engine has tried to crank for 10 times unsuccessfully, this will trigger.If the engine has tried to crank for 10 times unsuccessfully, this will trigger.Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10 KVA
1200Overspeed — Prolonged (60 Hz on a 50 Hz unit, 72Hz on 60Hz unit) Over specified Hz for 3 seconds.Stepper motor/mixer body assembly issueTest 12Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10 KVA
1200/1201/1205OVERSPEEDTEST 60 AND TEST 64Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10000006453-E WD/SD Air-cooled HSB Evolution 2.0 w/426-460cc Engine 60 Hz
1201Overspeed — Prolonged—Throttle stuck open. Over 72 Hz for three seconds with the throttle stuck open.Stuck throttleTest 68Generac Not explicitly stated
1204Overspeed — External Ignition Overspeed. CAN alarm from external ignition, threshold is >30% over nominal.Test 68Generac Not explicitly stated
1205Overspeed — Instantaneous (62 Hz on a 50 Hz unit, 75Hz on 60Hz unit) Over specified Hz for 0.1 second (100 milliseconds).Stepper motor/mixer body assembly issueTest 12Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10 KVA
1206Overspeed — Instantaneous—Throttle stuck open. Over 75 Hz for one second with the throttle stuck open, total loss of control.Stuck throttleTest 68Generac Not explicitly stated
1207Overspeed — Monitors zero cross timing of the AVR to determine the alternator frequency which is a speed indicator. Set for 150 milliseconds of 4500 rpm or higher. Used if the normal ignition pulse sequence(s) are not being seen by the controller.Monitors zero cross timing of the AVR to determine the alternator frequency which is a speed indicator. Set for 150 milliseconds of 4500 rpm or higher. Used if the normal ignition pulse sequence(s) are not being seen by the controllerTest 64 and Test 60Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10 KVA
1300Low Oil Pressure — Occurred while running. The default Extended alarm for low oil pressure.Occurred while running. The default Extended alarm for low oil pressureCheck oil level and pressure. Test 61Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10 KVA
1400High Temperature — Condition - Air Flow Impeded / Flow IssueCondition - Air Flow Impeded / Flow IssueCheck the inlet/outlet for debris. Check temperature sensor and wiring. Test 62Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10 KVA
1400HIGH TEMPTEST 62 – CHECK HIGH OIL TEMPERATURE SWITCH; CHECK INSTALLATION FOR PROPER AIRFLOW OR REPLACE DEFECTIVE SWITCHGenerac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10000006453-E WD/SD Air-cooled HSB Evolution 2.0 w/426-460cc Engine 60 Hz
1401High Temperature — Fuel Pressure Low—Running Lean. Very low fuel pressure while running will cause an increase in engine temperature. Fuel pressure must be measured as low for 1200 ms preceding high temperature alarm to set this E-Code.Problem 34Generac Not explicitly stated
1500Rpm Sensor — Missing Mag Pickup Pulses.Problem 31Generac Not explicitly stated
1501RPM Sensor — Twin Cylinder+Running. Twin Cylinder Running faults to RPM Sensor Loss.Air pocket in fuel line; dirty fuel; missing ignition pulse (loss of one of the primary coils)Test 50 and Test 64Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10 KVA
1501/1511RUNNINGTEST 64 – CHECK WIRE 18 CONTINUITYGenerac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10000006453-E WD/SD Air-cooled HSB Evolution 2.0 w/426-460cc Engine 60 Hz
1505RPM Sensor — Twin Cylinder+Cranking. Twin Cylinder Cranking faults to RPM sensor loss.Starter motor issue; missing ignition pulse (loss of one of the primary coils)If engine cranks, Test 64. If engine does not crank, Problem 15.Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10 KVA
1505/1515NO CRANKGO TO PROBLEM 17Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10000006453-E WD/SD Air-cooled HSB Evolution 2.0 w/426-460cc Engine 60 Hz
1505/1515RPM SENSE LOSSTEST 50 – CHECK FUEL SUPPLY AND PRESSURE; TEST 55 – CHECK FOR IGNITION SPARK; TEST 60 – CHECK IGNITION MAGNETOSGenerac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10000006453-E WD/SD Air-cooled HSB Evolution 2.0 w/426-460cc Engine 60 Hz
1511RPM Sensor — Single Cylinder+Running. Single Cylinder Running RPM sensor loss.Air pocket in fuel line; dirty fuel; loss of ignition pulseTest 50 and Test 64Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10 KVA
1511RPM SENSE LOSS — 8 kW SINGLE CYLINDERTEST 50 – CHECK FUEL SUPPLY AND PRESSURE; TEST 55 – CHECK FOR IGNITION SPARK; TEST 60 – CHECK IGNITION MAGNETOSGenerac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10000006453-E WD/SD Air-cooled HSB Evolution 2.0 w/426-460cc Engine 60 Hz
1515RPM Sensor — Single Cylinder+Cranking. Single Cylinder Cranking faults to RPM sensor loss.Starter motor and/or engine issue; loss of ignition pulseIf engine cranks, Test 64. If engine does not crank, Problem 15.Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10 KVA
1516Rpm Sensor — Cranking + Low Fuel. Cranking with Low Fuel Pressure faults to rpm sensor loss.Low fuel pressure for at least 1200 ms; ignition fault; air pocket in fuel line; dirty fuelProblem 34Generac Not explicitly stated
1517Rpm Sensor — Running + Low Fuel. Running with low fuel pressure faults to rpm sensor loss.Low fuel pressure for 1200 ms; ignition fault; air pocket in fuel line; dirty fuelProblem 34Generac Not explicitly stated
1518Rpm Sensor — No Pulse during Cranking. Rpm sensor loss, no tooth pulses sensed for 75 consecutive milliseconds while starter active.Starter circuit issue; rpm sensorProblem 31Generac Not explicitly stated
1519Rpm Sensor — No Pulse during Running. Cranking faults to rpm sensor loss.Starter circuit issue; rpm sensorProblem 31Generac Not explicitly stated
1520Rpm Sensor — Missing Pulses during Cranking. Cranking faults to rpm sensor loss. Starter engaged, no tooth pulses for 75 ms.Starter circuit issue; rpm sensor alignment; low batteryProblem 31Generac Not explicitly stated
1521Rpm Sensor — Missing Pulses during Running. While running, no tooth pulses for 75 consecutive milliseconds.Rpm sensor alignment; low batteryProblem 31Generac Not explicitly stated
1600Underspeed — Condition - Unit is Overloaded (55 Hz for 60 Hz for 30 sec, 40 Hz for 50 Hz unit). Unit is Overloaded slowing engine speed.Fuel supply low; throttle control problemProblem 3, or Test 50, or Test 12Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10 KVA
1601Underspeed — Low Fuel Pressure. Low fuel pressure starves the engine, slowing it. Low fuel pressure detected for 1200 ms before underspeed condition detected.Check fuel supply and settings; Problem 34Generac Not explicitly stated
1602Underspeed — Throttle Stuck Closed/near Closed. The throttle is stuck closed or stuck near closed limiting the fuel to the engine, slowing it down. Stuck closed must be detected for one second with underspeed to set E-Code.Test 68Generac Not explicitly stated
1603Underspeed — The engine never comes up to 3600 RPM.The engine never comes up to 3700 RPM.Check fuel selection and fuel supplyGenerac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10 KVA
1800Overvoltage — Prolonged Over-VoltageProlonged Over-VoltageProblem 2; Preliminary Output Voltage Test (firmware v1.12 and above). Note: Update controller to latest firmware.Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10 KVA
1800 - 1803 and 2101Generator Shuts Down for Overload / Over VoltageOverloaded; Not overloaded; Shorted condition in a connected load or in one of the load circuits; Load that is causing the problemTest 24 – Check AC Output Voltage; Test 25 – Check AC Output Frequency; Test 27 – Check Voltage and Frequency Under Load; Test 28 – Check for Overload Condition; Test 12 – Test AC Sensing Circuit; Test 18 – Test Stator; Test 58 – Check Fuel Supply and Pressure; Test 68 – Test Actuator/Mixer Function; Reduce loads to unit's rated capacity; Correct the fuel supply problem; Look for a shorted condition in a connected load or in one of the load circuits; Open all load breakers and bring them on one at a time to determine which branch circuit is the cause of the problem; Discontinue testing; Contact technical service; Repair or replaceGenerac Not explicitly stated
1801Overvoltage — Instantaneous—Set by an instantaneous measurement 30% over nominal.Problem 3Generac Not explicitly stated
1803Overvoltage — Overspeed. Generator running at higher speed (25% over nominal rpm) causing overvoltage.Problem 3Generac Not explicitly stated
001810Auxiliary ShutdownGenerac G0072100
1900Undervoltage — Prolonged Under-Voltage. Undervoltage due to loss of voltage. Below 80% for 10+ seconds.Prolonged Under-Voltage. Undervoltage due to loss of voltage. Below 80% for 10+ secondsPreliminary Output Voltage Test (firmware v1.12 and above). Note: Update controller to latest firmware.Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10 KVA
1900 - 1906Generator Shuts Down for Under VoltageTest 1 – Test the Main Circuit Breaker; Test 4 – Fixed Excitation Test; Test 5 – Test Field Flash Circuit; Test 6 – Flash Wiring; Test 7 – Test DB1 Diode; Test 8 – Test DB2 Diode; Test 9 – Wire 14 Field Flash Circuit; Test 10 – Test DPE Breaker; Test 11 – Test DPE Circuit; Test 12 – Test AC Sensing Circuit; Test 13 – Test Regulator Output; Test 18 – Test Stator; Test 19 – Test Brushed Rotor Assembly; Perform Rotor Insulation Resistance Test – Section 1.6; Replace controller; Replace stator only; Replace rotor only; Replace rotor and stator; Repair or replaceGenerac Not explicitly stated
1901Undervoltage — Instantaneous. Undervoltage due to sudden loss of voltage. (Voltage less than 15 sec 2 sec+)Instantaneous. Undervoltage due to sudden loss of voltage. (Voltage less than 15 sec 2 sec+)Preliminary Output Voltage Test (firmware v1.12 and above). Note: Update controller to latest firmware.Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10 KVA
1902Undervoltage — Both Zero Crosses missing. Undervoltage due to faulty excitation winding, or zero cross circuit, or circuit in general. (Both zero cross missing greater than 1.5 sec)Loose wiring; field boost hardware failurePreliminary Output Voltage Test (firmware v1.12 and above). Note: Update controller to latest firmware.Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10 KVA
1903Undervoltage — Little / No Voltage (<120V). Controller measuring no voltage resulting in undervoltage. Generator voltage less than 120V when undervoltage set.Problem 1Generac Not explicitly stated
1904Undervoltage — No Field Current But Have DPE. No field current during undervoltage alarm.Wire loose; brush failureProblem 1Generac Not explicitly stated
1905Undervoltage — Low Speed. Generator running underspeed for > 30 seconds when undervoltage alarm set.Fuel supply/control system; engine intake exhaust or mechanical issuesProblem 1Generac Not explicitly stated
1906Undervoltage — Single Zero Cross missing. Undervoltage due to faulty excitation winding, zero cross circuit, or circuit in general. (One zero cross missing greater than 1.5 sec)Field boost hardware failurePreliminary Output Voltage Test (firmware v1.12 and above). Note: Update controller to latest firmware.Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10 KVA
1916Undervoltage — Single Zero Cross missing. Undervoltage due to faulty excitation winding, or zero cross circuit, or circuit in general. One zero cross missing for greater than 1.5 seconds.Field boost hardware failureProblem 1Generac Not explicitly stated
2098Wiring Error — Mis-wired Customer connection; Insufficient DC voltage on transfer power output.Shorted 194 to groundCheck for shorted 194 to ground. Refer to RTS Diagnostic Manual A0001176044.Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10000006453-E WD/SD Air-cooled HSB Evolution 2.0 w/426-460cc Engine 60 Hz
2099Wiring Error — Mis-wired. Customer connection low voltage and high voltage wires are crossed.Mis-wired. Customer connection low voltage and high voltage wires are crossedCheck customer connection in generatorGenerac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10 KVA
2099Wire Error — Incorrect DC AC wiring hook up.Generac Not explicitly stated
2100Overload Remove Load — Overloaded - Default (Output Current Method). Unit is overloaded. One or both CT(s) detecting an overload condition.Overloaded - Default (Output Current Method). Unit is overloaded. One or both CT(s) detecting an overload conditionCheck transfer switch loadshed functionality. (Change load dynamics or utilize loadshed). Remove LoadGenerac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10 KVA
2101Overload Remove Load — Overload (DPE Style Field Current Method). Field Current measured value is above threshold.OverloadGenerac Not explicitly stated
2101Overload (DPE Style Field Current Method). Field Current measured value is above threshold.OverloadGenerac Not explicitly stated
2102Overload Remove Load — Overloaded. Unit re-cranks 5 times when load is applied, engine dies (0 RPM) and has low voltage (< 180V)Unit recranks 5 times when load is applied, engine dies (0 RPM) and has low voltage (< 180V)Check for Overloaded conditionGenerac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10 KVA
2103Overload Remove Load — Overloaded. Unit has run and attempted to accept load 10 times, could not accept due to overload conditionUnit has run and attempted to accept load 10 times, could not accept due to overload conditionCheck for Overloaded condition on unitGenerac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10 KVA
2299Undervoltage Overload — Unit was overloaded and attempted to start with a large load connected. The unit can not ramp up the generator voltage to its normal target voltage value if it starts with a large load connectedUnit was overloaded and attempted to start with a large load connected. The unit can not ramp up the generator voltage to its normal target voltageRemove LoadGenerac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10 KVA
2399Stepper Overcurrent — Current flow in stepper coil(s) above specificationCurrent flow in stepper coil(s) above specificationTest 12Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10 KVA
2400Fuse Problem — Missing / Damaged Fuse. The 7.5 amp Controller Fuse is missing or blown (open). *Firmware version 1.11 and older onlyThe 7.5 amp Controller Fuse is missing or blown (open).Test 44Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10 KVA
24007.5 Amp Fuse (F1) BlownFuse blows when placed in “AUTO” or “MANUAL”TEST 66 – CHECK CRANKING AND RUNNING CIRCUITSGenerac 10 KVA, Generac 10 KW, Generac 11 kW, Generac 13 kVA, Generac 13 kW, Generac 14 kW
002404Inspect Spark Arrestor ScreenInspect and clean the screen every 50 hours of operation or every season, whichever comes first.Generac IQ3500
2500Bosch — Command and position feedback not matching or taking too much time to achieve.Governor wire loose; governor moduleTest 68Generac Not explicitly stated
2501Bosch — Stuck Open. Command and position feedback not matching or taking too much time to achieve. Governor in open position for greater than one second.Governor wire loose; governor moduleTest 68Generac Not explicitly stated
2502Bosch — Stuck Closed. Command and position feedback not matching or taking too much time to achieve. Governor in closed position (commanded otherwise) for greater than one second.Governor wire loose; governor moduleTest 68Generac Not explicitly stated
2600Ignition — Ignition FaultProblem 37, 38, 39Generac Not explicitly stated
2601Ignition — Missing Cam Pulse—Cam pulses missing for five seconds.Problem 38Generac Not explicitly stated
2602Ignition — Crank Circuit (External Module)Problem 38, 39Generac Not explicitly stated
2611Over current cylinder1 — Coil current too high for one second.Problem 37Generac Not explicitly stated
2612Over current cylinder2 — Coil current too high for one second.Problem 37Generac Not explicitly stated
2613Over current cylinder3 — Coil current too high for one second.Problem 37Generac Not explicitly stated
2614Over current cylinder4 — Coil current too high for one second.Problem 37Generac Not explicitly stated
2615Over current cylinder5 — Coil current too high for one second.Problem 37Generac Not explicitly stated
2616Over current cylinder6 — Coil current too high for one second.Problem 37Generac Not explicitly stated
2617Over current cylinder7 — Coil current too high for one second.Problem 37Generac Not explicitly stated
2618Over current cylinder8 — Coil current too high for one second.Problem 37Generac Not explicitly stated
2619Over current cylinder9 — Coil current too high for one second.Problem 37Generac Not explicitly stated
2620Over current cylinder10 — Coil current too high for one second.Problem 37Generac Not explicitly stated
2621Under current cylinder1 — Coil current too low for one minute.Problem 37Generac Not explicitly stated
2622Under current cylinder2 — Coil current too low for one minute.Problem 37Generac Not explicitly stated
2623Under current cylinder3 — Coil current too low for one minute.Problem 37Generac Not explicitly stated
2624Under current cylinder4 — Coil current too low for one minute.Problem 37Generac Not explicitly stated
2625Under current cylinder5 — Coil current too low for one minute.Problem 37Generac Not explicitly stated
2626Under current cylinder6 — Coil current too low for one minute.Problem 37Generac Not explicitly stated
2627Under current cylinder7 — Coil current too low for one minute.Problem 37Generac Not explicitly stated
2628Under current cylinder8 — Coil current too low for one minute.Problem 37Generac Not explicitly stated
2629Under current cylinder9 — Coil current too low for one minute.Problem 37Generac Not explicitly stated
2630Under current cylinder10 — Coil current too low for one minute.Problem 37Generac Not explicitly stated
2650Internal Ignition Missing Cam — Cranked for four seconds on gaseous unit, no cam pulses detected.Problem 38Generac Not explicitly stated
2651External Ignition Missing Cam — No cam pulses detected by external ignition.Problem 38Generac Not explicitly stated
2660Internal Ignition Missing Crank Pulses — Missing crank pulses detected by internal ignition.Problem 39Generac Not explicitly stated
2661External Ignition Missing Crank Pulses — Missing crank pulses detected by external ignition.Problem 39Generac Not explicitly stated
2671CAN Bus — CANbus error reported by external ignition.Problem 36Generac Not explicitly stated
2672CAN Bus — CANbus error reported by Diesel ECU.Problem 36Generac Not explicitly stated
2700Fuel Level Low — Fuel level below 10%Generac Not explicitly stated
2800Aux Shutdown — External shut down circuit is open.Check the continuity of the harness and operation of the switch(es). Repair/replace as needed.Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10 KVA
005483Daños a los equipos y la propiedad.Generac IQ3500
007634(000209b) Fallecimiento. Este producto no se ha diseñado para que se utilice en aplicaciones de apoyo vital crítico. En caso de hacerlo, podría provocar la muerte o lesiones graves.Generac IQ3500
007843OUTPUT FAULTGenerac IQ3500
007846Output FaultGenerac IQ3500
008034Fault Output MGenerac IQ3500
9202-1Bottom outGenerac 9202-1, Generac 9203-1, Generac 9204-1, Generac 9205-1, Generac 9206-1, Generac 9207-1
9203-1Bottom outGenerac 9202-1, Generac 9203-1, Generac 9204-1, Generac 9205-1, Generac 9206-1, Generac 9207-1
9204-1Bottom outGenerac 9202-1, Generac 9203-1, Generac 9204-1, Generac 9205-1, Generac 9206-1, Generac 9207-1
9205-1Bottom out | Out-the-sideGenerac 9202-1, Generac 9203-1, Generac 9204-1, Generac 9205-1, Generac 9206-1, Generac 9207-1
9206-1Bottom out | Out-the-sideGenerac 9202-1, Generac 9203-1, Generac 9204-1, Generac 9205-1, Generac 9206-1, Generac 9207-1
9207-1NP 6600 120/240 55/27 60 3600 | 2300 | Bottom out |Out-the-side| 89405Generac 9202-1, Generac 9203-1, Generac 9204-1, Generac 9205-1, Generac 9206-1, Generac 9207-1
009209Puesta en marcha automáticaGenerac G0072100
9290-2Bottom out | Bottom outGenerac 9202-1, Generac 9203-1, Generac 9204-1, Generac 9205-1, Generac 9206-1, Generac 9207-1
9592-15500 120/240 Bottom out UniversalGenerac 9202-1, Generac 9203-1, Generac 9204-1, Generac 9205-1, Generac 9206-1, Generac 9207-1
9593-17000 120/240 Bottom out UniversalGenerac 9202-1, Generac 9203-1, Generac 9204-1, Generac 9205-1, Generac 9206-1, Generac 9207-1
9593-27000 120/240 Bottom out | UniversalGenerac 9202-1, Generac 9203-1, Generac 9204-1, Generac 9205-1, Generac 9206-1, Generac 9207-1
9600-0NP 6600 120/240 55/27 60 3600 | 2700 | Bottom out | Universal 92116Generac 9202-1, Generac 9203-1, Generac 9204-1, Generac 9205-1, Generac 9206-1, Generac 9207-1
9600-16600 120/240 Bottom out UniversalGenerac 9202-1, Generac 9203-1, Generac 9204-1, Generac 9205-1, Generac 9206-1, Generac 9207-1
9677-17200 120/240 Bottom out UniversalGenerac 9202-1, Generac 9203-1, Generac 9204-1, Generac 9205-1, Generac 9206-1, Generac 9207-1
9677-27000 120/240 Bottom out UniversalGenerac 9202-1, Generac 9203-1, Generac 9204-1, Generac 9205-1, Generac 9206-1, Generac 9207-1
9677-3Q 7000 120/240 58/29 60 3600 | 2570 | Bottom out | Universal 92116Generac 9202-1, Generac 9203-1, Generac 9204-1, Generac 9205-1, Generac 9206-1, Generac 9207-1
9677-4Q 7000 120/240 58/29 60 3600 | 2570 | Bottom out | Universal 92116Generac 9202-1, Generac 9203-1, Generac 9204-1, Generac 9205-1, Generac 9206-1, Generac 9207-1
9712-0NP 5000 120/240 41/20 60 3600 | 2751 Bottom out | Universal 92116Generac 9202-1, Generac 9203-1, Generac 9204-1, Generac 9205-1, Generac 9206-1, Generac 9207-1
9712-1NP 5000 120/240 41/20 60 3600 | 2751 Bottom out | Universal 92116Generac 9202-1, Generac 9203-1, Generac 9204-1, Generac 9205-1, Generac 9206-1, Generac 9207-1
9734-1NP 6600 120/240 55/27 60 3600 | 2700 | Bottom out | Universal 92116Generac 9202-1, Generac 9203-1, Generac 9204-1, Generac 9205-1, Generac 9206-1, Generac 9207-1
9735-1Q 5500 120/240 46/23 60 3600 | 2570 | Bottom out | Universal 92116Generac 9202-1, Generac 9203-1, Generac 9204-1, Generac 9205-1, Generac 9206-1, Generac 9207-1
9736-1Q 7000 120/240 58/29 60 3600 | 2570 | Bottom outGenerac 9202-1, Generac 9203-1, Generac 9204-1, Generac 9205-1, Generac 9206-1, Generac 9207-1
013428Vision LossGenerac GP5500E, Generac Mod A
020000Explosion and FireGenerac GP5500E, Generac Mod A
020423Accidental Start-upGenerac GP5500E, Generac Mod A
ALow engine oil pressure or high engine coolant temperatureSee General Troubleshooting — low oil pressure & high engine coolant temperature.Generac MLTS Export Power Option, Generac MLTS Standard Unit
A0006052083Calcomanía de escape calienteGenerac GP5500E, Generac Mod A
A+CEngine overspeed or engine underspeedCheck connection on W terminal of DC Charge Alternator—WH/VI to pin-9 on the Power Zone controller; Inspect function of DC charge alternator; Inspect tension of DC charge alternator drive belt; Contact Generac Mobile.Generac MLTS Export Power Option, Generac MLTS Standard Unit
Accy PwrOver WarningAccy PwrOver Warning — controller internal circuit protection activatedPress OFF to reset; Contact an authorized Kohler distributor/dealer for serviceGenerac 10RESV, Generac 12RESV, Generac 8RESV
AlNon-shut down alarmGenerac H-100
Al/Hist. msg 1-16Al/Hist. msg 1-16 activity indication (Al/Hist. msg means Alarm/History message)Al/Hist. msg can be used as a customized message for additional protection configured to any controller internal value. See GenConfig manual - ProtectionsGenerac MGG280, Generac MGG350N2
AUXILIARY SHUTDOWNUnit will not start in AUTO with utility lossCheck auxiliary shutdown switchesVerify both auxiliary shutdown switches are ON (I). See Figure 3-6 for locations.Generac 10 KW, Generac 10 kW, Generac 100 kW / 130 kW / 150 kW, Generac 11 kW, Generac 12.0DTA, Generac 14 kW
B+CLoss of speedCheck connection on W terminal of DC Charge Alternator—WH/VI to pin-9 on the Power Zone controller; Inspect function of DC charge alternator; Inspect tension of DC charge alternator drive belt; Contact Generac Mobile.Generac MLTS Export Power Option, Generac MLTS Standard Unit
Batt voltIndication of battery voltage protection activityThis protection is based on Analog protect: Batt >V, Batt <V, and Batt volt del setpointsCheck if engine alternator or independent battery charger works properlyGenerac MGG280, Generac MGG350N2
Battery ChargeBattery Charge — Battery voltage is below 25 V with engine in RUNGenerac MFH900
Battery is DeadProblem 22 – Battery is DeadTest 45 – Check Battery and CablesGenerac 10 KVA, Generac 10 KW, Generac 11 kW, Generac 12 kW, Generac 13 kVA, Generac 13 kW
BATTERY PROBLEMYellow LED illuminated in any stateCheck the screen for additional informationContact an IASD.Generac 0066780, Generac 10 KVA, Generac 10 KW, Generac 10 kW, Generac 100 kW / 130 kW / 150 kW, Generac 11 kW
BATTERY PROBLEMControl panel indicates battery problem.Check for additional informationContact servicing dealer.Generac 6/7 kW, Generac 7.5 kW PowerPact
Battery Under/Over VoltageEngine’s DC supply has fallen below or risen above its configured alarm level.Generac MLT4200IF4
BREAK IN MAINTENANCE DUEControl panel indicates break-in maintenance dueCheck for additional informationPerform break in maintenance. Clear Maintenance Due light.Generac 6/7 kW
Break-In Maintenance DueControl panel indicates break-in maintenance due.Check for additional information.Perform break-in maintenance. Clear maintenance due light.Generac 7.5 kW PowerPact
BREAK-IN MAINTENANCE DUEControl panel indicates break-in maintenance dueCheck the screen for additional informationPerformGenerac 7.5 kW PowerPact
CFail to crank (AUTO mode only)See General Troubleshooting — fail to crank.Generac MLTS Export Power Option, Generac MLTS Standard Unit
C1Low Oil Pressure ShutdownCheck the engine oil level.Generac NP-30G
C2High Temperature ShutdownGenerac NP-30G
C4Low Voltage ShutdownDisconnect all loads the generator might power by whatever means provided, such as the recreational vehicle’s main circuit breaker.Generac NP-30G
CHARGER MISSING ACYellow LED illuminated in any stateContact an IASDGenerac 10 KW, Generac 10 kW, Generac 11 kW, Generac 14 kW, Generac 16 kW, 20 kW, 22 kW, Generac 18 kW
CHARGER PROBLEMControl panel indicates charging problem.Check for additional informationContact servicing dealerGenerac 6/7 kW, Generac 7.5 kW PowerPact
CHARGER WARNINGYellow LED illuminated in any stateCheck the screen for additional informationContact an IASD.Generac 0066780, Generac 10 KVA, Generac 10 KW, Generac 10 kW, Generac 100 kW / 130 kW / 150 kW, Generac 11 kW
Check Engine FaultA fault not recognized by the controller has been detected.Generac MLT4200IF4
Code 0Ignition Fault Code 0Generac Not explicitly stated
Control System FaultControl System Fault — Any control system faultGenerac MFH900
DEF Fluid LevelDEF Fluid Level — Steady ON (amber): DEF fluid level is 20%; Slow flash (red): DEF fluid level is 16% or belowGenerac MFH900
Delayed Engine ShutdownDelayed Engine Shutdown — DPF outlet temperature is above a set temperature threshold; Engine is coolingGenerac MFH900
E1100Over Crank - E1100Section 4.5, Problem 17Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10000006453-E WD/SD Air-cooled HSB Evolution 2.0 w/426-460cc Engine 60 Hz
E1207Overspeed - E1207Test 64 and Test 60Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10000006453-E WD/SD Air-cooled HSB Evolution 2.0 w/426-460cc Engine 60 Hz
E1300Low Oil Pressure - E1300Test 61Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10000006453-E WD/SD Air-cooled HSB Evolution 2.0 w/426-460cc Engine 60 Hz
E1400High Temperature - E1400Test 62Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10000006453-E WD/SD Air-cooled HSB Evolution 2.0 w/426-460cc Engine 60 Hz
E1800Overvoltage - E1800Section 2.2, Problem 2Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10000006453-E WD/SD Air-cooled HSB Evolution 2.0 w/426-460cc Engine 60 Hz
E2099Wiring Error - E2099Check Wiring InterconnectionGenerac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10000006453-E WD/SD Air-cooled HSB Evolution 2.0 w/426-460cc Engine 60 Hz
E2100Overload Remove Load - E2100Test 15Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10000006453-E WD/SD Air-cooled HSB Evolution 2.0 w/426-460cc Engine 60 Hz
E2299Undervoltage Overload - E2299Test 15Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10000006453-E WD/SD Air-cooled HSB Evolution 2.0 w/426-460cc Engine 60 Hz
EarthFaultCurrIndication of Earth fault current protection activityThis protection is based on Gener protect: EarthFaultCurr and EthFltCurr del setpoints. Setpoint EarthFltCurrCT from Basic settings group of setpoints is related to this protection tooGenerac MGG280, Generac MGG350N2
ECUIndication of error in communication with ECUCheck if the ECU is: correctly connected to the CAN1 port of the controller (refer to Comap Electronic Engines Support manual for information about ECU connection); powered up; terminating resistors are properly connected; the CAN bus Low and High wires are not swappedGenerac MGG280, Generac MGG350N2
ECUDiagBlockedAlarm is active when Comms settings: ECU diag = DISABLED. This setting means that ECU alarms are not displayed and considered by controller and this alarm is the setting notificationGenerac MGG280, Generac MGG350N2
Engine Coolant TemperatureEngine Coolant Temperature — Coolant level is above 228 °F (109 °C)Generac MFH900
Engine Emissions MalfunctionEngine Emissions Malfunction — Indicates failure of a critical emissions component. Engine derate: Steady ON: 0%; Slow flash: 50%; Fast flash: 100%Generac MFH900
Engine Intake TemperatureEngine Intake Temperature — Engine intake temperature is above 253 °F (123 °C)Generac MFH900
Engine Oil PressureEngine Oil Pressure — Steady ON: Severity level 1—0% derated engine power; Flashing: Severity level 3—100% derated engine powerGenerac MFH900
Engine OverspeedEngine Overspeed — Engine rpm exceeds set parameter in EPEC ECU for overspeed, or the engine ECU transmits the overspeed indication; Remains ON until engine cycles through a stopped state; Setpoint: 2,600 rpmGenerac MFH900
Engine Stop/ShutdownEngine Stop/Shutdown — Indicates engine shutdown required for severe system faults/events.Generac MFH900
Engine WarningEngine Warning — Used to indicate engine and emissions system diagnostics.Generac MFH900
EngProt001Overcrank ShutdownOvercrank LED will turn ON. Turn OFF the AUTO/OFF/MANUAL switch, then turn switch back to AUTO to reset the generator control boardGenerac 2.4L 45kW, Generac 2.4L 60kW, Generac 45 KW, Generac 60 KW
EST 1Ac OUTPUT VOLTAGEGenerac 9344, Generac IM Series, Generac NP Series
Evolution E-Code 2400Engine Will Not Crank When Utility Power Source FailsTest 44 – Check 7.5 Amp Fuse Evolution Alarm Code 2400Generac 10 KVA, Generac 10 KW, Generac 11 kW, Generac 12 kW, Generac 13 kVA, Generac 13 kW
Evolution Fault codes 1900 - 1906Generator Shuts Down for Under VoltageGenerac Not explicitly stated
F1Blown F1 or F2 fuseFuse F1 or F2 blownCheck fuse F1 & F2 (Test 30); check N1 & N2 wiring (Test 34); check transformer TX (Test 35); repair or replace; replaceGenerac 005240 & 005280, Generac 005241 & 005281, Generac 005242 & 005282, Generac 005243 & 005283, Generac 005244 & 005284, Generac 10 KW
F115 Amp fuse (F1) blownFuse blows immediately when replaced; fuse blows when placed in "AUTO" or "MANUAL"Check battery voltage circuit (Test 75); check cranking and running circuits (Test 76)Generac 005240 & 005280, Generac 005241 & 005281, Generac 005242 & 005282, Generac 005243 & 005283, Generac 005244 & 005284, Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz
F1Engine cranks but will not start — Open F1 7.5 amp fuseOpen F1 7.5 amp fuseReplace F1 7.5 amp fuse if fuse blows again. Contact an IASD.Generac 48 KW, Generac 60 KW, Generac 80 kW
F1Open F1 7.5 amp fuseBlown fuse F1Replace F1 7.5 amp fuse if fuse blows again. Contact an IASD.Generac 0066780, Generac 100 kW / 130 kW / 150 kW, Generac 12.0DTA, Generac 12.5 KW, Generac 16 kW, Generac 20 kW
F17.5A (F1) fuse blowingFuse blows upon installationInstall new 7.5 amp fuse; check that fuse holder is not grounded; check remote harness wire 15 for short to ground; check choke solenoid and starter contactor; check wire 56 short to ground; check wire 90 short to groundGenerac 4700, Generac QuietPact 55G & LP, Generac QuietPact 65G & LP, Generac QuietPact 75G & LP, Generac QuietPact® 55/65/75
F110 Amp Fuse (F1) BlowingFuse blows upon installation; fuse blows when running; fuse is good but blows when placed to start; start-run-stop switch wired incorrectly; start stop relay (SSR) bad; fuel solenoid bad; starter contactor relay bad; BCR1 and BCR2 wired incorrectly; battery charge rectifier 2 (BCR2) bad; wire 15 bad; wire 15B bad; wire 14 circuit bad; diode/resistor bad; fuel shutoff solenoid (FSS) bad; hourmeter (HM) bad; wire 167 badInstall new 10 amp fuse; verify start-run-stop switch is wired correctly (see Figure 6-46, pg. 55); check fuel solenoid (Test 47) and starter contactor relay (Test 44); verify BCR1 and BCR2 are wired correctly; repair or replace wire 14; correct wiring; repair or replace; replaceGenerac GPS 12500 (004451, 004986), Generac GPS 15000 (004582, 004987, 005209), Generac GPS 17500
F1/F2Blown F1 or F2 FuseTest 28 – Check Fuse F1 & F2; Test 32 – Check N1 & N2 Wiring; inspect/replace controller; finish; repair or replace wiringGenerac 10 KVA, Generac 10 KW, Generac 11 kW, Generac 13 kVA, Generac 13 kW, Generac 14 kW
F2Blown F1 or F2 fuseFuse F1 or F2 blownCheck fuse F1 & F2 (Test 30); check N1 & N2 wiring (Test 34); check transformer TX (Test 35); repair or replace; replaceGenerac 005240 & 005280, Generac 005241 & 005281, Generac 005242 & 005282, Generac 005243 & 005283, Generac 005244 & 005284, Generac 10 KW
F2Engine cranks but will not start — Open F2 15 amp fuseOpen F2 15 amp fuseReplace F2 15 amp fuse if fuse blows again. Contact an IASD.Generac 48 KW, Generac 60 KW, Generac 80 kW
F2Open F2 15 amp fuseReplace F2 15 amp fuse if fuse blows again. Contact an IASD.Generac 100 kW / 130 kW / 150 kW, Generac 12.0DTA
Fail to StartFail to Start — engine does not start and run within three starting cycles; LCD screen displays the "Fail to Start" alarmThe starting sequence can be repeated after the starter cools for at least two minutes. Pressing the Stop (O) button will clear the alarm and reset the controller.Generac MLT6
FAULT_01Generator Produces Zero Voltage or Residual VoltageGenerac CorePower 6/7 kW, Generac PowerPact 5.6 kVA 50 Hz, Generac PowerPact 6/7 kW 60 Hz, Generac PowerPact 6/7.5 kW 60 Hz
FAULT_02Generator Produces Low Voltage at No-LoadGenerac CorePower 6/7 kW, Generac PowerPact 5.6 kVA 50 Hz, Generac PowerPact 6/7 kW 60 Hz, Generac PowerPact 6/7.5 kW 60 Hz
FAULT_03Generator Produces High Voltage at No-LoadGenerac CorePower 6/7 kW, Generac PowerPact 5.6 kVA 50 Hz, Generac PowerPact 6/7 kW 60 Hz, Generac PowerPact 6/7.5 kW 60 Hz
FAULT_04Voltage and Frequency Drop Excessively When Loads Are AppliedGenerac CorePower 6/7 kW, Generac PowerPact 5.6 kVA 50 Hz, Generac PowerPact 6/7 kW 60 Hz, Generac PowerPact 6/7.5 kW 60 Hz
FIREFIREGenerac GP Series
Fuel Not ReadyFuel Not Ready — normal during a controller power loss; clears automatically in 30 seconds; user unable to start the unit during this timeGenerac MGG450
FuelSys006Fuel System FaultGenerac 6.8L V-10, Generac V-10 6.8L
FUSE PROBLEMUnit will not start in AUTO with remote start signal — LED redCheck the LEDs / screen for alarmsCheck the 7.5 amp fuse. If it is blown, replace it with an ATO 7.5 amp fuse. If the fuse is intact, contact an IASD.Generac 0066780, Generac 10 KVA, Generac 10 KW, Generac 11 kW, Generac 12 kW, Generac 13 kVA
FXXXIndicates a fault state. The DVR stops providing excitation.Generac MDG150, Generac MDG175, Generac MDG250
Gen I unbalGenerator voltage unbalance alarmBased on Gener protect: Gen V unbal and Gen V unb del setpointsGenerac MGG280, Generac MGG350N2
Gen V unbalGenerator voltage unbalance alarmBased on Gener protect: Gen V unbal and Gen V unb del setpoints. The voltage unbalance is calculated as a maximum difference between phase voltagesGenerac MGG280, Generac MGG350N2
Generator Will Not ExerciseProblem 20 – Generator Will Not ExerciseTest 45 – Check Battery and CablesGenerac 10 KVA, Generac 10 KW, Generac 11 kW, Generac 12 kW, Generac 13 kVA, Generac 13 kW
H01Low Coolant LevelAdd coolant to the proper level.Generac SG035
H02High Coolant TemperatureReduce load or allow engine to cool.Generac SG035
H03Low Engine Oil PressureCheck and add oil if necessary, or replace oil filter.Generac SG035
H04Overspeed ShutdownReduce load immediately to prevent engine damage.Generac SG035
H05Overcrank ShutdownCheck fuel system and ignition components.Generac SG035
H06RPM Sensor Loss ShutdownCheck RPM sensor connections and replace if necessary.Generac SG035
H07Low Fuel Pressure WarningCheck fuel system for leaks or blockages.Generac SG035
High Exhaust Temperature (HEST)High Exhaust Temperature (HEST) — Engine is NOT at idle and the engine ECU is requesting high idle (typically, 1,200 rpm); Control system has granted permission for high idle state; Typical when DPF is above 80% soot loadGenerac MFH900
HIGH TEMPShutdown alarm/fault occurred — High tempHigh oil temperature switch faultyTest 76 - Check high oil temperature switch; check installation for proper airflow or replace defective switchGenerac 10 KW, Generac 12 kW, Generac 14 kW, Generac 16 kW, Generac 17 kW, Generac 20 kW
HIGH TEMPERATUREUnit shuts down during operation — LED redCheck the LEDs / screen for alarmsCheck ventilation around the generator, intake, exhaust, and rear of generator. If no obstructions are present, contact an IASD.Generac 0066780, Generac 10 KVA, Generac 10 KW, Generac 10 kW, Generac 100 kW / 130 kW / 150 kW, Generac 11 kW
HTOHigh Temp SwitchGenerac 0F3982
HTOHigh Oil TemperatureGenerac 9202-1, Generac 9203-1, Generac 9204-1, Generac 9205-1, Generac 9206-1, Generac 9207-1
Hydraulic Oil Level LowHydraulic Oil Level Low — Low hydraulic oil levelGenerac MFH900
Hydraulic Oil TemperatureHydraulic Oil Temperature — Tank >160 °F (71 °C) or oil stream >200 °F (93 °C); Tank >170 °F (77 °C) or oil stream >210 °F (99 °C); High-temperature cut-out switch openGenerac MFH900
Hydraulic Return FilterHydraulic Return Filter — Filter conditionGenerac MFH900
IDMT ALARMIf the Over Current IDMT Alarm is enabled, the controller begins following the IDMT ‘curve’ when the current on any phase passes the Trip setting. If the Trip is surpassed for an excess amount of time, the IDMT Alarm triggers (Shutdown or Electrical Trip as selected in Action). The larger the over circuit fault, the faster the trip.Generator current exceeds the trip level and remains above it for a duration that surpasses the set threshold.DSE7310 MKII controller
IMMEDIATE WARNINGIf the Immediate Warning is enabled, the controller generates a warning alarm as soon as the Trip level is reached. The alarm automatically resets once the generator loading current falls below the Trip level (unless All Warnings are latched is enabled).Generator current exceeds the trip level.DSE7310 MKII controller
INSPECT BATTERYYellow LED illuminated in any stateCheck the screen for additional informationInspect battery. Press ENTER to clear.Generac 10 kW, Generac 11 kW, Generac 14 kW, Generac 15 kW EcoGen, Generac 16 kW, 20 kW, 22 kW, Generac 18 kW
Inspect BatteryYellow LED illuminated in any state — Inspect BatteryInspect Battery, hit ENTER to clear.Generac 10 KVA, Generac 10 KW, Generac 11 kW, Generac 12 kW, Generac 13 kVA, Generac 13 kW
LOPLow Oil Pressure SwitchGenerac 0F3982, Generac 9202-1, Generac 9203-1, Generac 9204-1, Generac 9205-1, Generac 9206-1
LOW BATTERYYellow LED illuminated in any stateCheck the screen for additional informationClear alarm. Using the control panel, check the battery by navigating to the BATTERY MENU option from the MAIN MENU. If battery condition displays GOOD, contact an IASD. If control panel displays CHECK BATTERY, replace the battery.Generac 0066780, Generac 10 KVA, Generac 10 KW, Generac 10 kW, Generac 100 kW / 130 kW / 150 kW, Generac 11 kW
LOW BATTERYShutdown alarm/fault occurred — Low batteryBattery charging system faultProceed to Problems 10-13Generac 10 KW, Generac 12 kW, Generac 14 kW, Generac 16 kW, Generac 17 kW, Generac 20 kW
Low Diesel FuelLow Diesel Fuel — Steady ON (amber): Fuel level is 20%; Slow flash (red): Fuel level is 16%; Fast flash (red): Fuel level is 12% or belowGenerac MFH900
Low Fuel LevelEngine’s fuel level has fallen below its configured low fuel level alarm.Generac MLT4200IF4
LOW FUEL LEVEL SHUT DOWNEngine automatically shuts down.Fuel level is low, fuel tank has leaks, or fuel level sender is damaged.Check the fuel level on the LCD window. Confirm that the generator is sitting level to ensure an accurate reading. Check for leaks in the fuel tank. If the fuel level is good and no leaks are found, check the fuel level sender and the connecting wiring for damage.Generac MMG50ITM, Generac MMG50ITM, MMG50ITMBAU
LOW OILShutdown alarm/fault occurred — Low oilOil pressure switch and wire 86 faultyTest 75 - Check oil pressure switch and wire 86; repair or replaceGenerac 10 KW, Generac 12 kW, Generac 14 kW, Generac 16 kW, Generac 17 kW, Generac 20 kW
LOW OIL LEVELUnit will not start in AUTO with utility loss.Check for alarmsCheck oil level. Add oil per Owner’s Manual. Contact servicing dealer if oil level is correct.Generac 6/7 kW
LOW OIL PRESSUREUnit will not start in AUTO with remote start signal — LED redCheck the LEDs / screen for alarmsCheck oil level and add oil as needed. If oil level is correct, contact an IASD.Generac 0066780, Generac 10 KVA, Generac 10 KW, Generac 10 kW, Generac 100 kW / 130 kW / 150 kW, Generac 11 kW
Low Oil PressureEngine oil pressure has fallen below its configured low oil pressure alarm level.Generac MLT4200IF4
LOW VOLTS REMOVE LOADUnit will not start in AUTO with remote start signal — LED redCheck the LEDs / screen for alarmsClear alarm and remove household loads from the generator. Put in AUTO and restart.Generac 10 KW, Generac 10 kW, Generac 11 kW, Generac 14 kW, Generac 15 kW EcoGen, Generac 16 kW
M01Low Oil Pressure ShutdownCheck the engine oil level. If necessary, add oil to the FULL mark.Generac NP-30G
M02High Temperature ShutdownGenerac NP-30G
M03Overspeed ShutdownDo not attempt a manual adjustment to control engine speed.Generac NP-30G
M04Low Voltage ShutdownGenerac NP-30G
MainPwrOverL ShutdownMainPwrOverL Shutdown — controller internal circuit protection activatedPress OFF to reset; Contact an authorized Kohler distributor/dealer for serviceGenerac 10RESV, Generac 12RESV, Generac 8RESV
Mains Earth FaultGenerator earth fault current rose above the Mains Earth Fault Trip Level for the duration of the IDMT function.DSE7310 MKII controller
Mains Over CurrentMains output current rose above the Mains Over Current Trip level.DSE7310 MKII controller
Mains Phase Seq WrongPhase rotation of mains was different to configured Mains Phase Rotation Alarm setting.DSE7310 MKII controller
MenuMenuGenerac PWRcell
MISWIREUnit will not start in AUTO with remote start signal — LED redCheck the LEDs / screen for alarmsContact an IASD.Generac 0066780, Generac 10 KVA, Generac 10 KW, Generac 11 kW, Generac 12 kW, Generac 13 kVA
No E-code on HSBController FaultReplace ControllerGenerac 6 kW, Generac 8-20 kW
NO LEDs LITUnit will not start in AUTO with utility loss.Check for alarmsCheck ATO 7.5 Amp ATO® fuse. Replace with same type fuse if bad. Contact servicing dealer if fuse is good.Generac 6/7 kW, Generac 7.5 kW PowerPact
No Low Speed ExerciseProblem 21 – No Low Speed ExerciseGenerac 10 KVA, Generac 10 KW, Generac 11 kW, Generac 12 kW, Generac 13 kVA, Generac 13 kW
NO RPM SENSEShutdown alarm/fault occurred — No RPM senseNo signalRepair or replaceGenerac 10 KW, Generac 12 kW, Generac 14 kW, Generac 16 kW, Generac 17 kW, Generac 20 kW
NOT ACTIVATEDUnit will not start in AUTO with remote start signal — LED noneCheck if screen says unit not activatedRefer to “Activation” in installation manual.Generac 0066780, Generac 10 KVA, Generac 10 KW, Generac 10 kW, Generac 100 kW / 130 kW / 150 kW, Generac 11 kW
OCField boost voltage is available.Generac 9344, Generac IM Series, Generac NP Series
OtherMultipleContact IASDGenerac 15,5 / 18,0 kW**, Generac GP Series Portable Generator, Generac GP18000EFI, Generac Portables
OtroMúltipleComuníquese con un IASD.Generac 15,5 / 18,0 kW**, Generac GP Series Portable Generator, Generac GP18000EFI, Generac Portables
Over Speed AlarmShutdown alarm in the event of the engine speed rising above the configured Over Speed Alarm Trip value for longer than the Activation Delay.DSE7310 MKII controller
Over Speed Pre-AlarmWarning alarm in the event of the engine speed rising above the configured Over Speed Pre-Alarm Trip value for longer than the Activation Delay. The Warning is automatically reset when the engine speed falls below the configured Return level.DSE7310 MKII controller
OVER VOLTAGEUnit will not start in AUTO with utility lossGenerac 100 kW / 130 kW / 150 kW, Generac 12.0DTA, Generac 48 KW, Generac 60 KW, Generac 80 kW
OVERCRANKUnit will not start in AUTO with remote start signal — LED redCheck the LEDs / screen for alarmsCheck fuel line shutoff valve is ON. Clear alarm. Start the unit in MANUAL. If it does not start, or starts and runs rough, contact an IASD.Generac 0066780, Generac 10 KVA, Generac 10 KW, Generac 10 kW, Generac 100 kW / 130 kW / 150 kW, Generac 11 kW
OVERCRANKShutdown alarm/fault occurred — OvercrankEngine cranking faultProceed to Problem 16Generac 10 KW, Generac 12 kW, Generac 14 kW, Generac 16 kW, Generac 17 kW, Generac 20 kW
OVERLOADUnit shuts down during operationClear alarm and remove loads from generator. Put back in AUTO and restart.Generac 0066780, Generac 100 kW / 130 kW / 150 kW, Generac 12.0DTA, Generac 48 KW, Generac 60 KW, Generac 80 kW
OVERLOAD REMOVE LOADUnit shuts down during operation — LED redCheck the LEDs / screen for alarmsClear alarm and remove household loads from the generator. Put in AUTO and restart.Generac 10 KVA, Generac 10 KW, Generac 10 kW, Generac 11 kW, Generac 12 kW, Generac 13 kVA
OVERLOAD REMOVE LOADUnit will not start in AUTO with utility loss — OVERLOAD REMOVE LOADOverload conditionClear alarm and remove household loads from the generator. Put back in AUTO and restart.Generac 10 KVA, Generac 10 KW, Generac 11 kW, Generac 12 kW, Generac 13 kVA, Generac 13 kW
OVERSPEEDUnit will not start in AUTO with remote start signal — LED redCheck the LEDs / screen for alarmsContact an IASD.Generac 0066780, Generac 10 KVA, Generac 10 KW, Generac 10 kW, Generac 100 kW / 130 kW / 150 kW, Generac 11 kW
OVERSPEEDShutdown alarm/fault occurred — OverspeedEngine governor out of adjustmentTest 15 - Check and adjust engine governor; repair linkage if binding, check throttle operationGenerac 10 KW, Generac 12 kW, Generac 14 kW, Generac 16 kW, Generac 17 kW, Generac 20 kW
OverspeedEngine speed has risen above its configured overspeed alarm level.Generac MLT4200IF4
Overspeed shutdown.Overspeed shutdown.Check governor and throttle linkages for freedom of movement. Check overspeed switch.Generac XG03245, Generac XG04045, Generac XG04845
OVERSPEED UNDERSPEEDUnit will not start in AUTO with utility loss.Check for alarmsContact servicing dealer.Generac 6/7 kW, Generac 7.5 kW PowerPact
OVERVOLTAGEUnit will not start in AUTO with remote start signal — LED redCheck the LEDs / screen for alarmsContact an IASD.Generac 0066780, Generac 10 KVA, Generac 10 KW, Generac 10 kW, Generac 11 kW, Generac 12 kW
P0134Oxygen sensor has not toggled between indicating lean and indicating rich for at least one minute — displays Malfunction Indicator Light (MIL) message CHECK ENGINE on the H-100 control panel display; does not generate audible alarmsAutomatically clears after three run cycles (three times fully starting the unit and then completely shutting it down) in which no DTC conditions are active; a GMPASD can also clear the DTC through GenLinkGenerac MGG100M
P0300Cylinder Misfire DetectedGenerac 4.3 Liter Gas Engine
P1034Oxygen Sensor has not toggled between indicating lean and indicating rich for at least 1 minuteGenerac H-100
Problem 10In Automatic Mode, No Transfer to StandbyPerform Test 26 – Check Manual Transfer Switch Operation (50 Amp Switch Only); Test 27 – Check Voltage at Transfer Switch; Test 28 – Test Transfer Operator (GenReady Switch Only); Test 29 – Check Wire 15B/194 Circuit; Test 30 – Check Wire 23 Circuit; replace transfer operator; replace controller; find cause of no AC output to transfer switch from generator; repair or replace as neededGenerac CorePower 6/7 kW, Generac PowerPact 5.6 kVA 50 Hz, Generac PowerPact 6/7 kW 60 Hz, Generac PowerPact 6/7.5 kW 60 Hz
Problem 11In Automatic Mode, Generator Starts When Loss of Utility Occurs, Generator Shuts Down When Utility Returns But There is No Retransfer to Utility Power Or Generator Transfers to Standby During Exercise or in Manual ModeGenerac CorePower 6/7 kW, Generac PowerPact 5.6 kVA 50 Hz, Generac PowerPact 6/7 kW 60 Hz, Generac PowerPact 6/7.5 kW 60 Hz
Problem 12Blown F1 or F2 FuseTest 32 – Check Fuse F1 & F2; Test 33 – Check N1 & N2 Wiring; repair or replace wiring; inspect/replace controller; finishGenerac CorePower 6/7 kW, Generac PowerPact 5.6 kVA 50 Hz, Generac PowerPact 6/7 kW 60 Hz, Generac PowerPact 6/7.5 kW 60 Hz
Problem 13Blown T1 FuseTest 35 – Check Fuse F3 (T1); Test 36 – Check T1 Wiring; repair or replace wiring; replace controller; stop testingGenerac CorePower 6/7 kW, Generac PowerPact 5.6 kVA 50 Hz, Generac PowerPact 6/7 kW 60 Hz, Generac PowerPact 6/7.5 kW 60 Hz
Problem 14Unit Starts and Transfer Occurs When Utility Power Is OnTest 41 – Check Utility Sensing Voltage at Controller; Test 38 – Check N1 & N2 Voltage; Test 39 – Check Utility Sense Voltage; Test 32 – Check Fuse F1 & F2; replace controller; correct utility source voltage; replace; go to Problem 7; repair or replace wiring; repair or replace wire N1A/N2A between N1/N2 lugs and fuse holder; repair N1/N2 open wiring between transfer switch and generator; check meter settings and functionalityGenerac CorePower 6/7 kW, Generac PowerPact 5.6 kVA 50 Hz, Generac PowerPact 6/7 kW 60 Hz, Generac PowerPact 6/7.5 kW 60 Hz
Problem 18Shutdown Alarm/Fault OccurredGenerac 10 KW, Generac 13 kW, Generac 14 kW, Generac 15 kW, Generac 16 kW, Generac 17 kW
Problem 20Engine Will Not Crank When Utility Power Source FailsVerify utility source is "OFF"; Test 52 – Check Position of Auto-Off-Manual Mode; Test 53 – Try a Manual Start; if switch is in "AUTO" and engine does not crank, go to Problem 21; if switch is "OFF", set to "AUTO" - retest; if switch is "ON", turn "OFF" - retest; replace controller assembly; Test 55 – Check 7.5 Amp Fuse; Test 56 – Check Battery; Test 58 – Check Starter Contactor; Test 59 – Test Starter Motor; recharge/replace; replaceGenerac CorePower 6/7 kW, Generac PowerPact 5.6 kVA 50 Hz, Generac PowerPact 6/7 kW 60 Hz, Generac PowerPact 6/7.5 kW 60 Hz
Problem 21Engine Will Not Crank When Controller is Set to "MANUAL" ModeTest 55 – Check 7.5 Amp Fuse; Test 56 – Check Battery; Test 57 – Check Wire 56 Voltage; Test 58 – Check Starter Contactor; Test 59 – Test Starter Motor; replace controller assembly; recharge/replace; replaceGenerac CorePower 6/7 kW, Generac PowerPact 5.6 kVA 50 Hz, Generac PowerPact 6/7 kW 60 Hz, Generac PowerPact 6/7.5 kW 60 Hz
Problem 22Engine Cranks but Won't StartCheck air filter - replace as needed; Test 60 – Check Fuel Supply and Pressure; Test 61 – Check Controller Wire 14 Output; Test 62 – Check Fuel Solenoid; Test 63 – Check Choke Solenoid; Test 64 – Check for Ignition Spark; Test 65 – Check Spark Plugs; Test 66 – Check Engine Compression; Test 67 – Check Ignition Magneto; Test 70 – Check and Adjust Valves; Test 79 – Check Shutdown Wire; contact technical service; replace choke solenoid; clean, regap or replace; replace controller; replace fuel solenoid; replace fuel regulator; adjust or replace; repair or replace shorted wire 18 or controller; check flywheel key; find and correct cause of no fuel or low pressure; readjustGenerac CorePower 6/7 kW, Generac PowerPact 5.6 kVA 50 Hz, Generac PowerPact 6/7 kW 60 Hz, Generac PowerPact 6/7.5 kW 60 Hz
Problem 23Engine Starts Hard and Runs Rough / Lacks Power / BackfiresCheck air filter - replace as needed; Test 60 – Check Fuel Supply and Pressure; Test 63 – Check Choke Solenoid; Test 64 – Check for Ignition Spark; Test 65 – Check Spark Plugs; Test 66 – Check Engine Compression; Test 67 – Check Ignition Magnetos; Test 70 – Check and Adjust Valves; Test 13 – Check and Adjust Engine Governor; if reconfigured to LP gas, verify that proper procedure was followed (refer to Section 1.3); check flywheel key; replace choke solenoid; refer to engine service manual; readjust; adjust or replace; clean, regap or replace; find and correct cause of no fuel or low pressureGenerac CorePower 6/7 kW, Generac PowerPact 5.6 kVA 50 Hz, Generac PowerPact 6/7 kW 60 Hz, Generac PowerPact 6/7.5 kW 60 Hz
Problem 24Shutdown Alarm/Fault Occurred — Low Oil CorePowerTest 68A – Check Oil Pressure Switch and Wire 86Generac CorePower 6/7 kW, Generac PowerPact 5.6 kVA 50 Hz, Generac PowerPact 6/7 kW 60 Hz, Generac PowerPact 6/7.5 kW 60 Hz
Problem 257.5 Amp Fuse (F1) Blown — fuse blows when placed in "AUTO" or "MANUAL"Test 73 – Check Cranking and Running CircuitsGenerac CorePower 6/7 kW, Generac PowerPact 5.6 kVA 50 Hz, Generac PowerPact 6/7 kW 60 Hz, Generac PowerPact 6/7.5 kW 60 Hz
Problem 26Generator Will Not ExerciseTest 72 – Test Exercise Function; replace printed controller; repair or replaceGenerac CorePower 6/7 kW, Generac PowerPact 5.6 kVA 50 Hz, Generac PowerPact 6/7 kW 60 Hz, Generac PowerPact 6/7.5 kW 60 Hz
Problem 27No Battery Charge — no battery supply voltageTest 74 – Check Battery Charger Supply Voltage; Test 75 – Check Battery Charger Output Voltage; Test 78 – Check Wire 0/15B; repair or replace; replace chargerGenerac CorePower 6/7 kW, Generac PowerPact 5.6 kVA 50 Hz, Generac PowerPact 6/7 kW 60 Hz, Generac PowerPact 6/7.5 kW 60 Hz
QAW WARNINGGenerac NP-30G
Regen InhibitRegen Inhibit — Control system not allowing high idle that engine has requestedGenerac MFH900
RPM SENSE LOSSUnit was running and shut down, attempts to restart — LED redCheck the LEDs / screen for alarmsClear alarm and remove household loads from the generator. Put into AUTO and restart. If generator does not start, contact an IASD.Generac 0066780, Generac 10 KVA, Generac 10 KW, Generac 10 kW, Generac 100 kW / 130 kW / 150 kW, Generac 11 kW
RPM SENSE LOSSUnit will not start in AUTO with remote start signal — LED redCheck the LEDs / screen for alarmsClear alarm. Using the control panel, check the battery by navigating to the BATTERY MENU option from the MAIN MENU. If battery condition displays GOOD, contact an IASD. If control panel displays CHECK BATTERY, replace the battery.Generac 0066780, Generac 10 KVA, Generac 10 KW, Generac 10 kW, Generac 100 kW / 130 kW / 150 kW, Generac 11 kW
RTCbatteryFlatThis warning message "RTCbatteryFlat" appears in Alarmlist when battery is close to be completely flatIf power supply cut comes when the RTC battery is flat, the statistic values, history and setpoints settings are lostSend a controller to your distributor for battery exchange if the RTCbatteryFlat message is displayedGenerac MGG280, Generac MGG350N2
Run AwayIn the event of the generator output frequency rising above the configured Trip value, the Run Away Shutdown alarm is immediately triggered. This is used to protect against engine damage due to uncontrolled speed increase.Generator output frequency exceeds the configured trip value.DSE7310 MKII controller
Run AwayImmediate Shutdown alarm triggered when the engine speed rises above the configured Trip value.DSE7310 MKII controller
S1Overspeed ShutdownDo not attempt a manual adjustment to control the engine speed.Generac NP-30G
SDShut down alarmGenerac H-100
Sd ECUSd ECU — normal during a controller power loss; can be cleared immediatelyGenerac MGG450
SERVICE AYellow LED illuminated in any stateCheck the screen for additional informationPerform SERVICE A maintenance. Press ENTER to clear.Generac 10 KVA, Generac 10 KW, Generac 10 kW, Generac 11 kW, Generac 12 kW, Generac 13 kVA
SERVICE BYellow LED illuminated in any stateCheck the screen for additional informationPerform SERVICE B maintenance. Press ENTER to clear.Generac 10 KVA, Generac 10 KW, Generac 10 kW, Generac 11 kW, Generac 12 kW, Generac 13 kVA
Service DueService Due — Service is due for one or more of: Engine oil; Air filter; Engine fuel filter; Hydraulic oil filtersSee Draining Fluids—Union Fluid Drain.Generac MFH900
SERVICE SCHEDULE AWarning activePerform SERVICE SCHEDULE A maintenance; press ENTER to clear.Generac 0066780, Generac 100 kW / 130 kW / 150 kW, Generac 12.0DTA, Generac 48 KW, Generac 60 KW, Generac 80 kW
SERVICE SCHEDULE BWarning activePerform SERVICE SCHEDULE B maintenance; press ENTER to clear.Generac 0066780, Generac 100 kW / 130 kW / 150 kW, Generac 12.0DTA, Generac 48 KW, Generac 60 KW, Generac 80 kW
SERVICE SCHEDULE CWarning activePerform SERVICE SCHEDULE C maintenance; press ENTER to clear.Generac 0066780, Generac 100 kW / 130 kW / 150 kW, Generac 12.0DTA, Generac 48 KW, Generac 60 KW, Generac 80 kW
SHAinCfgErrShared Analog module configuration errorMore than one source module (SHAOUT) were configured (on the CAN2 bus)Make sure that only one SHAOUT x module is configured in controllersGenerac MGG280, Generac MGG350N2
Short Circuit IDMT AlarmGenerator output current rose above the Short Circuit Trip for the duration of the IDMT function.DSE7310 MKII controller
SHUTDOWN SWITCHUnit will not start — LED flashing redSet emergency shutdown switch(es) to CLOSED (I). Clear alarmGenerac G0072100
SMM Problem 1Load Management Module (SMM) LED is OFF, Load Not PoweredVerify utility available and/or generator on; enable MLCB and/or verify generator operation; enable circuit breaker; check wiring to SMM and connections inside SMM; line voltage must connect to the left side of the contactor, load to the right side; retestGenerac CorePower 6/7 kW, Generac PowerPact 5.6 kVA 50 Hz, Generac PowerPact 6/7 kW 60 Hz, Generac PowerPact 6/7.5 kW 60 Hz
SMM Problem 2Load Management Module (SMM) LED is ON, Load Not PoweredGenerator was overloaded, shed occurred and power applied to SMM; this will also occur if utility power was just applied (except if transferring from gen to utility)Test 37 – Check Voltage at ContactorGenerac CorePower 6/7 kW, Generac PowerPact 5.6 kVA 50 Hz, Generac PowerPact 6/7 kW 60 Hz, Generac PowerPact 6/7.5 kW 60 Hz
SMM Problem 3Load Management Module (SMM) LED is Flashing, Load Not Powered — LED flashing 1 second intervalGenerator overloaded while attempting recovery from sheddingWait 5 minutes plus the priority time delay for SMM to enable output; review all enabled loads; disable suspect loads to prevent overload from recurringGenerac CorePower 6/7 kW, Generac PowerPact 5.6 kVA 50 Hz, Generac PowerPact 6/7 kW 60 Hz, Generac PowerPact 6/7.5 kW 60 Hz
SMM Problem 4Load Management Module (SMM) is Humming or Buzzing — humming sound coming from SMM, load not poweredImproper mounting or incorrect connectionsMount securely to wall or vertical surface with arrows pointing up only; note: PMM must have 240 VAC to operate correctly; Test 37 – Check Voltage at ContactorGenerac CorePower 6/7 kW, Generac PowerPact 5.6 kVA 50 Hz, Generac PowerPact 6/7 kW 60 Hz, Generac PowerPact 6/7.5 kW 60 Hz
Start Fail AlarmStart Fail Alarm — controller alarm sounds and LCD window displays "Start Fail Alarm" after three start attemptsEngine fails to start after a pre-specified duration of cranking (three crank cycles of 15 seconds each, followed by a 15 second pause to cool the starter).Generac MGG450
STEPPER OVERCURRENTUnit will not start in AUTO with remote start signal — LED redCheck the LEDs / screen for alarmsContact an IASD.Generac 10 KVA, Generac 10 KW, Generac 10 kW, Generac 11 kW, Generac 12 kW, Generac 13 kVA
T1Blown T1 fuseGenerac CorePower 6/7 kW, Generac PowerPact 5.6 kVA 50 Hz, Generac PowerPact 6/7 kW 60 Hz, Generac PowerPact 6/7.5 kW 60 Hz
T1High Temperature ShutdownGenerac NP-30G
TDNHTS has detected utility present, but loss of communications with the H-100 Control Panel.Generac H-100
TEST 2VOLTAGE REGULATOR LAMPSGenerac 9344, Generac IM Series, Generac NP Series
TEST 3REPLACE VOLTAGE REGULATORGenerac 9344, Generac IM Series, Generac NP Series
TEST 4TEST EXCITATION CIRCUIT BREAKERGenerac 9344, Generac IM Series, Generac NP Series
TEST 5TEST EXCITATION WINDINGGenerac 9344, Generac IM Series, Generac NP Series
TEST 6TEST THERMAL PROTECTORGenerac 9344, Generac IM Series, Generac NP Series
TEST 7TEST EXCITATION LEADSGenerac 9344, Generac IM Series, Generac NP Series
TEST 8REGULATOR TEST & ADJUSTGenerac 9344, Generac IM Series, Generac NP Series
TEST 9CHECK SENSING LEADS TRANSFORMER POWER WINDINGSGenerac 9344, Generac IM Series, Generac NP Series
TEST 10STATOR AC GOODGenerac 9344, Generac IM Series, Generac NP Series
TEST 11TEST Rotor Brushes AND Wires No. 1 & 4 BOOSTGenerac 9344, Generac IM Series, Generac NP Series
TEST 12CHECK FIELDGenerac 9344, Generac IM Series, Generac NP Series
TEST 13CHECK SLIP RINGS 1 AND 4Generac 9344, Generac IM Series, Generac NP Series
TEST 14RECONNECT, REPAIR OR REPLACE BAD WIRE(S) OR PART(S)Generac 9344, Generac IM Series, Generac NP Series
TEST 15CHECK BOTH VOLTAGE AND FREQUENCYGenerac 9344, Generac IM Series, Generac NP Series
TEST 16ADJUST ENGINE GOVERNORGenerac 9344, Generac IM Series, Generac NP Series
TEST 17CHECK VOLTAGE REGULATORGenerac 9344, Generac IM Series, Generac NP Series
TEST 18UNIT IS NOT OVERLOADEDGenerac 9344, Generac IM Series, Generac NP Series
TEST 19REPAIR ENGINE POWERGenerac 9344, Generac IM Series, Generac NP Series
Trblsht003Defective Control Module circuit boardReplace board.Generac 36kW Models
UNDER SPEEDUnit will not start in AUTO with utility lossGenerac 100 kW / 130 kW / 150 kW, Generac 12.0DTA, Generac 48 KW, Generac 60 KW, Generac 80 kW
Under Speed AlarmShutdown or Warning depending on configuration: The engine speed falling below the configured Under Speed Alarm Trip value for longer than the Activation Delay.DSE7310 MKII controller
UNDER VOLTAGEUnit will not start in AUTO with utility lossCheck the LEDs/Screen for alarms.Contact Independent Authorized Servicing Dealer.Generac 0066780, Generac 100 kW / 130 kW / 150 kW, Generac 12.0DTA, Generac 15 kW EcoGen, Generac 48 KW, Generac 60 KW
UNDERSPEEDUnit will not start in AUTO with remote start signal — LED redCheck the LEDs / screen for alarmsContact an IASD.Generac 0066780, Generac 10 KVA, Generac 10 KW, Generac 10 kW, Generac 11 kW, Generac 12 kW
UnderspeedEngine speed has fallen below its configured underspeed alarm level.Generac MLT4200IF4
UNDERSPEED - 6 FLASHES OF LED6 flashes of LEDPlease reference Appendix 1, Troubleshooting, if this fault occurs.Generac Centurion 3500
UNDERVOLTAGEUnit will not start in AUTO with remote start signal — LED redCheck the LEDs / screen for alarmsContact an IASD.Generac 10 KVA, Generac 10 KW, Generac 10 kW, Generac 11 kW, Generac 12 kW, Generac 13 kVA
V1Low Voltage ShutdownGenerac NP-30G
W000146Do not alter construction of, installation, or block ventilation for generator. Failure to do so could result in unsafe operation or damage to the generator.Generac XG03245, Generac XG04045, Generac XG04845
W000163Do not open or mutilate batteries. Batteries contain electrolyte solution which can cause burns and blindness. If electrolyte contacts skin or eyes, flush with water and seek immediate medical attention.Generac XG03245, Generac XG04045, Generac XG04845
W000209Loss of life.Generac XG03245, Generac XG04045, Generac XG04845
Water In FuelWater In Fuel — Water detected in fuelGenerac MFH900
WIRING ERRORUnit will not start in AUTO with utility loss.Check for alarmsContact servicing dealer.Generac 10 KW, Generac 10 kW, Generac 100 kW / 130 kW / 150 kW, Generac 12.0DTA, Generac 14 kW, Generac 18 kW
Wrong configWrong controller configuration indication. Indicates that controller hardware doesn't support PLC used in configurationTo check it send the IDch and Dngl strings from controller Info screen 2 and archive to your technical supportGenerac MGG280, Generac MGG350N2
YELLOWYellow LED illuminated in any state.Check the screen for additional information. Perform SERVICE A maintenance. Press ENTER to clear.Generac G0070420

Compiled from Generac service manuals and controller documentation. 37 code numbers mean different things on different controllers; each meaning is listed with the models it applies to. Cause/remedy shown where extracted; always verify against the manual for your exact model.

Common questions

What does Generac fault code 0 mean?

Utility failure. Remedy: Crank and start engine, transfer load to Generator if Utility returns above 75% nominal for 15 seconds.

What does Generac fault code 0F9677 mean?

Engine won’t crank.. Remedy: Replace fuse..

What does Generac fault code 0G0008 mean?

Engine cranks but won't start. Remedy: Tighten, clean or replace battery cables; replace starter contactor or motor; replace battery if dead..

What does Generac fault code 0G0056 mean?

Engine cranks but won't start. Remedy: Tighten, clean or replace battery cables; replace starter contactor or motor; replace battery if dead..

What does Generac fault code 1-1 mean?

CO Monitor. Remedy: Move generator outside. Contact IASD..

What does Generac fault code 1-2 mean?

Battery Voltage. Cause: Battery voltage above normal operating range. Remedy: Contact IASD.

What does Generac fault code 1-3 mean?

Battery Voltage. Cause: Battery voltage below normal operating range. Remedy: Charge battery to correct level.

What does Generac fault code 2 flashes of LED mean?

OVERCRANK — 2 flashes of LED. Cause: No fuel to the engine. Remedy: Make sure that the tanks are full and the valves are opened.

What does Generac fault code 3 flashes of LED mean?

OVERSPEED — 3 flashes of LED. Cause: Governor spring is disconnected. Remedy: Reconnect spring. Spring should be in the second hole from the bottom (shaft end) of the governor arm.

What does Generac fault code 4 flashes of LED mean?

LOW OIL PRESSURE — 4 flashes of LED. Cause: Engine oil is low. Remedy: Check and fill engine oil. Check generator compartment for leaks.

What does Generac fault code 5 flashes of LED mean?

HIGH TEMPERATURE — 5 Flashes of LED. Cause: Engine oil is low. Remedy: Check and fill engine oil.

What does Generac fault code 5-2 mean?

Engine Speed. Cause: No or low fuel; Engine speed below normal operating range. Remedy: Fill fuel tank; Contact IASD.

What does Generac fault code 6 flashes of LED mean?

UNDERSPEED — 6 flashes of LED. Cause: Fuel supply is low. Remedy: Check and replenish fuel supply.

What does Generac fault code 6-1 mean?

Engine Oil Pressure. Cause: Low oil pressure; Switch voltage not detected. Remedy: Fill crankcase to correct level; Contact IASD.