| BATTERY PROBLEM | Battery Problem | Yellow LED illuminated in any state. | Warning | Contact an IASD for assistance. |
| CHARGER MISSING AC | Charger Missing AC | AC input to battery charger circuit missing for greater than 5 minutes during charging cycle. | Warning | Inspect connections at transfer switch, fuses in transfer switch. Contact an IASD for assistance. |
| CHARGER WARNING | Charger Warning | Yellow LED illuminated in any state. | Warning | Contact an IASD for assistance. |
| Configuration Mismatch | Configuration Mismatch (3-Phase only) | Unit either shuts down or does not start. | Shutdown | Correct voltage configuration selection in the control panel to match installed VCC. Contact an IASD for assistance. |
| FUSE PROBLEM | Fuse Problem | Unit will not start in AUTO with utility loss. | Shutdown | Inspect 7.5 amp fuse. Replace with an ATO 7.5 amp fuse if bad; if fuse is good, contact an IASD. |
| GENERATOR EMERGENCY SHUTDOWN SWITCH | Generator Emergency Shutdown Switch | Unit either shuts down or does not start when one or both switches are OFF (O). | Shutdown | Clear alarm and verify both generator emergency shutdown switches are ON (I). |
| HIGH TEMPERATURE | High Temperature | Unit shuts down during operation. | Shutdown | Inspect ventilation around generator, intake, exhaust, and rear of generator. If no obstruction, contact an IASD. |
| INSPECT BATTERY | Inspect Battery | Yellow LED illuminated in any state. | Warning | Inspect battery. Press ENTER to clear. |
| LOW BATTERY | Low Battery | Yellow LED illuminated in any state. | Warning | Clear alarm. Check battery option in control menu; if GOOD contact an IASD, if CHECK BATTERY replace battery. |
| LOW OIL PRESSURE | Low Oil Pressure | Unit will not start in AUTO with utility loss. | Shutdown | Check oil level / add oil per owner's manual. If oil level is correct, contact an IASD. |
| LOW VOLTS REMOVE LOAD | Low Volts Remove Load | Unit will not start in AUTO with utility loss. | Shutdown | Clear alarm and remove household loads. Set to AUTO and restart. |
| NOT ACTIVATED | Not Activated | Unit will not start in AUTO with utility loss. | Info | See Checking Manual Transfer Switch Operation. |
| OVERCRANK | Overcrank | Unit will not start in AUTO with utility loss. | Shutdown | Verify fuel line shutoff valve is ON. Clear alarm. Attempt start in MANUAL. If it does not start or runs rough, contact an IASD. |
| OVERLOAD REMOVE LOAD | Overload Remove Load | Unit shuts down during operation. | Shutdown | Correct voltage configuration selection in the control panel. Clear alarm and remove household loads. Put back in AUTO and restart. |
| OVERSPEED | Overspeed | Unit will not start in AUTO with utility loss. | Shutdown | Contact an IASD for assistance. |
| OVERVOLTAGE | Overvoltage | Unit will not start in AUTO with utility loss. | Shutdown | Contact an IASD for assistance. |
| RPM SENSE LOSS | RPM Sense Loss (shutdown) | Unit was running and shuts down, attempts to restart. | Shutdown | Clear alarm and remove household loads. Set to AUTO and restart. If it does not start, contact an IASD. |
| SERVICE A | Service A | Yellow LED illuminated in any state. | Warning | Perform SERVICE A maintenance. Press ENTER to clear. |
| SERVICE B | Service B | Yellow LED illuminated in any state. | Warning | Perform SERVICE B maintenance. Press ENTER to clear. |
| STEPPER OVERCURRENT | Stepper Overcurrent | Unit will not start in AUTO with utility loss. | Shutdown | Contact an IASD for assistance. |
| UNDERSPEED | Underspeed | Unit will not start in AUTO with utility loss. | Shutdown | Contact an IASD for assistance. |
| UNDERVOLTAGE | Undervoltage | Unit will not start in AUTO with utility loss. | Shutdown | Correct voltage configuration selection in the control panel. Contact an IASD for assistance. |
| WIRING ERROR | Wiring Error | Unit will not start in AUTO with utility loss. | Shutdown | Verify wiring is installed and landed correctly. |