Generac Fault Codes

215 Generac generator fault/alarm codes with symptom, cause and remedy — compiled from Generac service and controller documentation.

Fault / alarm codes

215
CodeMeaning / symptomCauseRemedy Models affected
(000139)Low oil pressure shutdownLow oil levelVerify oil level on dipstick. Add oil, if needed.Generac MLT3080KV, Generac MLT4150, Generac MLT4200, Generac MLT5150, Generac MLT5200, Generac MLT5200ICAN
(000278)High coolant temperature shutdownLow coolant levelAdd coolant if needed. Allow engine to cool, then check coolant level in radiator. Restart engine and check coolant temperature. Stop engine immediately if coolant temperature is 210°F (99°C) or more.Generac MLT4150, Generac MLT4200
0Utility failureCrank and start engine, transfer load to Generator if Utility returns above 75% nominal for 15 secondsGenerac 10 KW, Generac 13 KW, Generac 14 kW, Generac 15 kW, Generac 16 kW, Generac 17 kW
000001DANGERGenerac 10 KW, Generac 10 kVA, Generac 11 kW, Generac 13 KW, Generac 13 kVA, Generac 14 kW
000002AVERTISSEMENTGenerac G0070420
000003MISE EN GARDEGenerac G0070420
000100aConsultez le manuel.Generac 16 to 22 kW, Generac G0070420
000103Asphyxie.Generac 16 to 22 kW, Generac G0070420
000105Explosion et incendie.Generac G0072100, Generac MGG450
000107WARNING Hearing LossGenerac MGG450
000108Surfaces chaudes.Generac G0070420, Generac MGG450
000111Pièces mobiles.Generac G0070420, Generac MGG450
000115Pièces mobiles.Generac G0070420
000130Démarrage accidentel.Generac G0070420
000137aExplosionGenerac 22 kW 2.4L, Generac 25 kW 1.5L, Generac 27 kW 2.4L, Generac 30 kW 1.5L, Generac 32 kW 2.4L, Generac 36 kW 2.4L
000141Accidental start-up. Disconnect spark plug wires when working on unit.Disconnect spark plug wires before working on unit.Generac IQ3500
000146Dommages à l’équipement et aux biens.Generac G0070420
000149Risk of poisoningGenerac SG100
000151La branchement à une source de carburant doit être effectué par un technicien ou un entrepreneur professionnel qualifié.Generac 16 to 22 kW, Generac G0070420
000155Seul un électricien formé et agréé devrait s’occuper du câblage et des connexions à l’appareil.Generac G0070420
000162ExplosionGenerac 22 kW 2.4L, Generac 25 kW 1.5L, Generac 27 kW 2.4L, Generac 30 kW 1.5L, Generac 32 kW 2.4L, Generac 36 kW 2.4L
000164Electrical shockGenerac 22 kW 2.4L, Generac 25 kW 1.5L, Generac 27 kW 2.4L, Generac 30 kW 1.5L, Generac 32 kW 2.4L, Generac 36 kW 2.4L
000165aRisk of overheatingGenerac SG100
000178aAsphyxie.Generac G0070420
000182Seul un technicien qualifié peut installer, utiliser et entretenir cet équipement.Generac G0070420
000182aEquipment damageGenerac SG100
000187Electrocución.Generac G0070420
000190Loss of life. Property damage.Generac 22 kW 2.4L, Generac 25 kW 1.5L, Generac 27 kW 2.4L, Generac 30 kW 1.5L, Generac 32 kW 2.4L, Generac 36 kW 2.4L
000191DO NOT OPERATEGenerac 22 kW 2.4L, Generac 25 kW 1.5L, Generac 27 kW 2.4L, Generac 30 kW 1.5L, Generac 32 kW 2.4L, Generac 36 kW 2.4L
000192Engine downGenerac 16 to 22 kW, Generac 22 kW 2.4L, Generac 25 kW 1.5L, Generac 27 kW 2.4L, Generac 30 kW 1.5L, Generac 32 kW 2.4L
000209aCe produit n’est pas conçu pour être utilisé dans un système de maintien de la vie.Generac G0070420
000209bDanger de mort. Ce produit ne doit pas être utilisé dans une application critique de support de vie.Generac G0072100, Generac MGG450
000216Blessures et dommages à l’équipement.Generac G0070420
000218Explosion et incendieGenerac 16 to 22 kW, Generac G0070420
000228Environmental HazardGenerac 22 kW 2.4L, Generac 25 kW 1.5L, Generac 27 kW 2.4L, Generac 30 kW 1.5L, Generac 32 kW 2.4L, Generac 36 kW 2.4L
000231aWARNING (000231a)Generac MGG450
000234aWARNING Crushing hazardGenerac MGG450
000235WARNING Property or Equipment DamageGenerac MGG450
000237Retour d’énergie électrique.Generac 16 to 22 kW, Generac G0070420
000247Cet appareil n’est pas conçu pour être utilisé comme source d’alimentation principale.Generac G0070420
000247aADVERTÊNCIAGenerac G0072100
000278Mast Lights Off, but Ballast Indicators on Control Panel are On.Light fixture is too hot. Faulty lamp connection. Lamp broken Loose lighting connections Damaged or loose electrical cordAllow light to cool 10-15 minutes before restarting. Check that the lamp is tight in the socket. Check for broken arc tube or outer lamp jacket, broken or loose components in lamp envelope, or blackening/deposits inside tube. Check the connections inside the mast junction box and each mast light housing/socket. Check the mast electrical cord for damage and check the cord connections inside the control box.Generac MLT Light Tower, Generac MLT3060KE
001063CAUTION Figure 4-1. Gearbox Oil Servicing PointsGenerac SG100
001810Auxiliary ShutdownGenerac G0072100
002404Inspect Spark Arrestor ScreenInspect and clean the screen every 50 hours of operation or every season, whichever comes first.Generac IQ3500
005483Daños a los equipos y la propiedad.Generac IQ3500
005492Daño para el equipoGenerac G0072100
007634(000209b) Fallecimiento. Este producto no se ha diseñado para que se utilice en aplicaciones de apoyo vital crítico. En caso de hacerlo, podría provocar la muerte o lesiones graves.Generac IQ3500
007843OUTPUT FAULTGenerac IQ3500
007846Output FaultGenerac IQ3500
008034Fault Output MGenerac IQ3500
009209Puesta en marcha automáticaGenerac G0072100
057-243Generator Under Volts gives a warning alarm in the event of the generator output falling below the configured Under Volts Pre-Alarm Trip value for longer than the Activation Delay.
0F9677Engine won’t crank.Replace fuse.Generac 2.4L 45kW, Generac 2.4L 60kW, Generac 45 kW, Generac 60 kW
0G0008Engine cranks but won't startTighten, clean or replace battery cables; replace starter contactor or motor; replace battery if dead.Generac 2.4L 45kW, Generac 2.4L 60kW, Generac 45 kW, Generac 60 kW
0G0056Engine cranks but won't startTighten, clean or replace battery cables; replace starter contactor or motor; replace battery if dead.Generac 2.4L 45kW, Generac 2.4L 60kW, Generac 45 kW, Generac 60 kW
1Ignition cannot initialize1. Replace fuse. 2. Tighten, clean or replace battery cables as necessary. 3. Replace contactor.* 4. Replace starter motor.* 5. Remove, change or replace battery. 6. Replace fuse.*Generac 22 kW, Generac 22/27 kW, Generac 25 kW, Generac 27 kW, Generac 30k, Generac 35 kW
10Defective Low Coolant Level SwitchGenerac 22 kW, Generac 22/27 kW, Generac 25 kW, Generac 27 kW, Generac 30k, Generac OMASPFY025-030S-01
10 kWAuto/Off/Manual switch is set to OFF, but the engine continues to run.Generac 0E8012, Generac AND, Generac Models:, Generac YEAR, Generac number
11Defective AUTO/OFF/MANUAL switchGenerac 22 kW, Generac 22/27 kW, Generac 25 kW, Generac 27 kW, Generac 30k, Generac OMASPFY025-030S-01
11 kWThere is no AC output from the generator.Reset circuit breaker to ON (or closed).Generac 0E8012, Generac AND, Generac Models:, Generac YEAR, Generac number
12Open/disconnected wire #15A between AUTO/OFF/MANUAL switch and Control Module circuit board.Generac 22 kW, Generac 22/27 kW, Generac 25 kW, Generac 27 kW, Generac 30k, Generac OMASPFY025-030S-01
12 kWThere is no transfer to standby after utility source failure.Generac 0E8012, Generac AND, Generac Models:, Generac YEAR, Generac number
12-1No AC output from generatorMain line circuit breaker is tripped/open. Generator internal failure. Thermal circuit breaker open.Generac 36kW Models
13Engine starts then shuts down.Generac 22 kW, Generac 22/27 kW, Generac 27 kW
13 kWUnit consumes large amounts of oil.Generac 0E8012, Generac AND, Generac Models:, Generac YEAR, Generac number
14Output FaultGenerac IQ3500
14 AMP (F1) FUSE BLOWINGENGINE WILL NOT CRANKGenerac 4270
1501RPM Sensor ALARMGenerac 10 KW, Generac 10 kVA, Generac 11 kW, Generac 13 KW, Generac 13 kVA, Generac 14 kW
18Oil Level LowAdd oil to the specified level before restarting.Generac IQ3500
19OverloadReduce load or check if the generator is overloaded.Generac IQ3500
1900Prolonged Over-Voltage UndervoltageGenerac 10 KW, Generac 10 kVA, Generac 11 kW, Generac 13 KW, Generac 13 kVA, Generac 14 kW
1901Instantaneous UndervoltageGenerac 10 KW, Generac 10 kVA, Generac 11 kW, Generac 13 KW, Generac 13 kVA, Generac 14 kW
1902UndervoltageGenerac 10 KW, Generac 10 kVA, Generac 11 kW, Generac 13 KW, Generac 13 kVA, Generac 14 kW
2Engine Overspeed1. Replenish fuel. 2. Replace solenoid.* 3. Reconnect wire. 4. Clean, regap or replace plugs. 5. Close door on tank.Generac 22 kW, Generac 22/27 kW, Generac 25 kW, Generac 27 kW, Generac 30k, Generac 35 kW
2099Wiring Error ALARMGenerac 10 KW, Generac 10 kVA, Generac 11 kW, Generac 13 KW, Generac 13 kVA, Generac 14 kW
2100Stepper Overcurrent ALARMGenerac 10 KW, Generac 10 kVA, Generac 11 kW, Generac 13 KW, Generac 13 kVA, Generac 14 kW
2102Overloaded ALARMGenerac 10 KW, Generac 10 kVA, Generac 11 kW, Generac 13 KW, Generac 13 kVA, Generac 14 kW
22Oil Level LowAdd oil to the specified level before restarting.Generac IQ3500
23Electrical TripCheck the system for any faults and correct them before restarting.Generac IQ3500
2399Overload Remove Load ALARMGenerac 10 KW, Generac 10 kVA, Generac 11 kW, Generac 13 KW, Generac 13 kVA, Generac 14 kW
3No Crank SignalGenerac 22 kW, Generac 22/27 kW, Generac 25 kW, Generac 27 kW, Generac 30k, Generac 35 kW
4No Cam SignalGenerac 22 kW, Generac 22/27 kW, Generac 25 kW, Generac 27 kW, Generac 30k, Generac 35 kW
5Engine is overheated.Generac 22 kW, Generac 22/27 kW, Generac 25 kW, Generac 27 kW, Generac 30k, Generac OMASPFY025-030S-01
6Defective Low Oil Pressure SwitchGenerac 22 kW, Generac 22/27 kW, Generac 25 kW, Generac 27 kW, Generac 30k, Generac OMASPFY025-030S-01
7Defective Coolant Temperature SwitchGenerac 22 kW, Generac 22/27 kW, Generac 25 kW, Generac 27 kW, Generac 30k, Generac OMASPFY025-030S-01
7 kWEngine will not crank.Replace 15A fuse in generator control panel.Generac 0E8012, Generac AND, Generac Models:, Generac YEAR, Generac number
7.5 AMP (F1) FUSE BLOWINGENGINE WILL NOT CRANKGenerac 4702
8Defective Control Module circuit boardGenerac 22 kW, Generac 22/27 kW, Generac 25 kW, Generac 27 kW, Generac 30k, Generac OMASPFY025-030S-01
8 kWEngine cranks but will not start.Tighten, clean or replace as necessary.Generac 0E8012, Generac AND, Generac Models:, Generac YEAR, Generac number
801Engine will not crankCorrect short circuit condition, replace 7.5A fuse in generator control panel. Tighten, clean or replace battery cables as necessary. Replace defective starter contactor or motor.Generac 20 KW
802Engine cranks but will not startReplenish fuel/Turn on fuel valve. Replace defective fuel solenoid or open #14 wire from engine control board. Clean, re-gap or replace spark plugs as necessary. Reset valve lash. Verify choke plate moves freely.Generac 20 KW
803Engine starts hard and runs roughCheck, replace air cleaner as necessary. Clean, re-gap or replace spark plugs as necessary. Confirm fuel pressure to regulator is 10-12” water column (0.36-0.43 psi) for LP, and 5-7” water column (0.18-0.25 psi) for natural gas. Move selector to correct position. Verify choke plate moves freely.Generac 20 KW
804AUTO/OFF/MANUAL switch is set to OFF, but the engine continues to runGenerac 20 KW
805There is no AC output from the generatorReset circuit breaker to ON (or CLOSED). Contact nearest Dealer for assistance.Generac 20 KW
806There is no transfer to standby after utility source failureGenerac 20 KW
807Unit consumes large amounts of oilAdjust oil to proper level. See 'Engine Oil Recommendations'. Check for oil leaks.Generac 20 KW
9Coolant Level is Low.Generac 22 kW, Generac 22/27 kW, Generac 25 kW, Generac 27 kW, Generac 30k, Generac OMASPFY025-030S-01
9 kWEngine starts hard and runs rough.Generac 0E8012, Generac AND, Generac Models:, Generac YEAR, Generac number
9202-1Bottom outGenerac N, Generac Q, Generac Q70
9203-1Bottom outGenerac N, Generac Q, Generac Q70
9204-1Bottom outGenerac N, Generac Q, Generac Q70
9205-1Bottom out | Out-the-sideGenerac N, Generac Q, Generac Q70
9206-1Bottom out | Out-the-sideGenerac N, Generac Q, Generac Q70
9207-1NP 6600 120/240 55/27 60 3600 | 2300 | Bottom out |Out-the-side| 89405Generac N, Generac Q, Generac Q70
9290-2Bottom out | Bottom outGenerac N, Generac Q, Generac Q70
9509-26600Generac N, Generac Q, Generac Q70
9592-15500 120/240 Bottom out UniversalGenerac N, Generac Q, Generac Q70
9592-25500Generac N, Generac Q, Generac Q70
9593-17000 120/240 Bottom out UniversalGenerac N, Generac Q, Generac Q70
9593-27000 120/240 Bottom out | UniversalGenerac N, Generac Q, Generac Q70
9600-0NP 6600 120/240 55/27 60 3600 | 2700 | Bottom out | Universal 92116Generac N, Generac Q, Generac Q70
9600-16600 120/240 Bottom out UniversalGenerac N, Generac Q, Generac Q70
9600-26600Generac N, Generac Q, Generac Q70
9677-17200 120/240 Bottom out UniversalGenerac N, Generac Q, Generac Q70
9677-27000 120/240 Bottom out UniversalGenerac N, Generac Q, Generac Q70
9677-3Q 7000 120/240 58/29 60 3600 | 2570 | Bottom out | Universal 92116Generac N, Generac Q, Generac Q70
9677-4Q 7000 120/240 58/29 60 3600 | 2570 | Bottom out | Universal 92116Generac N, Generac Q, Generac Q70
9712-0NP 5000 120/240 41/20 60 3600 | 2751 Bottom out | Universal 92116Generac N, Generac Q, Generac Q70
9712-1NP 5000 120/240 41/20 60 3600 | 2751 Bottom out | Universal 92116Generac N, Generac Q, Generac Q70
9734-1NP 6600 120/240 55/27 60 3600 | 2700 | Bottom out | Universal 92116Generac N, Generac Q, Generac Q70
9735-1Q 5500 120/240 46/23 60 3600 | 2570 | Bottom out | Universal 92116Generac N, Generac Q, Generac Q70
9736-1Q 7000 120/240 58/29 60 3600 | 2570 | Bottom outGenerac N, Generac Q, Generac Q70
99Maintenance RequiredGenerac 2.4L 45kW, Generac 2.4L 60kW, Generac 45 kW, Generac 60 kW
AlNon-shut down alarmGenerac H-100
Battery Under/Over VoltageEngine’s DC supply has fallen below or risen above its configured alarm level.Generac MLT4200IF4
Battery is DeadProblem 22 – Battery is DeadTest 45 – Check Battery and CablesGenerac 10 KW, Generac 10 kVA, Generac 11 kW, Generac 12 kW, Generac 13 KW, Generac 13 kVA
C1Low Oil Pressure ShutdownCheck the engine oil level.Generac NP-30G
C2High Temperature ShutdownGenerac NP-30G
C4Low Voltage ShutdownDisconnect all loads the generator might power by whatever means provided, such as the recreational vehicle’s main circuit breaker.Generac NP-30G
Check Engine FaultA fault not recognized by the controller has been detected.Generac MLT4200IF4
EST 1Ac OUTPUT VOLTAGEGenerac IM Series, Generac NP Series
EngProt001Overcrank ShutdownOvercrank LED will turn ON. Turn OFF the AUTO/OFF/MANUAL switch, then turn switch back to AUTO to reset the generator control boardGenerac 2.4L 45kW, Generac 2.4L 60kW, Generac 45 kW, Generac 60 kW
Evolution E-Code 2400Engine Will Not Crank When Utility Power Source FailsTest 44 – Check 7.5 Amp Fuse Evolution Alarm Code 2400Generac 10 KW, Generac 10 kVA, Generac 11 kW, Generac 12 kW, Generac 13 KW, Generac 13 kVA
FAULT_01Generator Produces Zero Voltage or Residual VoltageGenerac CorePower 6/7 kW 60 Hz, Generac PowerPact 5.6 kVA 50 Hz, Generac PowerPact 6/7 kW 60 Hz, Generac PowerPact 6/7.5 kW 60 Hz
FAULT_02Generator Produces Low Voltage at No-LoadGenerac CorePower 6/7 kW 60 Hz, Generac PowerPact 5.6 kVA 50 Hz, Generac PowerPact 6/7 kW 60 Hz, Generac PowerPact 6/7.5 kW 60 Hz
FAULT_03Generator Produces High Voltage at No-LoadGenerac CorePower 6/7 kW 60 Hz, Generac PowerPact 5.6 kVA 50 Hz, Generac PowerPact 6/7 kW 60 Hz, Generac PowerPact 6/7.5 kW 60 Hz
FAULT_04Voltage and Frequency Drop Excessively When Loads Are AppliedGenerac CorePower 6/7 kW 60 Hz, Generac PowerPact 5.6 kVA 50 Hz, Generac PowerPact 6/7 kW 60 Hz, Generac PowerPact 6/7.5 kW 60 Hz
FCECU alarm FailureCodeGenerac MMG35D, Generac MMG45K, Generac MMG55D, Generac XXX000
FIREFIREGenerac GP Series
FXXXIndicates a fault state. The DVR stops providing excitation.Generac MDG150, Generac MDG175, Generac MDG250
FuelSys006Fuel System FaultGenerac V-type
GenTHDHighHigh Total Harmonic Distortion (THD) Measured THD is above 25%Generator power output is not stable and having high THD (THD means total harmonic distortion, which is a metric to measure the power quality. If the THD is high, the performance of your electronics will be affected; for example, you may see flickering lights).Generac G0052440, Generac G0065510, Generac G007223-0, Generac G007224-0, Generac G007225-0, Generac Guardian Series
Generator Will Not ExerciseProblem 20 – Generator Will Not ExerciseTest 45 – Check Battery and CablesGenerac 10 KW, Generac 10 kVA, Generac 11 kW, Generac 12 kW, Generac 13 KW, Generac 13 kVA
GeneratorStartFailedGenerator not startingThe generator does not start as selected in user preferences.Check if the generator 2-wire start/stop wiring to IQ System Controller is loose. Check whether the generator breaker at the unit was tripped (if so turn the breaker off and then on. Also switch the controller to the auto position), whether the generator is out of fuel, or the starting battery of the generator was dead. Contact your installer or Enphase customer support if the problem persists.Generac G0052440, Generac G0065510, Generac G007223-0, Generac G007224-0, Generac G007225-0, Generac Guardian Series
GeneratorStopFailedGenerator not stoppingGenerator continues to run even though user preferences indicate it should have stopped.Check if the generator 2-wire start/stop wiring to IQ System Controller is loose. Turn off the generator manually and contact installer or Enphase customer support.Generac G0052440, Generac G0065510, Generac G007223-0, Generac G007224-0, Generac G007225-0, Generac Guardian Series
H01Low Coolant LevelAdd coolant to the proper level.Generac SG035
H02High Coolant TemperatureReduce load or allow engine to cool.Generac SG035
H03Low Engine Oil PressureCheck and add oil if necessary, or replace oil filter.Generac SG035
H04Overspeed ShutdownReduce load immediately to prevent engine damage.Generac SG035
H05Overcrank ShutdownCheck fuel system and ignition components.Generac SG035
H06RPM Sensor Loss ShutdownCheck RPM sensor connections and replace if necessary.Generac SG035
H07Low Fuel Pressure WarningCheck fuel system for leaks or blockages.Generac SG035
HTOHigh Temp SwitchGenerac 0F3982, Generac N, Generac Q, Generac Q70
IDMT ALARMIf the Over Current IDMT Alarm is enabled, the controller begins following the IDMT ‘curve’ when the current on any phase passes the Trip setting. If the Trip is surpassed for an excess amount of time, the IDMT Alarm triggers (Shutdown or Electrical Trip as selected in Action). The larger the over circuit fault, the faster the trip.Generator current exceeds the trip level and remains above it for a duration that surpasses the set threshold.
IMMEDIATE WARNINGIf the Immediate Warning is enabled, the controller generates a warning alarm as soon as the Trip level is reached. The alarm automatically resets once the generator loading current falls below the Trip level (unless All Warnings are latched is enabled).Generator current exceeds the trip level.
LOPLow Oil Pressure SwitchGenerac 0F3982, Generac N, Generac Q, Generac Q70
LOW FUEL LEVEL SHUT DOWNEngine automatically shuts down.Fuel level is low, fuel tank has leaks, or fuel level sender is damaged.Check the fuel level on the LCD window. Confirm that the generator is sitting level to ensure an accurate reading. Check for leaks in the fuel tank. If the fuel level is good and no leaks are found, check the fuel level sender and the connecting wiring for damage.Generac MMG50ITM, Generac MMG50ITM, MMG50ITMBAU
Low Fuel LevelEngine’s fuel level has fallen below its configured low fuel level alarm.Generac MLT4200IF4
Low Oil PressureEngine oil pressure has fallen below its configured low oil pressure alarm level.Generac MLT4200IF4
M01Low Oil Pressure ShutdownCheck the engine oil level. If necessary, add oil to the FULL mark.Generac NP-30G
M02High Temperature ShutdownGenerac NP-30G
M03Overspeed ShutdownDo not attempt a manual adjustment to control engine speed.Generac NP-30G
M04Low Voltage ShutdownGenerac NP-30G
Mains Earth FaultGenerator earth fault current rose above the Mains Earth Fault Trip Level for the duration of the IDMT function.
Mains Over CurrentMains output current rose above the Mains Over Current Trip level.
Mains Phase Seq WrongPhase rotation of mains was different to configured Mains Phase Rotation Alarm setting.
MenuMenuGenerac PWRcell
No Low Speed ExerciseProblem 21 – No Low Speed ExerciseGenerac 10 KW, Generac 10 kVA, Generac 11 kW, Generac 12 kW, Generac 13 KW, Generac 13 kVA
OCField boost voltage is available.Generac IM Series, Generac NP Series
Over Speed AlarmShutdown alarm in the event of the engine speed rising above the configured Over Speed Alarm Trip value for longer than the Activation Delay.
Over Speed Pre-AlarmWarning alarm in the event of the engine speed rising above the configured Over Speed Pre-Alarm Trip value for longer than the Activation Delay. The Warning is automatically reset when the engine speed falls below the configured Return level.
OverspeedEngine speed has risen above its configured overspeed alarm level.Generac MLT4200IF4
P0300Cylinder Misfire DetectedGenerac 4.3 Liter Gas Engine
P1034Oxygen Sensor has not toggled between indicating lean and indicating rich for at least 1 minuteGenerac H-100
Problem 18Shutdown Alarm/Fault OccurredGenerac 10 KW, Generac 13 KW, Generac 14 kW, Generac 15 kW, Generac 16 kW, Generac 17 kW
QAW WARNINGGenerac NP-30G
Run AwayIn the event of the generator output frequency rising above the configured Trip value, the Run Away Shutdown alarm is immediately triggered. This is used to protect against engine damage due to uncontrolled speed increase.Generator output frequency exceeds the configured trip value.
S1Overspeed ShutdownDo not attempt a manual adjustment to control the engine speed.Generac NP-30G
SDShut down alarmGenerac H-100
Safety 001DANGERNot statedGenerac AND, Generac Models: 005259-1, Generac Q, Generac QT 3.9L 40kW, Generac QT 40kW, Generac RATED
Safety-001Not statedNot statedGenerac Q
Safety001Do Not OperateGenerac 0G0238, Generac 0G1260, Generac 0G2966, Generac 70kW Models, Generac Industrial QT
Safety004Do Not OperateGenerator will automatically restart and the LED will reset once the temperature has returned to a safe operating levelGenerac 2.4L 45kW, Generac 2.4L 60kW, Generac 22 kW, Generac 22/27 kW, Generac 27 kW, Generac 36k
Short Circuit IDMT AlarmGenerator output current rose above the Short Circuit Trip for the duration of the IDMT function.
T1High Temperature ShutdownGenerac NP-30G
TDNHTS has detected utility present, but loss of communications with the H-100 Control Panel.Generac H-100
TEST 10STATOR AC GOODGenerac IM Series, Generac NP Series
TEST 11TEST Rotor Brushes AND Wires No. 1 & 4 BOOSTGenerac IM Series, Generac NP Series
TEST 12CHECK FIELDGenerac IM Series, Generac NP Series
TEST 13CHECK SLIP RINGS 1 AND 4Generac IM Series, Generac NP Series
TEST 14RECONNECT, REPAIR OR REPLACE BAD WIRE(S) OR PART(S)Generac IM Series, Generac NP Series
TEST 15CHECK BOTH VOLTAGE AND FREQUENCYGenerac IM Series, Generac NP Series
TEST 16ADJUST ENGINE GOVERNORGenerac IM Series, Generac NP Series
TEST 17CHECK VOLTAGE REGULATORGenerac IM Series, Generac NP Series
TEST 18UNIT IS NOT OVERLOADEDGenerac IM Series, Generac NP Series
TEST 19REPAIR ENGINE POWERGenerac IM Series, Generac NP Series
TEST 2VOLTAGE REGULATOR LAMPSGenerac IM Series, Generac NP Series
TEST 3REPLACE VOLTAGE REGULATORGenerac IM Series, Generac NP Series
TEST 4TEST EXCITATION CIRCUIT BREAKERGenerac IM Series, Generac NP Series
TEST 5TEST EXCITATION WINDINGGenerac IM Series, Generac NP Series
TEST 6TEST THERMAL PROTECTORGenerac IM Series, Generac NP Series
TEST 7TEST EXCITATION LEADSGenerac IM Series, Generac NP Series
TEST 8REGULATOR TEST & ADJUSTGenerac IM Series, Generac NP Series
TEST 9CHECK SENSING LEADS TRANSFORMER POWER WINDINGSGenerac IM Series, Generac NP Series
Trblsht003Defective Control Module circuit boardReplace board.Generac 36kW Models
UNDERSPEED - 6 FLASHES OF LED6 flashes of LEDPlease reference Appendix 1, Troubleshooting, if this fault occurs.Generac Centurion 3500
Under Speed AlarmShutdown or Warning depending on configuration: The engine speed falling below the configured Under Speed Alarm Trip value for longer than the Activation Delay.
UnderspeedEngine speed has fallen below its configured underspeed alarm level.Generac MLT4200IF4
V1Low Voltage ShutdownGenerac NP-30G
W000146Do not alter construction of, installation, or block ventilation for generator. Failure to do so could result in unsafe operation or damage to the generator.Generac S
W000163Do not open or mutilate batteries. Batteries contain electrolyte solution which can cause burns and blindness. If electrolyte contacts skin or eyes, flush with water and seek immediate medical attention.Generac S
W000209Loss of life.Generac S
YELLOWYellow LED illuminated in any state.Check the screen for additional information. Perform SERVICE A maintenance. Press ENTER to clear.Generac 16 kW / 20 kW, Generac 16–22kW, Generac G0070420
nullThe door covering the customer connection lugs/cam lock receptacles is opened.Generac MMG35D, Generac MMG45K, Generac MMG55D, Generac XXX000

Compiled from Generac service manuals and controller documentation. Cause/remedy shown where extracted; always verify against the manual for your exact model.

Common questions

What does Generac fault code (000139) mean?

Low oil pressure shutdown. Cause: Low oil level. Remedy: Verify oil level on dipstick. Add oil, if needed..

What does Generac fault code (000278) mean?

High coolant temperature shutdown. Cause: Low coolant level. Remedy: Add coolant if needed. Allow engine to cool, then check coolant level in radiator. Restart engine and check coolant temperature. Stop engine immediately if coolant temperature is 210°F (99°C) or more..

What does Generac fault code 0 mean?

Utility failure. Remedy: Crank and start engine, transfer load to Generator if Utility returns above 75% nominal for 15 seconds.

What does Generac fault code 000141 mean?

Accidental start-up. Disconnect spark plug wires when working on unit.. Remedy: Disconnect spark plug wires before working on unit..