Generac XG04045 Generator Set

The Generac XG04045 is a 40 kW (50 kVA) Natural Gas (NG) or Liquid Propane (LP) Vapor standby generator set powered by a 4.5 L NA engine. It is available at 240 V, 208/120 V, 240/120 V and 480/277 V, single-phase, 60 Hz and rated 167 A. It holds about 11 L (2.9 gal) of oil and 11 L (2.9 gal) of coolant, with a maximum ambient rating of 50 °C. Starting uses 1 group-27 battery rated 600 CCA at 12 V. The set measures 2121×862×1147 mm (83.5×33.9×45.2 in), weighs about 689 kg (1519 lb) and produces 60 dBA at 7 m.

40 kW
Standby
4.5 L
Displacement
11.0 L
Oil capacity
4
Document types

How to read your Generac serial & model number →

Typical fuel consumption for 40–45 kW Bi-Fuel (NG/LP) generators →

Compare with other 40–45 kW Bi-Fuel (NG/LP) generators →

Service parts for the XG04045

Grouped by system, with how many of each the parts manual calls for.

Air intake

1 required

Oil system

1 required

Prices captured from merchant listings; some links are affiliate links. Confirm against your serial number before ordering.

Specifications

FuelNatural Gas (NG) or Liquid Propane (LP) Vapor
Frequency60.0 Hz
Standby power40 kW
Standby kVA50
Prime power40 kW
EmissionsEPA & SCAQMD
ControllerPower Zone 410
Oil capacity11.0 L
Alternator4-lead (1-phase) or 12-lead (3-phase) stator
Voltage options240 V, 208/120 V, 240/120 V, 480/277 V
Phase1 or 3
Rated current167 A
Power factor1.0 (1-phase), 0.8 (3-phase)
Circuit breaker200 A
Battery group27 (recommended), 31 (maximum)
Battery cranking600 CCA minimum (Group 27), 750 CCA minimum (Group 31 max) CCA
Battery voltage12 V V
Battery quantity1
Coolant capacity11 L
Max ambient50 °C
Dimensions (L×W×H)2121×862×1147 mm
Dry weight689 kg
Sound level64.0 dBA @ 7 m

Engine

4.5 L NA
Oil capacity11.0 L
Coolant capacity11.0 L
Displacement4.5 L
AspirationNaturally aspirated
Rated speed1800 rpm

Maintenance & consumables

for the 4.5 L NA
ItemSpecCapacityPart #Interval
Air filter140-1347150 hr Amazon eBay $100.60
Fuel filter—
Oil filterFull flow spin-on cartridge—150 hr
BatteryGroup 27 recommended (600 CCA min); Group 31 maximum (750 CCA min); 12 V—
Belt—1000 hr
CoolantGenerac brand 50/50 ethylene glycol type coolant11.0 L—1000 hr
Oil4.5 L Gaseous Engine Regular Maintenance Kit4.5 LG0079910 Amazon Amazon eBay eBay
Spark plugGap 0.012-0.017 in (0.31-0.45 mm); torque 28 ft-lb (38 Nm)—300 hr

Service intervals

13
ItemActionHoursMonthsNotes
Accessory drive beltInspect1000 hr24 moSchedule C: inspect for wear or damage
Accessory drive beltReplace1000 hrSchedule C
Air filter elementReplace1000 hr24 moSchedule C
Coolant level and hosesInspect1000 hr24 moSchedule C
Coolant systemDrain1000 hr24 moSchedule C: drain/flush
Critical fastenersAdjust1000 hrSchedule C: tighten
Enclosure slots and openingsInspect1000 hr24 moSchedule C
Fuel hosesInspect1000 hr24 moSchedule C
Lubricating oil and oil filterReplace1000 hr24 moFirst service — Schedule C
Lubricating oil level and drain hoseInspect1000 hr24 moSchedule C
Radiator for cloggingInspect1000 hr24 moSchedule C
Spark plugsReplace1000 hr24 moSchedule C
BatteryReplace36 moReplace battery every three years; every two years in extreme conditions

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

25
TypeItemValueUnitCondition
GapSpark plug gap0.012-0.017in (0.31-0.45 mm)
PressureLP fuel pressure to regulator7-14in H2O (1.74-3.48 kPa)
PressureLP vapor fuel supply pressure to fuel shutoff valve7-14in H2O (1.74-3.48 kPa)
PressureMaximum fuel system pressure drop (static/cranking/no-load/full-load)1-2in H2O (0.25-0.50 kPa)
PressureNG fuel pressure to regulator3.5-14in H2O (0.87-3.48 kPa)
PressureNG fuel supply pressure to fuel shutoff valve3.5-14in H2O (0.87-3.48 kPa)
Torque1-phase (1 position) load lug (C, D)375in-lbs (42.37 Nm)
Torque1-phase (1 position) lug375in-lbs (42.37 Nm)
Torque3-phase (1 position) distribution block lug375in-lb (42.37 Nm)
Torque3-phase (2 position) distribution block lug275in-lb (31.07 Nm)
Torque3-phase distribution block S1, S2, S3 lug120in-lb (13.6 Nm)
Torque3-phase distribution block, 1-position lug (A)375in-lb (42.37 Nm)
Torque3-phase distribution block, 2-position lug (B)275in-lb (31.07 Nm)
TorqueFrame breaker lug torque (Generac 225 AF 2/3 Pole)375in-lb (42.4 Nm)
TorqueGenerac 225 AF 2-Pole / 3-Pole frame breaker lug375in-lb (42.4 Nm)
TorqueNeutral bonding wire removal nut200in-lb (22.6 Nm)when neutral bonding wire removed
TorqueNeutral/ground bonding nut200in-lb (22.6 Nm)if neutral bonding wire removed
TorqueS1, S2, S3 lug torque (3-phase distribution block)120in-lb (13.6 Nm)
TorqueSpark plug28ft-lb (38 Nm)
TorqueVoltage Configuration Cartridge (VCC) mounting screws55in-lb (6.2 Nm)
Voltage1-phase circuit breaker terminal to neutral120V
Voltage1-phase circuit breaker terminal to terminal240V
Voltage3-Phase Delta config circuit breaker terminal to terminal (240/120 V VCC)240VE1-E2, E1-E3, E2-E3
Voltage3-Phase Y config circuit breaker terminal to terminal (208/120 V VCC)208VE1-E2, E1-E3, E2-E3
Voltage3-Phase Y config circuit breaker terminal to terminal (480/277 V VCC)480VE1-E2, E1-E3, E2-E3

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Coolant50/50 Ethylene Glycolbelow 50°C11.0 LCoolant system capacity 2.9 US gal (11 L)
Coolant50/50 ethylene glycol11.0 LUse only Generac brand 50/50 ethylene glycol type coolant. Do not use propylene glycol. Mix ratio 40-60% antifreeze depending on ambient.
Engine oil5W-20SAE11.0 LFactory filled with 5W-20 conventional; after 25 hour break-in use Generac proprietary 5W-20 Synthetic. Once synthetic is used, use for life. Do not use special additives.
FuelLiquid Propane (LP) Vapor or Natural Gas (NG)LP energy density >= 91,420 BTU/US gal (25.5 MJ/L); NG >= 1,036 BTU/ft3 (37.3 MJ/m3)LP minimum tank size 250 US gal (946 L) recommended.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

23
CodeNameMeaningSeverityAction
BATTERY PROBLEMBattery ProblemYellow LED illuminated in any state.WarningContact an IASD for assistance.
CHARGER MISSING ACCharger Missing ACAC input to battery charger circuit missing for greater than 5 minutes during charging cycle.WarningInspect connections at transfer switch, fuses in transfer switch. Contact an IASD for assistance.
CHARGER WARNINGCharger WarningYellow LED illuminated in any state.WarningContact an IASD for assistance.
Configuration MismatchConfiguration Mismatch (3-Phase only)Unit either shuts down or does not start.ShutdownCorrect voltage configuration selection in the control panel to match installed VCC. Contact an IASD for assistance.
FUSE PROBLEMFuse ProblemUnit will not start in AUTO with utility loss.ShutdownInspect 7.5 amp fuse. Replace with an ATO 7.5 amp fuse if bad; if fuse is good, contact an IASD.
GENERATOR EMERGENCY SHUTDOWN SWITCHGenerator Emergency Shutdown SwitchUnit either shuts down or does not start when one or both switches are OFF (O).ShutdownClear alarm and verify both generator emergency shutdown switches are ON (I).
HIGH TEMPERATUREHigh TemperatureUnit shuts down during operation.ShutdownInspect ventilation around generator, intake, exhaust, and rear of generator. If no obstruction, contact an IASD.
INSPECT BATTERYInspect BatteryYellow LED illuminated in any state.WarningInspect battery. Press ENTER to clear.
LOW BATTERYLow BatteryYellow LED illuminated in any state.WarningClear alarm. Check battery option in control menu; if GOOD contact an IASD, if CHECK BATTERY replace battery.
LOW OIL PRESSURELow Oil PressureUnit will not start in AUTO with utility loss.ShutdownCheck oil level / add oil per owner's manual. If oil level is correct, contact an IASD.
LOW VOLTS REMOVE LOADLow Volts Remove LoadUnit will not start in AUTO with utility loss.ShutdownClear alarm and remove household loads. Set to AUTO and restart.
NOT ACTIVATEDNot ActivatedUnit will not start in AUTO with utility loss.InfoSee Checking Manual Transfer Switch Operation.
OVERCRANKOvercrankUnit will not start in AUTO with utility loss.ShutdownVerify fuel line shutoff valve is ON. Clear alarm. Attempt start in MANUAL. If it does not start or runs rough, contact an IASD.
OVERLOAD REMOVE LOADOverload Remove LoadUnit shuts down during operation.ShutdownCorrect voltage configuration selection in the control panel. Clear alarm and remove household loads. Put back in AUTO and restart.
OVERSPEEDOverspeedUnit will not start in AUTO with utility loss.ShutdownContact an IASD for assistance.
OVERVOLTAGEOvervoltageUnit will not start in AUTO with utility loss.ShutdownContact an IASD for assistance.
RPM SENSE LOSSRPM Sense Loss (shutdown)Unit was running and shuts down, attempts to restart.ShutdownClear alarm and remove household loads. Set to AUTO and restart. If it does not start, contact an IASD.
SERVICE AService AYellow LED illuminated in any state.WarningPerform SERVICE A maintenance. Press ENTER to clear.
SERVICE BService BYellow LED illuminated in any state.WarningPerform SERVICE B maintenance. Press ENTER to clear.
STEPPER OVERCURRENTStepper OvercurrentUnit will not start in AUTO with utility loss.ShutdownContact an IASD for assistance.
UNDERSPEEDUnderspeedUnit will not start in AUTO with utility loss.ShutdownContact an IASD for assistance.
UNDERVOLTAGEUndervoltageUnit will not start in AUTO with utility loss.ShutdownCorrect voltage configuration selection in the control panel. Contact an IASD for assistance.
WIRING ERRORWiring ErrorUnit will not start in AUTO with utility loss.ShutdownVerify wiring is installed and landed correctly.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Fuel Pressure Test at Startup diagnostic

⚠ Severe valve deformation can occur if gauge probe is left in test port for hours or days.

Tools: Pressure gauge or water manometer, Gauge adapter probe (Part Number 0K2341)

  1. Connect a load bank (or load bank + system load) to bring unit to full rated kW load.
  2. Measure fuel supply pressure at test port at fuel solenoid shutoff valve under static, cranking, no-load, and full-load conditions.
  3. Verify pressure stays within 3.5-14 in H2O (NG) or 7-14 in H2O (LP) and drop does not exceed 1-2 in H2O.
  4. Tighten protective cap on test port to prevent tampering.
Connecting Load Wiring - 1-Phase Models installation

⚠ Turn utility and emergency power OFF before connecting.

  1. Connect load wiring to E1 & E2.
  2. Connect generator neutral to neutral terminal bar.
  3. Connect equipment ground to equipment ground lug.
  4. Tighten 1-phase (1 position) lugs (C) and (D) to 375 in-lb (42.37 Nm).
Connecting Load Wiring - 3-Phase Without a Circuit Breaker installation
  1. Route copper load wires toward end panel; keep separated from factory wiring.
  2. Connect generator neutral to neutral terminal bar (A).
  3. Connect equipment ground to equipment ground lug (B).
  4. Tighten 3-phase 2-position lug (B) to 275 in-lb (31.07 Nm).
  5. Tighten 3-phase 1-position lug (A) to 375 in-lb (42.37 Nm).
Installing the Battery installation

⚠ Explosion. Batteries emit explosive gases. Always connect positive battery cable first to avoid spark. Failure to do so could result in death or serious injury. (W000133)

  1. Loosen nylon strap on battery tray.
  2. Install battery onto tray.
  3. Secure nylon strap over top of battery and tighten.
  4. Install positive battery cable (red) to positive terminal.
  5. Install negative battery cable (black) to negative terminal.
Installing the Voltage Configuration Cartridge (VCC) installation

⚠ Voltage selection installer code required.

  1. Assemble the new VCC (B) over the terminal block (C).
  2. VCC is designed to install one way with the tabs aligned.
  3. Install the five screws to secure the VCC tabs to the terminal block.
  4. Tighten screws to 55 in-lb (6.2 Nm).
  5. Navigate to the 3-phase voltage selection in the controller.
  6. Select the 3-phase voltage matching the installed VCC.
  7. Verify the voltage in the menu.
Cleaning/Gaping/Replacing Spark Plugs maintenance

⚠ Electric shock. Do not disconnect spark plug wires with engine running. Doing so could result in death or serious injury. (W000140)

Tools: spark plug socket, wire feeler gauge, wire brush

  1. Remove negative battery cable.
  2. Remove spark plug cables from terminals.
  3. Clean area around spark plugs.
  4. Remove spark plugs with spark plug socket.
  5. Inspect threads; clean with thread chaser if needed.
  6. Clean spark plugs with wire brush and solvent; do not blast.
  7. Inspect gap with wire feeler gauge; gap 0.012-0.017 in (0.31-0.45 mm).
  8. Adjust gap by bending ground electrode.
  9. Finger tighten spark plugs; tighten to 28 ft-lb (38 Nm) with socket.
  10. Install spark plug cables; verify captured in clips.
Draining and Flushing Coolant System maintenance

⚠ Risk of burns. Allow engine to cool before draining oil or coolant. Failure to do so could result in death or serious injury. (W000139)

Tools: wrenches, container, funnel

  1. Disconnect and empty coolant overflow reservoir.
  2. Rotate and remove plastic cover at top of enclosure.
  3. Slowly unscrew radiator cap.
  4. Locate drain screw at bottom left of radiator; open drain.
  5. Remove coolant drain hose from clamp; remove plug; drain coolant.
  6. Install drain plug and hose; close radiator drain screw.
  7. Fill radiator with de-ionized or distilled water and flushing product; use 2.9 US gal (11 L).
  8. Install radiator cap.
  9. Press MANUAL to start engine; run until thermostat opens.
  10. Inspect hoses for leaks; press OFF; allow engine to cool.
  11. Repeat steps 4-19 to drain.
  12. Add recommended coolant; top off radiator and overflow bottle.
Inspecting Accessory/Drive Belt maintenance
  1. Inspect belt for cracks, fraying, excessive wear, or damage.
  2. Verify belt is free of grease and oil.
  3. Replace belt if contaminated, damaged, frayed, or worn.
  4. Inspect belt and rotating components.
Preparing For Storage maintenance

Tools: wrenches, container

  1. Open viewing window.
  2. Press MANUAL to start engine; blue LED illuminates.
  3. Allow engine to reach normal operating temperature.
  4. Press OFF; red LED illuminates.
  5. Set generator MLCB to OFF (OPEN), if equipped.
  6. Remove 7.5 amp fuse.
  7. Turn off utility power to transfer switch.
  8. Place DO NOT OPERATE tag.
  9. Wait five minutes for engine to cool.
  10. Remove front access panel.
  11. Remove oil drain hose from holding clamp; drain oil.
  12. Install oil drain plug and hose.
  13. Remove oil filter; coat new filter gasket with oil.
  14. Install oil filter; tighten 3/4 to 1 full turn.
  15. Fill engine with recommended oil; install oil fill cap.
Removing Battery maintenance

⚠ Electrical shock. Disconnect battery ground terminal before working on battery or battery wires. Failure to do so could result in death or serious injury. (W000164)

  1. Remove negative battery cable from negative terminal.
  2. Remove positive battery cable from positive terminal.
  3. Install rubber protective cover over positive terminal.
  4. Release buckle on nylon strap securing battery.
  5. Grasp battery strap and lift battery from tray.
  6. Remove rubber protective cover from positive terminal.
Replacing Air Filter Element maintenance

Tools: wrenches

  1. Remove nut and bolt from air filter clamp; loosen elbow clamp.
  2. Remove air filter element and discard.
  3. Clean elbow of dust, dirt, or debris.
  4. Place new air filter element into elbow clamp.
  5. Install elbow clamp and tighten; install nut and bolt; tighten until snug.
Replacing Lubricating Oil and Oil Filter maintenance

⚠ Risk of burns. Allow engine to cool before draining oil or coolant. Failure to do so could result in death or serious injury. (W000139)

Tools: wrenches, container, shop towel

  1. Follow Removing From Service; wait at least 10 minutes.
  2. Remove oil drain hose from holding clamp.
  3. Use two wrenches to remove oil drain plug; drain oil.
  4. Install oil drain plug and hose into holding clamp.
  5. Turn oil filter counterclockwise to remove; wipe adapter.
  6. Apply clean engine oil to gasket of new oil filter.
  7. Install oil filter by hand until gasket contacts; tighten 3/4 to 1 full turn.
  8. Fill engine with 11.6 qt (11 L) recommended oil for 4.5 L NA.
  9. Install oil fill cap.
  10. Connect negative battery cable; install 7.5 amp fuse.
  11. Press MANUAL to start; run one minute; inspect for leaks.
  12. Press OFF; wait 10 minutes; check oil level and add as needed.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
208/1203 (Y)3-Phase Alternator Y Configuration, 12 leadE1, E2, E3, S1-S12208/120 V VCC installed
208/120 V3 (Y)12-lead stator, Y configuration with 208/120 V VCC (factory default)S1-S12, E1, E2, E3Rated voltage E1-E2, E1-E3, E2-E3 is 208V; each terminal to neutral (00) is 120V.
240 VAC 1-phase1Four-lead stator factory-connected to main circuit breakerE1, E3, 00 (neutral), 11/22/33/44Rated voltage between each breaker terminal and neutral (00) is 120V; between breaker terminals is 240V.
240/1201Four-Lead 1-Phase StatorE1, E3, neutral point 00Rated voltage between each circuit breaker terminal is 240V; between each terminal and neutral point 00 is 120V
240/1203 (Delta)3-Phase Alternator Delta Configuration, 12 leadE1, E2, E3, NB, S1-S12E2 to NB (high leg) is 208V; E1-00 and E3-NB approx 120V
240/120 V3 (Delta, high leg)12-lead stator, Delta configuration with 240/120 V VCCS1-S12, E1, E2, E3, NBRated voltage E1-E2, E1-E3, E2-E3 is 240V; E2-NB (high leg) is 208V; E1-00 and E3-NB approx. 120V.
480/2773 (Y)3-Phase Alternator Y Configuration, 12 leadE1, E2, E3, S1-S12480/277 V VCC
480/277 V3 (Y)12-lead stator, Y configuration with 480/277 V VCCS1-S12, E1, E2, E3Rated voltage E1-E2, E1-E3, E2-E3 is 480V; each terminal to neutral (00) is 277V.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What size generator is the Generac XG04045?

The Generac XG04045 is rated 40 kW standby (50.0 kVA).

What engine is in the Generac XG04045?

The Generac XG04045 is powered by the 4.5 L NA engine.

What fuel does the Generac XG04045 use?

The Generac XG04045 runs on Natural Gas (NG) or Liquid Propane (LP) Vapor.

What's the oil capacity on a Generac XG04045?

The None 4.5 L NA engine in the Generac XG04045 has an oil capacity of 11.0 liters.

How much coolant does the Generac XG04045 hold?

The Generac XG04045 cooling system holds 11 liters (2.9 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.

How loud is the Generac XG04045?

The Generac XG04045 is rated at 64.0 dBA at 7 m, per the manufacturer specification sheet.

How much does the Generac XG04045 weigh?

The Generac XG04045 has a dry weight of 689 kg (1518 lb).

What voltage does the Generac XG04045 produce?

The Generac XG04045 is offered in 240 V, 208/120 V, 240/120 V, 480/277 V, 1 or 3-phase.

How many cold cranking amps does the Generac XG04045 require?

The Generac XG04045 uses 1 battery, 12 V V each, 600 CCA minimum (Group 27), 750 CCA minimum (Group 31 max) CCA, group 27 (recommended), 31 (maximum), per the manufacturer specification sheet.

What alternator comes on the Generac XG04045?

The Generac XG04045 uses a 4-lead (1-phase) or 12-lead (3-phase) stator alternator.

What air filter does the Generac XG04045 use?

The Generac XG04045 uses air filter part number 140-1347.

Troubleshooting

6

Symptoms & remedies

SymptomRemedy
Engine stops cranking and fault lamp lights, after cranking approximately 75 seconds.See engine service manual for troubleshooting fuel system. After correcting problem, reset engine monitor relay by placing Run-Stop/Reset-Remote switch to Stop/Reset, then back to the required running position.
Fault lamp lights immediately after engine starts.Check for: Overspeed condition as engine starts.
Fault lamp lights and engine shuts down after running for a period.A. Oil level. Engine will shut down if sensor is closed. b. Check engine manual for troubleshooting oil system. c. High engine temperature. Check coolant level; check water flow (city water cooled systems); check radiator for free air flow, and fan belts for tightness. See engine manual for troubleshooting cooling system. d. Check for faulty oil pressure sensor or faulty high engine temperature sensor.
Engine runs, shuts down and cranks for 75-seconds. Cranking cycle stops; fault lamp lights.Check fuel supply.
Fault lamp lights, no fault exists.To check a no-fault condition, disconnect leads from T B I l terminals 29, 30 and 31. If fault lamp lights with leads disconnected, replace engine monitor board. Reconnect leads.
Overcrank fault lamp lights and engine stops cranking after approximately 75-seconds.See engine service manual for troubleshooting fuel system. After correcting fault, reset engine monitor relay by placing Run-Stop/Reset-Remote switch to Stop/Reset position, depressing Reset button, then to the required running position.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing. Full Generac XG04045 troubleshooting guide (16 entries) →

Parts

43
Part #DescriptionQtySystem
G0079910Regular maintenance kit includes oil filter, oil funnel, air filter, and spark plugs.1Air filter Amazon Amazon eBay eBay
G0099160Containment pan to capture all engine oil and coolant. Kit includes a sensor to detect the presence of fluid in the pan then displays a warning on the controller screen. The G0089370 Power Zone 410 I/O Extender Kit is required for the sensor installation.1Sensor Amazon eBay
G0056510Base plugs to fit in the lifting holes of the baseframe to keep debris out.1Service part / kit Amazon Amazon eBay $20.68 eBay $20.68
G007000050 A Smart Management Module (SMM) helps optimize the performance of the standby generator by managing large electrical loads upon startup and shed them to aid in recovery when overloaded.1Service part / kit Amazon Amazon eBay $65.00 eBay $151.10
G007000150 A Load Manager helps optimize the performance of the standby generator by managing large electrical loads upon startup and shed them to aid in recovery when overloaded.1Service part / kit Amazon Amazon eBay $69.99 eBay $125.00
G0070050The Tank Utility monitor integrates with Mobile Link to provide tank level readings, offering customers peace of mind.1Service part / kit Amazon Amazon eBay eBay
G0070060100 A Smart Management Module (SMM) helps optimize the performance of the standby generator by managing large electrical loads upon startup and shed them to aid in recovery when overloaded.1Service part / kit Amazon Amazon eBay $109.99 eBay $250.00
G0070061100 A Load Manager helps optimize the performance of the standby generator by managing large electrical loads upon startup and shed them to aid in recovery when overloaded.1Service part / kit Amazon Amazon eBay $300.00 eBay
G0070090The Propane Tank Fuel Level Monitor connects to 4G LTE cellular service to measure and report the amount of LP fuel remaining in the tank. The app alerts the user of both remaining LP fuel and usage reports.1Service part / kit Amazon Amazon eBay $157.99 eBay $157.99
G00741103-Phase Voltage Sensing Kit for 208/120 & 240/120 V RTS Transfer Switch1Service part / kit Amazon Amazon eBay eBay
G00741203-Phase Voltage Sensing Kit for 480/277 V RTS Transfer Switch1Service part / kit Amazon Amazon eBay eBay
G0079900Recommend for operating environments where the temperature drops below -18°C (0° F); externally powered by 120 VAC, 60 Hz.1Service part / kit Amazon Amazon eBay
G0079920Battery Heater Kit1Service part / kit Amazon Amazon eBay eBay
G0079930Enclosure Mounted Emergency Stop Kit1Service part / kit Amazon Amazon eBay eBay
G0089350Emergency Stop switch that can be mounted separate from the generator such as near an electrical panel.1Service part / kit Amazon
G0089360The Gateway provides an Ethernet connection port for the generator for a Building Management System (BMS). The Gateway is NOT intended for or able to be used with Mobile Link or Fleet.1Service part / kit Amazon eBay
G0089370The kit expands I/O for the Power Zone 410 controller to provide connections for additional accessories. It connects to the controller with a 3-wire RS-485 interface.1Service part / kit Amazon eBay
G0098511Remote annunciator panel with relays. The panel mounts in the structure that is connected to the backup generator.1Service part / kit Amazon eBay $149.00
G0098521Remote relay panel without LEDs or keypad. The panel mounts in the structure that is connected to the backup generator.1Service part / kit Amazon eBay $157.49
G0098531Remote annunciator panel without relays. The panel mounts in the structure that is connected to the backup generator.1Service part / kit Amazon eBay $199.99
G0099010Voltage Configuration Cartridge (VCC) for 208/120 V 3-phase output. It is INSTALLED in every 3-phase XG03245, XG04045, and XG04845 model. Offered as an accessory if a replacement is needed for any reason.1Service part / kit Amazon eBay
G0099020Voltage Configuration Cartridge (VCC) for 240/120 V 3-phase output. It is NOT included with any XG03245, XG04045, or XG04845 model.1Service part / kit Amazon eBay
G0099030Voltage Configuration Cartridge (VCC) for 480/277 V 3-phase output. It is NOT included with any XG03245, XG04045, or XG04845 model.1Service part / kit Amazon eBay
G00990403-pole, 60 A CB and mounting hardware (typical for 32 kW, 480/277 V 3-phase generator).1Service part / kit Amazon eBay
G00990503–pole, 80 A CB and mounting hardware (typical for 48 kW, 480/277 V 3-phase generator).1Service part / kit Amazon eBay
G00990603-pole, 100 A CB and mounting hardware (typical for 32 kW, 240/120 V 3-phase generator).1Service part / kit Amazon eBay
G00990703–pole, 125 A CB and mounting hardware (typical for 32 kW, 208/120 V; and 40 kW, 240/120 V 3-phase generators).1Service part / kit Amazon eBay
G00990803–pole, 150 A CB and mounting hardware (typical for 40 kW, 208/120 V and 48 kW, 240/120 V 3-phase generators).1Service part / kit Amazon eBay
G00990903–pole, 175 A CB and mounting hardware (typical for 48 kW, 208/120 V 3-phase generator).1Service part / kit Amazon eBay
G00991003-color LED providing at-a-glance indication of generator ready-to-run status. The display mounts to the front of the generator and plugs into the wire harness.1Service part / kit Amazon eBay
G0099110Further reduces sound level of generator; assembles to top of generator enclosure exhaust discharge area.1Service part / kit Amazon
G0099120Includes controller module with Key Switch, Alarm Horn, and Emergency Stop Switch that connects to the Power Zone 410 controller. The module mounts below the controller and is visible through the control panel cover. The G0098511, G0098521, or G0098531 panel and a capable transfer switch are required to be considered for NFPA 110 system control and remote annunciation.1Service part / kit Amazon eBay
G0099130Increases wind speed rating of generator to 186 mph (300 km/h). The kit assembles to the exterior of the generator enclosure and frame.1Service part / kit Amazon eBay
G0099140Support structure for mounting a generator on a rooftop or elevated frame; does NOT include the frame itself.1Service part / kit Amazon
G0099150Aluminum panel and hardware to close off the bottom of the generator. It allows correct airflow is maintained through the generator for cooling while keeping objects out? It is required anytime the generator is elevated. Fits XG03245, XG04045, and XG04845.1Service part / kit Amazon eBay
G0099170Anchor bolts for securing the generator in a defined, seismically active area with recommended mounting surface recommendations; does not supersede local building codes or requirements.1Service part / kit Amazon
G0099180It is important to touch-up the paint to protect against corrosion if the generator enclosure is scratched or damaged. The paint kit includes the necessary paint to correctly maintain or touch-up a generator enclosure.1Service part / kit Amazon Amazon eBay eBay
G00991903-pole, 70 A CB and mounting hardware (typical for 40 kW, 480/270 V 3-phase generator).1Service part / kit Amazon eBay
G00992003-pole, 200 A CB and mounting hardware (typical for 40kW, 208/120 V 3-phase generator)1Service part / kit Amazon eBay
G0099230Recommended for operating environments where the temperature drops below 0 °F (-18 °C). The heater is externally powered by 120 VAC, 60 Hz.1Service part / kit Amazon eBay
G0099250Remote Emergency Stop Kit, Surface Mount1Service part / kit Amazon eBay
G0099260Remote Emergency Stop Kit, Flush Mount1Service part / kit Amazon eBay
G0099270Remote Emergency Stop kit, Break Glass1Service part / kit Amazon eBay

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Fuel consumption

RatingLoadL/hgal/h
Prime25%10.02.6
Prime50%14.53.8
Prime75%17.74.7
Prime100%21.75.7
Standby25%8.32.2
Standby50%12.93.4
Standby75%15.84.2
Standby100%13.563.58

Available documents

Spec sheet (Generac)Spec sheet — 32-40kw-protector-xg-standby-generator-specsheet (Generac)Spec sheet — a0005286945-(1) (Generac)Owner's manual — generac-xg04045anac-owners-manual (Generac)Parts manual — 0Parts manual — generac-xg04045anac-specification-sheet (Generac)Parts manual — xg03245-xg04045 hsb specsheet (Generac)Service manual — 956-0302 Onan DFE Operator's and Parts Manual (4-1977) (Generac)Service manual — generac-xg04045anac-installation-sheet (Generac)

This page was generated from the 9 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.

Full service, cheapest listings

Priced items from this model's own parts manual.

Air filter 140-1347$100.60
1 priced item$100.60
Other sets with this engine