Generac Fault Codes

266 Generac generator fault/alarm codes with symptom, cause and remedy — compiled from Generac service and controller documentation.

Fault / alarm codes

266
CodeMeaning / symptomCauseRemedy Models affected
(000139)Low oil pressure shutdownLow oil levelVerify oil level on dipstick. Add oil, if needed.Generac MLT3080KV, Generac MLT4150, Generac MLT4200, Generac MLT5150, Generac MLT5200, Generac MLT5200ICAN
(000278)High coolant temperature shutdownLow coolant levelAdd coolant if needed. Allow engine to cool, then check coolant level in radiator. Restart engine and check coolant temperature. Stop engine immediately if coolant temperature is 210°F (99°C) or more.Generac MLT4150, Generac MLT4200
0Utility failureCrank and start engine, transfer load to Generator if Utility returns above 75% nominal for 15 secondsGenerac 10 kW, Generac 13 kW, Generac 14 kW, Generac 15 kW, Generac 16 kW, Generac 17 kW
000001DANGERGenerac 10 KVA, Generac 10 kW, Generac 11 kW, Generac 13 kVA, Generac 13 kW, Generac 14 kW
000002AVERTISSEMENTGenerac G0070420
000003MISE EN GARDEGenerac G0070420
000100aConsultez le manuel.Generac G0070420
000103DANGERGenerac G0070420, Generac GP5500E, Generac Mod A
000105Explosion et incendie.Generac G0072100, Generac MGG450
000107WARNING Hearing LossGenerac MGG450
000108Surfaces chaudes.Generac G0070420, Generac MGG450
000111Pièces mobiles.Generac G0070420, Generac MGG450
000115Daño al motor. Verifique el tipo y la cantidad apropiados del aceite del motor antes de poner en marcha el motor. No hacer esto puede provocar daños al motor.Verify the appropriate type and quantity of engine oil before starting the engine.Generac G0070420, Generac GP5500E, Generac Mod A
000130Démarrage accidentel.Generac G0070420
000136Equipment and property damageDisconnect electrical loadsGenerac 15,5 / 18,0 kW**, Generac GP Series Portable Generator, Generac GP18000EFI, Generac GP5500E, Generac Mod A, Generac Portables
000137aEquipment and property damageGenerac 22 kW 2.4L, Generac 25 kW 1.5L, Generac 27 kW 2.4L, Generac 30 kW 1.5L, Generac 32 kW 2.4L, Generac 36 kW 2.4L
000141Accidental start-up. Disconnect spark plug wires when working on unit.Disconnect spark plug wires before working on unit.Generac IQ3500
000146Dommages à l’équipement et aux biens.Generac G0070420
000149Risk of poisoningGenerac SG100
000151La branchement à une source de carburant doit être effectué par un technicien ou un entrepreneur professionnel qualifié.Generac G0070420
000155Seul un électricien formé et agréé devrait s’occuper du câblage et des connexions à l’appareil.Generac G0070420
000162ExplosionGenerac 22 kW 2.4L, Generac 25 kW 1.5L, Generac 27 kW 2.4L, Generac 30 kW 1.5L, Generac 32 kW 2.4L, Generac 36 kW 2.4L
000164Electrical shockGenerac 22 kW 2.4L, Generac 25 kW 1.5L, Generac 27 kW 2.4L, Generac 30 kW 1.5L, Generac 32 kW 2.4L, Generac 36 kW 2.4L
000165aRisk of overheatingGenerac SG100
000178aAsphyxie.Generac G0070420
000182Seul un technicien qualifié peut installer, utiliser et entretenir cet équipement.Generac G0070420
000182aEquipment damageGenerac SG100
000183Recoil HazardGenerac GP5500E, Generac Mod A
000187Electrocución.Generac G0070420
000190Loss of life. Property damage.Generac 22 kW 2.4L, Generac 25 kW 1.5L, Generac 27 kW 2.4L, Generac 30 kW 1.5L, Generac 32 kW 2.4L, Generac 36 kW 2.4L
000191DO NOT OPERATEGenerac 22 kW 2.4L, Generac 25 kW 1.5L, Generac 27 kW 2.4L, Generac 30 kW 1.5L, Generac 32 kW 2.4L, Generac 36 kW 2.4L
000192Engine downGenerac 22 kW 2.4L, Generac 25 kW 1.5L, Generac 27 kW 2.4L, Generac 30 kW 1.5L, Generac 32 kW 2.4L, Generac 36 kW 2.4L
000199PELIGROGenerac GP5500E, Generac Mod A
000200PELIGROGenerac GP5500E, Generac Mod A
000209aCe produit n’est pas conçu pour être utilisé dans un système de maintien de la vie.Generac G0070420
000209bDanger de mort. Ce produit ne doit pas être utilisé dans une application critique de support de vie.Generac G0072100, Generac MGG450
000216Blessures et dommages à l’équipement.Generac G0070420
000218Explosion et incendieGenerac G0070420
000228Environmental HazardGenerac 22 kW 2.4L, Generac 25 kW 1.5L, Generac 27 kW 2.4L, Generac 30 kW 1.5L, Generac 32 kW 2.4L, Generac 36 kW 2.4L
000231aWARNING (000231a)Generac MGG450
000234aWARNING Crushing hazardGenerac MGG450
000235WARNING Property or Equipment DamageGenerac MGG450
000237Retour d’énergie électrique.Generac G0070420
000247Cet appareil n’est pas conçu pour être utilisé comme source d’alimentation principale.Generac G0070420
000247aADVERTÊNCIAGenerac G0072100
000278Mast Lights Off, but Ballast Indicators on Control Panel are On.Light fixture is too hot. Faulty lamp connection. Lamp broken Loose lighting connections Damaged or loose electrical cordAllow light to cool 10-15 minutes before restarting. Check that the lamp is tight in the socket. Check for broken arc tube or outer lamp jacket, broken or loose components in lamp envelope, or blackening/deposits inside tube. Check the connections inside the mast junction box and each mast light housing/socket. Check the mast electrical cord for damage and check the cord connections inside the control box.Generac MLT Light Tower
001063CAUTION Figure 4-1. Gearbox Oil Servicing PointsGenerac SG100
001810Auxiliary ShutdownGenerac G0072100
002404Inspect Spark Arrestor ScreenInspect and clean the screen every 50 hours of operation or every season, whichever comes first.Generac IQ3500
005483Daños a los equipos y la propiedad.Generac IQ3500
005492Daño para el equipoGenerac G0072100
007634(000209b) Fallecimiento. Este producto no se ha diseñado para que se utilice en aplicaciones de apoyo vital crítico. En caso de hacerlo, podría provocar la muerte o lesiones graves.Generac IQ3500
007843OUTPUT FAULTGenerac IQ3500
007846Output FaultGenerac IQ3500
008034Fault Output MGenerac IQ3500
009209Puesta en marcha automáticaGenerac G0072100
013428Vision LossGenerac GP5500E, Generac Mod A
020000Explosion and FireGenerac GP5500E, Generac Mod A
020423Accidental Start-upGenerac GP5500E, Generac Mod A
057-243Generator Under Volts gives a warning alarm in the event of the generator output falling below the configured Under Volts Pre-Alarm Trip value for longer than the Activation Delay.
0F9677Engine won’t crank.Replace fuse.Generac 2.4L 45kW, Generac 2.4L 60kW, Generac 45 KW, Generac 60 KW
0G0008Engine cranks but won't startTighten, clean or replace battery cables; replace starter contactor or motor; replace battery if dead.Generac 2.4L 45kW, Generac 2.4L 60kW, Generac 45 KW, Generac 60 KW
0G0056Engine cranks but won't startTighten, clean or replace battery cables; replace starter contactor or motor; replace battery if dead.Generac 2.4L 45kW, Generac 2.4L 60kW, Generac 45 KW, Generac 60 KW
1Ignition cannot initialize1. Replace fuse. 2. Tighten, clean or replace battery cables as necessary. 3. Replace contactor.* 4. Replace starter motor.* 5. Remove, change or replace battery. 6. Replace fuse.*Generac 22 kW, Generac 22/27 kW, Generac 25 kW, Generac 27 kW, Generac 30 KW, Generac 35 KW
1-1CO MonitorMove generator outside. Contact IASD.Generac 15,5 / 18,0 kW**, Generac GP Series Portable Generator, Generac GP18000EFI, Generac Portables
1-2Battery Voltage1. Battery voltage above normal operating range.1. Contact IASD.Generac 15,5 / 18,0 kW**, Generac GP Series Portable Generator, Generac GP18000EFI, Generac Portables
1-3Battery VoltageCharge battery to correct level.Generac 15,5 / 18,0 kW**, Generac GP Series Portable Generator, Generac GP18000EFI, Generac Portables
10Defective Low Coolant Level SwitchSee Fault Code Example or contact IASD.Generac 15,5 / 18,0 kW**, Generac 22 kW, Generac 22/27 kW, Generac 25 kW, Generac 27 kW, Generac 30 KW
10 kWAuto/Off/Manual switch is set to OFF, but the engine continues to run.Generac 0E8012, Generac Models:, Generac Number, Generac YEAR
1048Unit shuts down during operation.Alternator, AVR or wiring is damaged.Contact servicing dealer.Generac 15 kW EcoGen
1049 VSCFOverload RED Unit shuts down during operation.Check the LEDs/Screen for alarms. Generator output is shorted or severely overloaded. Identify and clear the overload, and then restart.Generac MMG25IF4, Generac MMG35DF4, Generac MMG45IF4, Generac MMG55DF4
1051Yellow LED illuminated in any state.Voltage supply to the AVR is high. If an external battery charger is in use, contact installing dealer to correct installation. If an external battery charger is NOT in use, contact servicing dealer.Generac 15 kW EcoGen
1051 VSCFHigh Battery YELLOW LED illuminated in any state.Check the LEDs/Screen for alarms. Voltage supply to the AVR is high. If an external battery charger is in use, contact installing dealer to correct installation. If an external battery charger is NOT in use, contact Independent Authorized Servicing Dealer.Generac MMG25IF4, Generac MMG35DF4, Generac MMG45IF4, Generac MMG55DF4
1052Unit shuts down during operation or starting.Probable causes are: 1) The generator was temporarily overloaded. 2) The output was temporarily shorted. Try to restart the unit.Generac 15 kW EcoGen
1052 VSCFDC Overvoltage RED Unit shuts down during operation.Check the LEDs/Screen for alarms. Probable causes are: 1) The generator was temporarily overloaded. 2) The output was temporarily shorted. Try to restart the unit.Generac MMG25IF4, Generac MMG35DF4, Generac MMG45IF4, Generac MMG55DF4
1053 VSCFGate Fault RED Unit shuts down during operation or starting.Check the LEDs/Screen for alarms. AVR is damaged. Contact Independent Authorized Servicing Dealer.Generac MMG25IF4, Generac MMG35DF4, Generac MMG45IF4, Generac MMG55DF4
1055Unit shuts down during starting.An incorrect voltage and frequency has been detected during starting. Probable causes are: 1) Alternator damage. Contact servicing dealer. 2) Generator has started into a severe load. Manually operate generator breaker and try to restart unit. If problem persists, remove load and attempt to restart unit again. 3) The engine may not be reaching its prescribed speed. Proceed as follows: •Verify stepper motor is moving and linkage is free. •Verify stepper motor is plugged in. •Verify gas pressure is within specified limits.Generac 15 kW EcoGen
1055 VSCFPhase Error RED Unit shuts down during starting.Check the LEDs/Screen for alarms. An incorrect voltage and frequency has been detected during starting. Probable causes are: 1) Alternator damage. Contact Independent Authorized Servicing Dealer. 2) Generator has started into a severe load. Manually operate generator breaker and try to restart unit. If problem persists, remove load and attempt to restart unit again. 3) The engine may not be reaching its prescribed speed. Proceed as follows: •Verify stepper motor is moving and linkage is free. •Verify stepper motor is plugged in. •Verify gas pressure is within specified limits.Generac MMG25IF4, Generac MMG35DF4, Generac MMG45IF4, Generac MMG55DF4
1056 VSCFUndervoltage RED Unit shuts down during operation or starting.Check the LEDs/Screen for alarms. The generator output voltage is too low. Probable causes are: 1) The load is too large. Remove load and attempt to restart unit. 2) Alternator or AVR damage. Contact Independent Authorized Servicing Dealer.Generac MMG25IF4, Generac MMG35DF4, Generac MMG45IF4, Generac MMG55DF4
1057 VSCFOvervoltage RED Unit shuts down during operation or starting.Check the LEDs/Screen for alarms. Probable causes are: 1) The generator has been overloaded. Remove load and attempt to restart unit. 2) Generator has started into a severe load. Manually operate generator breaker and try to restart unit. If problem persists, remove load and attempt to restart unit again.Generac MMG25IF4, Generac MMG35DF4, Generac MMG45IF4, Generac MMG55DF4
1058 VSCFDC Undervoltage RED Unit shuts down during operation or starting.Check the LEDs/Screen for alarms. The DPE winding supplies this voltage. 1) Alternator damage. Contact Independent Authorized Servicing Dealer.Generac MMG25IF4, Generac MMG35DF4, Generac MMG45IF4, Generac MMG55DF4
1059Unit detects no output voltage while starting.Alternator damage. Contact servicing dealer.Generac 15 kW EcoGen
1059 VSCFField Loss RED Unit shuts down during starting.Check the LEDs/Screen for alarms. Unit detects no output voltage while starting. 1) Alternator damage. Contact Independent Authorized Servicing Dealer.Generac MMG25IF4, Generac MMG35DF4, Generac MMG45IF4, Generac MMG55DF4
1061Unit detects loss of output voltage while running.Alternator damage. Contact servicing dealer.Generac 15 kW EcoGen
1061 VSCFField Loss RED Unit shuts down during operation.Check the LEDs/Screen for alarms. Unit detects loss of output voltage while running. 1) Alternator damage. Contact Independent Authorized Servicing Dealer.Generac MMG25IF4, Generac MMG35DF4, Generac MMG45IF4, Generac MMG55DF4
1065Overfrequency RED Unit shuts down during operation.Check the LEDs/Screen for alarms. Probable causes are: 1) Overload. Remove load and attempt to restart unit. 2) RPM sensor has failed. Contact Independent Authorized Servicing Dealer. 3) Stepper motor problem. Contact Independent Authorized Servicing Dealer.Generac MMG25IF4, Generac MMG35DF4, Generac MMG45IF4, Generac MMG55DF4
1066 VSCFSpeed mismatch RED Unit shuts down during Operation or starting.Check the LEDs/Screen for alarms. Probable causes are: 1) Fuel problem (pressure loss). Check fuel supply and attempt to restart unit. 2) Large overload. Remove load and attempt to restart unit. 3) Throttle or engine problem. Contact Independent Authorized Servicing Dealer.Generac MMG25IF4, Generac MMG35DF4, Generac MMG45IF4, Generac MMG55DF4
1070"Small fan failure" is displayed.Small fan current incorrect. Probable causes are: 1) Fan wiring or mechanical problem. Contact servicing dealer. 2) Air path is blocked. Check AVR filter.Generac 15 kW EcoGen
11Fuel Injector FailureSee Fault Code Example or contact IASD.Generac 15,5 / 18,0 kW**, Generac 22 kW, Generac 22/27 kW, Generac 25 kW, Generac 27 kW, Generac 30 KW
11 kWThere is no AC output from the generator.Reset circuit breaker to ON (or closed).Generac 0E8012, Generac Models:, Generac Number, Generac YEAR
1100Condition - Engine Cranks but will not Start (5 crank attempts)Unit turns over but will not start. Controller is receiving signal on Wire 18.Problem 17Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10000006453-E WD/SD Air-cooled HSB Evolution 2.0 w/426-460cc Engine 60 Hz
12Open/disconnected wire #15A between AUTO/OFF/MANUAL switch and Control Module circuit board.See Fault Code Example or contact IASD.Generac 15,5 / 18,0 kW**, Generac 22 kW, Generac 22/27 kW, Generac 25 kW, Generac 27 kW, Generac 30 KW
12 kWThere is no transfer to standby after utility source failure.Generac 0E8012, Generac Models:, Generac Number, Generac YEAR
12-1No AC output from generatorMain line circuit breaker is tripped/open. Generator internal failure. Thermal circuit breaker open.Generac 36kW Models
1200Prolonged (60 Hz on a 50 Hz unit, 72Hz on 60Hz unit)Over specified Hz for 3 seconds. Possible cause: Stepper motor/mixer body assembly issue.Test 54Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10000006453-E WD/SD Air-cooled HSB Evolution 2.0 w/426-460cc Engine 60 Hz
1205Instantaneous (62 Hz on a 50 Hz unit, 75Hz on 60Hz unit)Over specified Hz for 0.1 second (100 milliseconds). Possible cause: Stepper motor/mixer body assembly issue.Test 54Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10000006453-E WD/SD Air-cooled HSB Evolution 2.0 w/426-460cc Engine 60 Hz
1207Monitors zero cross timing of the AVR to determine the alternator frequency which is a speed indicator. Set for 150 milliseconds of 4500 rpm or higher. Used if the normal ignition pulse sequence(s) are not being seen by the controller.Test 64 and Test 60Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10000006453-E WD/SD Air-cooled HSB Evolution 2.0 w/426-460cc Engine 60 Hz
13Fuel Pump FailureGenerac 22 kW, Generac 22/27 kW, Generac 27 kW, Generac XT8000E
13 kWUnit consumes large amounts of oil.Generac 0E8012, Generac Models:, Generac Number, Generac YEAR
1300Occurred while runningThe default Extended alarm for low oil pressure. Check oil level and pressure.Test 61Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10000006453-E WD/SD Air-cooled HSB Evolution 2.0 w/426-460cc Engine 60 Hz
14Output FaultGenerac IQ3500
1400Condition - Air Flow Impeded / Flow IssueTest 62Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10000006453-E WD/SD Air-cooled HSB Evolution 2.0 w/426-460cc Engine 60 Hz
15Ignition FailureGenerac XT8000E
1501RPM Sensor ALARMTwin Cylinder Running faults to RPM Sensor Loss. Possible Causes: air pocket in fuel line, dirty fuel, missing ignition pulse (loss of one of the primary coils).Test 50 and Test 64Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10 KVA
1505Twin Cylinder+CrankingTwin Cylinder Cranking faults to RPM sensor loss Possible Cause: starter motor issue, missing ignition pulse (loss of one of the primary coils). If engine cranks, Test 64. If engine does not crank, Problem 15.Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10000006453-E WD/SD Air-cooled HSB Evolution 2.0 w/426-460cc Engine 60 Hz
1511Single Cylinder+RunningSingle Cylinder Running RPM sensor loss Possible Causes: air pocket in fuel line, dirty fuel. Loss of ignition pulse.Test 50 and Test 64Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10000006453-E WD/SD Air-cooled HSB Evolution 2.0 w/426-460cc Engine 60 Hz
1515Single Cylinder+CrankingSingle Cylinder Cranking faults to RPM sensor loss Possible Cause: starter motor and/or engine issue. Loss of ignition pulse. If engine cranks, Test 64. If engine does not crank, Problem 15.Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10000006453-E WD/SD Air-cooled HSB Evolution 2.0 w/426-460cc Engine 60 Hz
1600Condition - Unit is Overloaded (55 Hz for 60 Hz for 30 sec, 40 Hz for 50 Hz unit)Unit is Overloaded slowing engine speed, fuel supply low or throttle control problem.Problem 3, or Test 50, or Test 54Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10000006453-E WD/SD Air-cooled HSB Evolution 2.0 w/426-460cc Engine 60 Hz
1603UnderspeedThe engine never comes up to 3600 RPM.Check fuel selection and fuel supplyGenerac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10000006453-E WD/SD Air-cooled HSB Evolution 2.0 w/426-460cc Engine 60 Hz
17ECU Internal FailureGenerac XT8000E
18Crankshaft Position Sensor FailureAdd oil to the specified level before restarting.Generac IQ3500, Generac XT8000E
1800Prolonged Over-VoltageProblem 2Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10000006453-E WD/SD Air-cooled HSB Evolution 2.0 w/426-460cc Engine 60 Hz
19ECU ResetReduce load or check if the generator is overloaded.Generac IQ3500, Generac XT8000E
1900Prolonged Over-Voltage UndervoltageUndervoltage due to loss of voltage. Below 80% for 10+ seconds)Controller will display “WARMING UP” for 4 minutes. Refer to Section 2.2. Perform Preliminary Output Voltage Test Note: Verify controller has latest firmware.Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10 KVA
1901Instantaneous UndervoltageUndervoltage due to sudden loss of voltage. (Voltage less than 15 sec 2 sec+)Controller will display “WARMING UP” for 4 minutes. Refer to Section 2.2. Perform Preliminary Output Voltage Test Note: Verify controller has latest firmware.Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10 KVA
1902UndervoltageUndervoltage due to faulty excitation winding, or zero cross circuit, or circuit in general. Possible cause: loose wiring, field boost hardware failure. (Both zero cross missing greater than 1.5 sec)Controller will display “WARMING UP” for 4 minutes. Refer to Section 2.2. Perform Preliminary Output Voltage Test Note: Verify controller has latest firmware.Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10 KVA
1906Single Zero Cross missingUndervoltage due to faulty excitation winding, zero cross circuit, or circuit in general. Possible cause: field boost hardware failure. (One zero cross missing greater than 1.5 sec)Controller will display “WARMING UP” for 4 minutes. Refer to Section 2.2. Perform Preliminary Output Voltage Test Note: Verify controller has latest firmware.Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10000006453-E WD/SD Air-cooled HSB Evolution 2.0 w/426-460cc Engine 60 Hz
2TPS Failure1. Replenish fuel. 2. Replace solenoid.* 3. Reconnect wire. 4. Clean, regap or replace plugs. 5. Close door on tank.Generac 22 kW, Generac 22/27 kW, Generac 25 kW, Generac 27 kW, Generac 30 KW, Generac 35 KW
2098Mis-wired Customer connectionInsufficient DC voltage on transfer power output. Check for shorted 194 to ground. Refer to RTS Diagnostic Manual A0001176044.Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10000006453-E WD/SD Air-cooled HSB Evolution 2.0 w/426-460cc Engine 60 Hz
2099Wiring Error ALARMCustomer connection low voltage and high voltage wires are crossed. Check for AC voltage on Wire 194 at customer connection in generator.Generac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10 KVA
2100Stepper Overcurrent ALARMUnit is overloaded. One or both CT(s) detecting an overload condition. Check transfer switch load shed functionality. (Change load dynamics or utilize load shed). Remove LoadGenerac 0J9961-D WD/SD Air-cooled Pre 2016 Evolution 1.0 (not Evolution 2.0) 11-24 kW 60 Hz, Generac 0K2945-E WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 8 kW 60 Hz, Generac 0L6822-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 9 kW 60 Hz, Generac 0L6823-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 60 Hz, Generac 0L6824-B WD/SD Air-cooled 2017 Evolution 1.0 and newer (not Evolution 2.0) 50 Hz, Generac 10 KVA
2102Overloaded ALARMGenerac 10 KVA, Generac 10 kW, Generac 11 kW, Generac 13 kVA, Generac 13 kW, Generac 14 kW
22Engine Overspeed FailureAdd oil to the specified level before restarting.Generac IQ3500, Generac XT8000E
23Electrical TripCheck the system for any faults and correct them before restarting.Generac IQ3500
2399Overload Remove Load ALARMGenerac 10 KVA, Generac 10 kW, Generac 11 kW, Generac 13 kVA, Generac 13 kW, Generac 14 kW
24Load Stability Sensor FailureGenerac XT8000E
27Stepper Motor StuckGenerac XT8000E
28Engine Starting FailureGenerac XT8000E
3Cylinder Temp. FailureSee Fault Code Example or contact IASD.Generac 15,5 / 18,0 kW**, Generac 22 kW, Generac 22/27 kW, Generac 25 kW, Generac 27 kW, Generac 30 KW
4Air Temp. FailureGenerac 22 kW, Generac 22/27 kW, Generac 25 kW, Generac 27 kW, Generac 30 KW, Generac 35 KW
5System Voltage LowGenerac 22 kW, Generac 22/27 kW, Generac 25 kW, Generac 27 kW, Generac 30 KW, Generac OMASPFY025-030S-01
5-2Engine Speed1. No or low fuel. 2. Engine speFill fuel tank. Contact IASD.Generac 15,5 / 18,0 kW**, Generac GP Series Portable Generator, Generac GP18000EFI, Generac Portables
6System Voltage HighGenerac 22 kW, Generac 22/27 kW, Generac 25 kW, Generac 27 kW, Generac 30 KW, Generac OMASPFY025-030S-01
6-1MIL is brightly illuminated and flashing.See Trouble-shooting.Generac 15,5 / 18,0 kW**, Generac GP Series Portable Generator, Generac GP18000EFI, Generac Portables
7Cylinder High Temp.Generac 22 kW, Generac 22/27 kW, Generac 25 kW, Generac 27 kW, Generac 30 KW, Generac OMASPFY025-030S-01
7 kWEngine will not crank.Replace 15A fuse in generator control panel.Generac 0E8012, Generac Models:, Generac Number, Generac YEAR
7.5 AMP (F1) FUSE BLOWINGENGINE WILL NOT CRANKGenerac QUIETPACT 55, Generac QuietPact 65, Generac QuietPact 75
8Barometric Pressure Sensor FailureGenerac 22 kW, Generac 22/27 kW, Generac 25 kW, Generac 27 kW, Generac 30 KW, Generac OMASPFY025-030S-01
8 kWEngine cranks but will not start.Tighten, clean or replace as necessary.Generac 0E8012, Generac Models:, Generac Number, Generac YEAR
801Engine will not crankCorrect short circuit condition, replace 7.5A fuse in generator control panel. Tighten, clean or replace battery cables as necessary. Replace defective starter contactor or motor.Generac 20 kW
802Engine cranks but will not startReplenish fuel/Turn on fuel valve. Replace defective fuel solenoid or open #14 wire from engine control board. Clean, re-gap or replace spark plugs as necessary. Reset valve lash. Verify choke plate moves freely.Generac 20 kW
803Engine starts hard and runs roughCheck, replace air cleaner as necessary. Clean, re-gap or replace spark plugs as necessary. Confirm fuel pressure to regulator is 10-12” water column (0.36-0.43 psi) for LP, and 5-7” water column (0.18-0.25 psi) for natural gas. Move selector to correct position. Verify choke plate moves freely.Generac 20 kW
804AUTO/OFF/MANUAL switch is set to OFF, but the engine continues to runGenerac 20 kW
805There is no AC output from the generatorReset circuit breaker to ON (or CLOSED). Contact nearest Dealer for assistance.Generac 20 kW
806There is no transfer to standby after utility source failureGenerac 20 kW
807Unit consumes large amounts of oilAdjust oil to proper level. See 'Engine Oil Recommendations'. Check for oil leaks.Generac 20 kW
9Oil Pressure AnomalyGenerac 22 kW, Generac 22/27 kW, Generac 25 kW, Generac 27 kW, Generac 30 KW, Generac OMASPFY025-030S-01
9 kWEngine starts hard and runs rough.Generac 0E8012, Generac Models:, Generac Number, Generac YEAR
9202-1Bottom outGenerac N, Generac Q, Generac Q-Series, Generac Q70
9203-1Bottom outGenerac N, Generac Q, Generac Q-Series, Generac Q70
9204-1Bottom outGenerac N, Generac Q, Generac Q-Series, Generac Q70
9205-1Bottom out | Out-the-sideGenerac N, Generac Q, Generac Q-Series, Generac Q70
9206-1Bottom out | Out-the-sideGenerac N, Generac Q, Generac Q-Series, Generac Q70
9207-1NP 6600 120/240 55/27 60 3600 | 2300 | Bottom out |Out-the-side| 89405Generac N, Generac Q, Generac Q-Series, Generac Q70
9290-2Bottom out | Bottom outGenerac N, Generac Q, Generac Q-Series, Generac Q70
9509-26600Generac N, Generac Q, Generac Q-Series, Generac Q70
9592-15500 120/240 Bottom out UniversalGenerac N, Generac Q, Generac Q-Series, Generac Q70
9592-25500Generac N, Generac Q, Generac Q-Series, Generac Q70
9593-17000 120/240 Bottom out UniversalGenerac N, Generac Q, Generac Q-Series, Generac Q70
9593-27000 120/240 Bottom out | UniversalGenerac N, Generac Q, Generac Q-Series, Generac Q70
9600-0NP 6600 120/240 55/27 60 3600 | 2700 | Bottom out | Universal 92116Generac N, Generac Q, Generac Q-Series, Generac Q70
9600-16600 120/240 Bottom out UniversalGenerac N, Generac Q, Generac Q-Series, Generac Q70
9600-26600Generac N, Generac Q, Generac Q-Series, Generac Q70
9677-17200 120/240 Bottom out UniversalGenerac N, Generac Q, Generac Q-Series, Generac Q70
9677-27000 120/240 Bottom out UniversalGenerac N, Generac Q, Generac Q-Series, Generac Q70
9677-3Q 7000 120/240 58/29 60 3600 | 2570 | Bottom out | Universal 92116Generac N, Generac Q, Generac Q-Series, Generac Q70
9677-4Q 7000 120/240 58/29 60 3600 | 2570 | Bottom out | Universal 92116Generac N, Generac Q, Generac Q-Series, Generac Q70
9712-0NP 5000 120/240 41/20 60 3600 | 2751 Bottom out | Universal 92116Generac N, Generac Q, Generac Q-Series, Generac Q70
9712-1NP 5000 120/240 41/20 60 3600 | 2751 Bottom out | Universal 92116Generac N, Generac Q, Generac Q-Series, Generac Q70
9734-1NP 6600 120/240 55/27 60 3600 | 2700 | Bottom out | Universal 92116Generac N, Generac Q, Generac Q-Series, Generac Q70
9735-1Q 5500 120/240 46/23 60 3600 | 2570 | Bottom out | Universal 92116Generac N, Generac Q, Generac Q-Series, Generac Q70
9736-1Q 7000 120/240 58/29 60 3600 | 2570 | Bottom outGenerac N, Generac Q, Generac Q-Series, Generac Q70
99Maintenance RequiredGenerac 2.4L 45kW, Generac 2.4L 60kW, Generac 45 KW, Generac 60 KW
A0006052083Calcomanía de escape calienteGenerac GP5500E, Generac Mod A
AlNon-shut down alarmGenerac H-100
Battery Under/Over VoltageEngine’s DC supply has fallen below or risen above its configured alarm level.Generac MLT4200IF4
Battery is DeadProblem 22 – Battery is DeadTest 45 – Check Battery and CablesGenerac 10 KVA, Generac 10 kW, Generac 11 kW, Generac 12 kW, Generac 13 kVA, Generac 13 kW
C1Low Oil Pressure ShutdownCheck the engine oil level.Generac NP-30G
C2High Temperature ShutdownGenerac NP-30G
C4Low Voltage ShutdownDisconnect all loads the generator might power by whatever means provided, such as the recreational vehicle’s main circuit breaker.Generac NP-30G
Check Engine FaultA fault not recognized by the controller has been detected.Generac MLT4200IF4
EST 1Ac OUTPUT VOLTAGEGenerac IM Series, Generac NP Series
EngProt001Overcrank ShutdownOvercrank LED will turn ON. Turn OFF the AUTO/OFF/MANUAL switch, then turn switch back to AUTO to reset the generator control boardGenerac 2.4L 45kW, Generac 2.4L 60kW, Generac 45 KW, Generac 60 KW
Evolution E-Code 2400Engine Will Not Crank When Utility Power Source FailsTest 44 – Check 7.5 Amp Fuse Evolution Alarm Code 2400Generac 10 KVA, Generac 10 kW, Generac 11 kW, Generac 12 kW, Generac 13 kVA, Generac 13 kW
Evolution Fault codes 1900 - 1906Generator Shuts Down for Under VoltageGenerac Not explicitly stated
FAULT_01Generator Produces Zero Voltage or Residual VoltageGenerac CorePower 6/7 kW 60 Hz, Generac PowerPact 5.6 kVA 50 Hz, Generac PowerPact 6/7 kW 60 Hz, Generac PowerPact 6/7.5 kW 60 Hz
FAULT_02Generator Produces Low Voltage at No-LoadGenerac CorePower 6/7 kW 60 Hz, Generac PowerPact 5.6 kVA 50 Hz, Generac PowerPact 6/7 kW 60 Hz, Generac PowerPact 6/7.5 kW 60 Hz
FAULT_03Generator Produces High Voltage at No-LoadGenerac CorePower 6/7 kW 60 Hz, Generac PowerPact 5.6 kVA 50 Hz, Generac PowerPact 6/7 kW 60 Hz, Generac PowerPact 6/7.5 kW 60 Hz
FAULT_04Voltage and Frequency Drop Excessively When Loads Are AppliedGenerac CorePower 6/7 kW 60 Hz, Generac PowerPact 5.6 kVA 50 Hz, Generac PowerPact 6/7 kW 60 Hz, Generac PowerPact 6/7.5 kW 60 Hz
FIREFIREGenerac GP Series
FXXXIndicates a fault state. The DVR stops providing excitation.Generac MDG150, Generac MDG175, Generac MDG250
Generator Will Not ExerciseProblem 20 – Generator Will Not ExerciseTest 45 – Check Battery and CablesGenerac 10 KVA, Generac 10 kW, Generac 11 kW, Generac 12 kW, Generac 13 kVA, Generac 13 kW
H01Low Coolant LevelAdd coolant to the proper level.Generac SG035
H02High Coolant TemperatureReduce load or allow engine to cool.Generac SG035
H03Low Engine Oil PressureCheck and add oil if necessary, or replace oil filter.Generac SG035
H04Overspeed ShutdownReduce load immediately to prevent engine damage.Generac SG035
H05Overcrank ShutdownCheck fuel system and ignition components.Generac SG035
H06RPM Sensor Loss ShutdownCheck RPM sensor connections and replace if necessary.Generac SG035
H07Low Fuel Pressure WarningCheck fuel system for leaks or blockages.Generac SG035
HIGH TEMPERATUREUnit shuts down during operation.Check ventilation around the intake, exhaust and rear of generator.Contact s Independent Authorized Servicing Dealer if no obstruction is found.Generac MMG25IF4, Generac MMG35DF4, Generac MMG45IF4, Generac MMG55DF4
HTOHigh Temp SwitchGenerac 0F3982, Generac N, Generac Q, Generac Q-Series, Generac Q70
IDMT ALARMIf the Over Current IDMT Alarm is enabled, the controller begins following the IDMT ‘curve’ when the current on any phase passes the Trip setting. If the Trip is surpassed for an excess amount of time, the IDMT Alarm triggers (Shutdown or Electrical Trip as selected in Action). The larger the over circuit fault, the faster the trip.Generator current exceeds the trip level and remains above it for a duration that surpasses the set threshold.
IMMEDIATE WARNINGIf the Immediate Warning is enabled, the controller generates a warning alarm as soon as the Trip level is reached. The alarm automatically resets once the generator loading current falls below the Trip level (unless All Warnings are latched is enabled).Generator current exceeds the trip level.
LOPLow Oil Pressure SwitchGenerac 0F3982, Generac N, Generac Q, Generac Q-Series, Generac Q70
LOW BATTERYYellow LED illuminated in any state.Check the screen for additional information. Clear alarm. Using the control panel, check the battery by navigating to the BATTERY MENU option from the MAIN MENU. If battery condition displays GOOD, contact an IASD. If control panel displays CHECK BATTERY, replace the battery.Generac 20 kW 3-Phase
LOW FUEL LEVEL SHUT DOWNEngine automatically shuts down.Fuel level is low, fuel tank has leaks, or fuel level sender is damaged.Check the fuel level on the LCD window. Confirm that the generator is sitting level to ensure an accurate reading. Check for leaks in the fuel tank. If the fuel level is good and no leaks are found, check the fuel level sender and the connecting wiring for damage.Generac MMG50ITM, Generac MMG50ITM, MMG50ITMBAU
LOW OIL PRESSUREUnit will not start in AUTO with remote start signal.Check the LEDs / screen for alarms. Check oil level and add oil as needed. If oil level is correct, contact an IASD.Generac 15 kW EcoGen
Low Fuel LevelEngine’s fuel level has fallen below its configured low fuel level alarm.Generac MLT4200IF4
Low Oil PressureEngine oil pressure has fallen below its configured low oil pressure alarm level.Generac MLT4200IF4
M01Low Oil Pressure ShutdownCheck the engine oil level. If necessary, add oil to the FULL mark.Generac NP-30G
M02High Temperature ShutdownGenerac NP-30G
M03Overspeed ShutdownDo not attempt a manual adjustment to control engine speed.Generac NP-30G
M04Low Voltage ShutdownGenerac NP-30G
Mains Earth FaultGenerator earth fault current rose above the Mains Earth Fault Trip Level for the duration of the IDMT function.
Mains Over CurrentMains output current rose above the Mains Over Current Trip level.
Mains Phase Seq WrongPhase rotation of mains was different to configured Mains Phase Rotation Alarm setting.
MenuMenuGenerac PWRcell
No Low Speed ExerciseProblem 21 – No Low Speed ExerciseGenerac 10 KVA, Generac 10 kW, Generac 11 kW, Generac 12 kW, Generac 13 kVA, Generac 13 kW
OCField boost voltage is available.Generac IM Series, Generac NP Series
OtroMúltipleComuníquese con un IASD.Generac 15,5 / 18,0 kW**, Generac GP Series Portable Generator, Generac GP18000EFI, Generac Portables
Over Speed AlarmShutdown alarm in the event of the engine speed rising above the configured Over Speed Alarm Trip value for longer than the Activation Delay.
Over Speed Pre-AlarmWarning alarm in the event of the engine speed rising above the configured Over Speed Pre-Alarm Trip value for longer than the Activation Delay. The Warning is automatically reset when the engine speed falls below the configured Return level.
OverspeedEngine speed has risen above its configured overspeed alarm level.Generac MLT4200IF4
Overspeed shutdown.Overspeed shutdown.Check governor and throttle linkages for freedom of movement. Check overspeed switch.Generac XG03245, Generac XG04045, Generac XG04845
P0300Cylinder Misfire DetectedGenerac 4.3 Liter Gas Engine
P1034Oxygen Sensor has not toggled between indicating lean and indicating rich for at least 1 minuteGenerac H-100
Problem 18Shutdown Alarm/Fault OccurredGenerac 10 kW, Generac 13 kW, Generac 14 kW, Generac 15 kW, Generac 16 kW, Generac 17 kW
QAW WARNINGGenerac NP-30G
RPM SENSE LOSSUnit was running and shuts down, attempts to restart.Check the LEDs/Screen for alarms.Clear alarm and remove household loads from the generator. Put back in AUTO and restart. If problem returns, contact Independent Authorized Servicing Dealer to investigate possible fuel issue.Generac 15 kW EcoGen, Generac MMG25IF4, Generac MMG35DF4, Generac MMG45IF4, Generac MMG55DF4
Run AwayIn the event of the generator output frequency rising above the configured Trip value, the Run Away Shutdown alarm is immediately triggered. This is used to protect against engine damage due to uncontrolled speed increase.Generator output frequency exceeds the configured trip value.
S1Overspeed ShutdownDo not attempt a manual adjustment to control the engine speed.Generac NP-30G
SDShut down alarmGenerac H-100
Safety 001DANGERNot statedGenerac In Line, Generac Models: 005259-1, Generac Number, Generac Q, Generac QT 3.9L 40kW, Generac QT Series
Safety-001Not statedNot statedGenerac 005260-0, Generac Model
Safety001Do Not OperateGenerac 0G0238, Generac 0G1260, Generac 0G2966, Generac 22 KW - 150 KW GASEOUS STATIONARY EMERGENCY, Generac 70kW Models, Generac Model
Safety004High Coolant Temperature SwitchGenerator will automatically restart and the LED will reset once the temperature has returned to a safe operating levelGenerac 2.4L 45kW, Generac 2.4L 60kW, Generac 22 kW, Generac 22/27 kW, Generac 27 kW, Generac 36kW Models
Short Circuit IDMT AlarmGenerator output current rose above the Short Circuit Trip for the duration of the IDMT function.
T1High Temperature ShutdownGenerac NP-30G
TDNHTS has detected utility present, but loss of communications with the H-100 Control Panel.Generac H-100
TEST 10STATOR AC GOODGenerac IM Series, Generac NP Series
TEST 11TEST Rotor Brushes AND Wires No. 1 & 4 BOOSTGenerac IM Series, Generac NP Series
TEST 12CHECK FIELDGenerac IM Series, Generac NP Series
TEST 13CHECK SLIP RINGS 1 AND 4Generac IM Series, Generac NP Series
TEST 14RECONNECT, REPAIR OR REPLACE BAD WIRE(S) OR PART(S)Generac IM Series, Generac NP Series
TEST 15CHECK BOTH VOLTAGE AND FREQUENCYGenerac IM Series, Generac NP Series
TEST 16ADJUST ENGINE GOVERNORGenerac IM Series, Generac NP Series
TEST 17CHECK VOLTAGE REGULATORGenerac IM Series, Generac NP Series
TEST 18UNIT IS NOT OVERLOADEDGenerac IM Series, Generac NP Series
TEST 19REPAIR ENGINE POWERGenerac IM Series, Generac NP Series
TEST 2VOLTAGE REGULATOR LAMPSGenerac IM Series, Generac NP Series
TEST 3REPLACE VOLTAGE REGULATORGenerac IM Series, Generac NP Series
TEST 4TEST EXCITATION CIRCUIT BREAKERGenerac IM Series, Generac NP Series
TEST 5TEST EXCITATION WINDINGGenerac IM Series, Generac NP Series
TEST 6TEST THERMAL PROTECTORGenerac IM Series, Generac NP Series
TEST 7TEST EXCITATION LEADSGenerac IM Series, Generac NP Series
TEST 8REGULATOR TEST & ADJUSTGenerac IM Series, Generac NP Series
TEST 9CHECK SENSING LEADS TRANSFORMER POWER WINDINGSGenerac IM Series, Generac NP Series
Trblsht003Defective Control Module circuit boardReplace board.Generac 36kW Models
UNDERSPEED - 6 FLASHES OF LED6 flashes of LEDPlease reference Appendix 1, Troubleshooting, if this fault occurs.Generac Centurion 3500
Under Speed AlarmShutdown or Warning depending on configuration: The engine speed falling below the configured Under Speed Alarm Trip value for longer than the Activation Delay.
UnderspeedEngine speed has fallen below its configured underspeed alarm level.Generac MLT4200IF4
V1Low Voltage ShutdownGenerac NP-30G
W000146Do not alter construction of, installation, or block ventilation for generator. Failure to do so could result in unsafe operation or damage to the generator.Generac XG03245, Generac XG04045, Generac XG04845
W000163Do not open or mutilate batteries. Batteries contain electrolyte solution which can cause burns and blindness. If electrolyte contacts skin or eyes, flush with water and seek immediate medical attention.Generac XG03245, Generac XG04045, Generac XG04845
W000209Loss of life.Generac XG03245, Generac XG04045, Generac XG04845
YELLOWYellow LED illuminated in any state.Check the screen for additional information. Perform SERVICE A maintenance. Press ENTER to clear.Generac G0070420

Compiled from Generac service manuals and controller documentation. Cause/remedy shown where extracted; always verify against the manual for your exact model.

Common questions

What does Generac fault code (000139) mean?

Low oil pressure shutdown. Cause: Low oil level. Remedy: Verify oil level on dipstick. Add oil, if needed..

What does Generac fault code (000278) mean?

High coolant temperature shutdown. Cause: Low coolant level. Remedy: Add coolant if needed. Allow engine to cool, then check coolant level in radiator. Restart engine and check coolant temperature. Stop engine immediately if coolant temperature is 210°F (99°C) or more..

What does Generac fault code 0 mean?

Utility failure. Remedy: Crank and start engine, transfer load to Generator if Utility returns above 75% nominal for 15 seconds.

What does Generac fault code 000115 mean?

Daño al motor. Verifique el tipo y la cantidad apropiados del aceite del motor antes de poner en marcha el motor. No hacer esto puede provocar daños al motor.. Remedy: Verify the appropriate type and quantity of engine oil before starting the engine..

What does Generac fault code 000136 mean?

Equipment and property damage. Remedy: Disconnect electrical loads.

What does Generac fault code 000141 mean?

Accidental start-up. Disconnect spark plug wires when working on unit.. Remedy: Disconnect spark plug wires before working on unit..