Service parts for the SR4B
Grouped by system, with how many of each the parts manual calls for.
Air intake
1 requiredFuel system
1 requiredOil system
1 requiredPrices captured from merchant listings; some links are affiliate links. Confirm against your serial number before ordering.
Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 650 kW |
| Standby kVA | 813 |
| Prime power | 910 kW |
| Emissions | EPA Tier 2 |
| Controller | EMCP 3.1, EMCP 3.2, EMCP 3.3 |
| Oil capacity | 16.103 L |
| Alternator | SR4B (Class Class H insulation) |
| Voltage options | 480 V |
| Phase | 3-phase |
| Rated current | 2405.6 A |
| Power factor | 0.8 |
| Circuit breaker | 3000 A |
| Battery group | 24 |
| Battery voltage | DC V |
| Battery quantity | 1 |
| Coolant capacity | 390.8 L |
| Max ambient | 40 °C |
| Dimensions (L×W×H) | 6452×2324×2711 mm |
| Dry weight | 15926 kg |
| Sound level | 72.0 dBA @ 15 m |
| Fuel tank | 4730.0 L |
| Tank runtime | 23.5 hr |
Engine
| Oil capacity | 68.0 L |
|---|---|
| Coolant capacity | 160.0 L |
| Displacement | 27.03 L |
| Aspiration | TA |
| Rated speed | 1800 rpm |
Maintenance & consumables
for the Caterpillar C27 TA| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | Air Shutoff | 101564109 | Amazon eBay | ||
| Fuel filter | 3890433 | 1250 hr | Amazon eBay $34.97 FridayParts $71.99 | ||
| Oil filter | 3890434 | 1250 hr | Amazon $148.00 eBay $82.42 PartsGeek $30.97 | ||
| Battery | — | 3650 hr | |||
| Belt | — | 1250 hr | |||
| Coolant | 160.0 L | — | |||
| Oil | 68.0 L | — | |||
| Spark plug | — | 1250 hr |
Service intervals
6| Item | Action | Hours | Months | Notes |
|---|---|---|---|---|
| Insulation | Test | 7500 hr | 12 mo | Every 7500 Service Hours or 1 Year (Standard and Standby schedule) |
| Rotating Rectifier | Check | 7500 hr | 12 mo | Every 7500 Service Hours or 1 Year (Standard and Standby schedule) |
| Bearing (Ball) | Lubricate | 2000 hr | 12 mo | Every Year (Standby schedule) |
| Bearing (Spherical Roller) | Lubricate | 1000 hr | 12 mo | Every Year (Standby schedule) |
| Generator Set Vibration | Inspect | 2000 hr | 12 mo | Every Year (Standby schedule) |
| Stator Lead | Check | 2000 hr | 6 mo | Every 6 Months (Standby schedule) |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Service specifications
37| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Clearance | Bearing bracket step minimum | less than 0.0762 | mm | |
| Other | High idle speed for droop governors | approximately 2% to 5% | above full load speed | governors equipped with droop |
| Other | Speed droop values commonly used | 3% and 0% | % | |
| Other | Voltage droop for 0.8 power factor load | approximately 5 | % | loads with a power factor of 0.8 |
| Pressure | Engine oil pressure at low idle | 186 to 344 | kPa | low idle speed |
| Pressure | Normal operating engine oil pressure | 275 to 600 | kPa | engine running at rated engine speed, SAE 10W30 oil, operating oil temperature 104 C (219.2 F), normal engine water temperature |
| Resistance | Exciter Armature (Rotor) (L2) resistance | less than 0.1 | ohm | room temperature |
| Resistance | Exciter Armature (Rotor) (L2) winding resistance | less than 0.1 | ohm | room temperature |
| Resistance | Exciter Field (Stator) (L1) resistance | 3.0 to 6.0 | ohms | room temperature |
| Resistance | Exciter Field (Stator) (L1) winding resistance | 3.0 to 6.0 | ohm | room temperature |
| Resistance | Main Armature (Stator) (L4) resistance | less than 0.1 | ohm | room temperature |
| Resistance | Main Field (Rotor) (L3) resistance | 0.75 to 2.0 | ohms | room temperature |
| Resistance | Main Field (Rotor) (L3) winding resistance | 0.75 to 2.0 | ohm | room temperature |
| Resistance | Main armature (Stator) (L4) winding resistance | less than 0.1 | ohm | room temperature |
| Resistance | Pilot Exciter Armature (L5) resistance | less than 0.1 | ohm | room temperature |
| Resistance | Pilot Exciter Armature (L5) winding resistance | less than 0.1 | ohm | room temperature |
| Resistance | Resistor (R5) resistance | 27000 | ohm | nominal ± 2700 ohms |
| Resistance | Varistor (CR7) resistance | 15000 | ohm | minimum |
| Resistance | Varistor (CR7) resistance | minimum 15000 | ohms | |
| Speed | Frequency vs RPM - four-pole generator | divide the RPM by 30 | Hz | |
| Speed | Frequency vs RPM - six pole generator | divide the RPM by 20 | Hz | |
| Speed | Low idle (50 Hz units) | approximately 80 | % of full load speed | 50 Hz units |
| Speed | Low idle (60 Hz units) | approximately 66 | % of full load speed | 60 Hz units |
| Temperature | Bearing installation heating | 149 | C | for press fit installation |
| Temperature | Bearing reinstall heating | 107 | C | heat for ten minutes |
| Temperature | Coupling installation heating | 315 | C | for press fit installation |
| Temperature | Engine water temperature operating range | 88 to 100 | C | 88 C (190.4 F) to 100 C (212.0 F) |
| Temperature | Generator drying temperature (oven method) | 65 | C | forced air oven for 4 hours |
| Temperature | Generator drying winding temperature rise rate | 10 | C per hour up to 85 C (185 F) | do not apply heat too rapidly |
| Temperature | Hub reinstall heating | 400 | C | heat for three hours |
| Temperature | Oven drying method temperature | 65 | C | forced air drying oven for four hours |
| Temperature | Winding temperature limit during drying | 85 | C | maximum to prevent insulation damage |
| Torque | Exciter armature bolt (3/8 inch) | 55.8 | N·m | with thread lock 9S-3263 |
| Torque | Exciter armature bolt (5/16 inch) | 35.4 | N·m | with thread lock 9S-3263 |
| Voltage | Generator set functional test minimum phase voltage | minimum 85 | VAC | generator set operated at half the rated speed with 12 VDC battery on F1+/F2- |
| Voltage | Insulation test voltage for units 600 volts or less | 500 | Volts | 600 volts or less |
| Voltage | Insulation test voltage for units more than 600 volts | 1000 | Volts | more than 600 volts |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Recommended fluids
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Coolant | Cat DEAC | Diesel; 3,000 Service Hours or Three Years; annual S·O·SSM Level 2 coolant sampling and analysis | |||
| Coolant | Cat ELC | Diesel; 12,000 Service Hours or Six Years; add Cat ELC Extender at 6,000 service hours or one half of service life; annual S·O·SSM Level 2 coolant sampling and analysis | |||
| Coolant | Cat NGEC | Natural Gas; 16,000 Service Hours or Three Years; use interval that occurs first | |||
| Engine oil | Cat NGEO | Natural Gas | |||
| Engine oil | SAE 10W30 | Referenced as the oil used when normal operating engine oil pressure is specified | |||
| Engine oil | Cat Arctic DEO SYN SAE 0W-30 | -40°C to 30°C | Engine Crankcase; Industrial Engines | ||
| Engine oil | Cat DEO SYN SAE 5W-40 | -30°C to 50°C | Engine Crankcase; Industrial Engines | ||
| Engine oil | Cat DEO SAE 10W-30 | -18°C to 40°C | Engine Crankcase; Industrial Engines | ||
| Engine oil | Cat DEO SAE 15W-40 | -9°C to 50°C | Engine Crankcase; Industrial Engines | ||
| Grease | Cat Generator Set Grease | Part Number 108-8611 | |||
| Grease | NLGI No. 1.5 Grade | Caterpillar 108-8611 Grease Cartridge for spherical roller bearings; contains Clay thickener; no molybdenum disulfide; viscosity 32 cSt at 40 C, 5 cSt at 100 C | |||
| Grease | NLGI No. 2 Grade | -29°C to 177°C | Caterpillar 2S-3230 Bearing Lubricant for ball bearings; contains Polyurea thickener; for extremely low temperatures use NLGI No. 1 Grade or NLGI No. 0 Grade |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Procedures
12VR3 Regulator Adjustment Procedure adjustment
⚠ The VR3 regulator is protected by a fuse(s) and a solid-state overcurrent protection. If a fuse becomes open, contact a Caterpillar dealer.
- Remove the access panel of the generator.
- Loosen the locknut on the voltage droop potentiometer (1).
- Remove the protective screw from the voltage level potentiometer (2) and from the voltage gain potentiometer (3).
- Turn the voltage droop potentiometer (1) counterclockwise to zero droop. Tighten the locknut.
- Turn the voltage gain potentiometer (3) counterclockwise to zero, then to about 1/4 of full range of clockwise travel.
- Perform required maintenance on the engine before you start the engine.
- Start the engine and allow the engine to warm up.
- Increase engine speed to full governed rated speed (high idle).
- Set the no-load voltage with the voltage level potentiometer (2) or the voltage adjust rheostat.
- Close the load circuit breaker and apply full load gradually. Adjust governor control to nameplate frequency or rated speed.
- If the voltmeter reading increases above no-load voltage, turn the voltage gain potentiometer counterclockwise. If it decreases, turn it clockwise.
- Remove the load. If necessary, adjust the voltage level potentiometer (2) to obtain desired voltage.
- Apply the load. Repeat Steps 10 through 12 until the voltage at no load equals the voltage at full load.
- Tighten the locknuts. Install the protective screws and the access panel of the generator.
Generator Set Functional Test diagnostic
⚠ Do not exceed half rated speed
⚠ Do not allow output to exceed nameplate rating
Tools: Digital Multimeter, 12 VDC Battery
- Disconnect wires F1 and F2 from voltage regulator
- Disconnect generator load
- Connect 12 VDC battery to wires F1+ and F2-
- Operate generator at half rated speed
- Measure AC voltage across terminals T1-T2, T1-T3, T2-T3
- Record voltages at half speed, then at ±10% speed variations
- Verify minimum 85 VAC output at half speed
- Verify speed changes produce proportional voltage changes
Rotating Rectifier - Test diagnostic
Tools: 6V-7070 Digital Multimeter, 146-4080 Digital Multimeter (RS-232)
- Touch the red ohmmeter lead to the rectifier terminal marked '+'.
- Touch the black ohmmeter lead to terminals AC1, AC2, and AC3; the meter should indicate an open circuit or high resistance.
- Touch the black ohmmeter lead to the rectifier terminal marked '+'.
- Touch the red ohmmeter lead to terminals AC1, AC2, and AC3; the meter should indicate a good diode or low resistance.
- Touch the black ohmmeter lead to the rectifier terminal marked '-'.
- Touch the red ohmmeter lead to terminals AC1, AC2, and AC3; the meter should indicate an open circuit or high resistance.
- Touch the red ohmmeter lead to the rectifier terminal marked '-'.
- Touch the black ohmmeter lead to terminals AC1, AC2, and AC3; the meter should indicate a good diode or low resistance.
- If the meter does not indicate the expected result, the rectifier is bad. Replace the rectifier.
Rotating Rectifier Block Diode Test diagnostic
⚠ Shorted diode can damage exciter rotor
Tools: Digital Multimeter 6V-7070
- Set digital multimeter to diode range and remove all leads
- Test forward bias on each diode (black to positive, red to AC terminals)
- Verify readings between 0.4 and 1.0
- Test reverse bias (red to positive, black to AC terminals)
- Verify overload (OL) readings on reverse bias
- Replace rectifier block if any reading is outside specifications
Varistor - Test diagnostic
Tools: Ohmmeter, Test Light
- Using an ohmmeter, place the ohmmeter across the varistor. The resistance should be a minimum of 15000 ohms.
- Disconnect either lead of the varistor (CR7).
- Place the test light across the varistor.
- Observe the results. The lamp should not light.
- Reverse the test light.
- Observe the results. The lamp should not light.
- If the test light illuminates in either direction, there is a short in the varistor. Replace any faulty varistors with comparable operating characteristics.
Winding Resistance Measurement diagnostic
⚠ Temperature affects resistance; test at room temperature only
⚠ Winding damage if outside specifications
Tools: Digital Multimeter, Milliohmmeter (Wheatstone Bridge)
- Disconnect winding from other components before measuring
- Measure armature windings with milliohmmeter (L2, L4, L5)
- Measure field windings with multimeter (L1, L3)
- Test at room temperature only
- Compare measurements to specification values
- Verify no continuity between windings or between winding and ground
Lead to Lead Connection installation
Tools: Varnished cambric tape 5N-4685, Vinyl plastic tape 5N-4686, Cable straps
- Fasten leads using flat plated washer under bolt and nut
- Apply two layers of varnished cambric high voltage tape
- Overlap tape 50% of width while wrapping
- Extend tape 25 mm onto wire insulation on each side
- Apply two layers of vinyl plastic tape over cambric tape
- Extend vinyl tape 51 mm onto wire insulation on each side
- Group all phase leads and secure with cable straps
Leads to Terminal Strip Connection installation
Tools: Flat plated washers, Cable straps
- When multiple leads attach to bus bar, place on alternate sides
- Use flat plated washers under bolt head and nut
- Group all generator phase leads together after connection
- Tie phase leads together with cable straps
- Maintain minimum 25 mm clearance between phase-to-phase connections
Bearing (Ball) - Lubricating Process maintenance
Tools: Grease fitting, 8F-9866 Grease gun
- Remove either the louver assembly or the rear plate from the rear of the generator housing.
- Remove the top grease pipe plug and remove the lower grease pipe plug.
- Install a grease fitting in the grease pipe.
- Grease the shielded ball bearings with 2S-3230 Bearing Lubricant (53.28 mL (1.8 ounces) to 59.20 mL (2.0 ounces)).
- Wipe off the excess grease. Remove the top grease fitting. Install the plug.
- Operate the generator for one hour to allow the grease to expand and force excess grease from the cavity.
- Stop the engine. Install the plug in the bottom grease pipe and wipe off the excess grease.
- Install the louver assembly or install the rear plate.
Generator - Dry (Controlled Current Method) maintenance
Tools: 8T-0900 Clamp on ammeter (1200 amperes), External Power Source, Rheostat
- Make an external power source.
- Disconnect F1+ and F2- from the voltage regulator. Disconnect the generator load. Connect generator output leads T0, T1, T2, and T3. Install the clamp-on ammeter on output lead T1.
- Connect the rheostat at maximum resistance value. Connect the external power source to wires F1+ and F2-.
- Start the generator set and run at idle speed.
- Monitor the phase current. Gradually increase engine RPM until rated phase current or full generator set speed is obtained.
- If more phase current is necessary, slowly turn the rheostat until the rated phase current is reached.
- On an hourly basis, stop the drying procedure and check the insulation resistance. Repeat until the insulation resistance is acceptable.
Generator Isolating for Maintenance maintenance
⚠ Personal injury or death can result from high voltage.
Tools: Audio/visual proximity tester, Ground straps, DO NOT OPERATE warning tags
- Stop the engine.
- Attach a DO NOT OPERATE or similar warning tag to the engine prime mover starting circuit. Disconnect the engine starting circuit.
- Disconnect the generator from the distribution system.
- Lock out the circuit breaker. Attach a DO NOT OPERATE or similar warning tag to the circuit breaker. Verify all points of possible reverse power flow are locked out.
- For power, sensing, and control circuitry, remove the transformer's fuses.
- Attach a DO NOT OPERATE or similar warning tag to the generator excitation controls.
- Remove the cover of the generator's terminal box.
- Use an audio/visual proximity tester insulated for the proper voltage rating to verify the generator is de-energized.
- Add ground straps to the conductors or terminals. During the entire work period, these ground straps must remain connected.
Recommended Periodic Insulation Test Procedure maintenance
⚠ Personal injury or death can result from electrocution. The megohmmeter applies a high voltage; discharge the leads before touching.
Tools: 142-5055 Insulation Testing Gp, 9U-6003 Insulation Testing Gp
- Take the generator out of service.
- Visually inspect the generator for moisture. If moisture exists, do not perform this insulation test. Dry the unit first.
- Inspect the installation. Determine the equipment that will be tested by the insulation tester.
- Discharge the capacitance of the windings.
- Disconnect T0 from ground.
- Disconnect the regulator sensing lead wires: 20, 22, and 24.
- Connect the insulation tester's RED lead to ground.
- Connect the insulation tester's BLACK lead to T0.
- For units 600 volts or less set the voltage to 500 Volts. For units more than 600 volts set the voltage to 1000 Volts.
- Use the 30/60 Time Resistance Method: apply voltage and observe readings at 30 seconds and 60 seconds.
- Record the 60 second reading corrected for temperature. Record temperature and humidity. Remove voltage.
- Evaluate the readings by comparing the 60 second resistance reading with previous readings taken under similar conditions.
- Switch the insulation tester to OFF to discharge the leads, then disconnect the insulation tester's leads.
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Voltage reconnection
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| 3 | Delta - 6 lead | 6 | Winding pitch must be two-thirds or the generator must be derated. | |
| 3 | Wye - 10 lead (high voltage) | 10 | Illustration 13. Only used on 3306B generator sets and 3406C generator sets. Terminal T0 is the neutral lead. | |
| 3 | Wye - 10 lead (low voltage) | 10 | Only used on 3306B and 3406C generator sets. Terminal T0 is the neutral lead. | |
| 3 | Wye - 12 lead (high voltage) | 12 | Terminals T10, T11, and T12 become neutral connections when tied together. | |
| 3 | Wye - 12 lead (low voltage) | 12 | Terminals T10, T11, and T12 become neutral connections when tied together. | |
| 3 | Wye - 4 lead | 4 | Only used on 3306B generator sets and 3406C generator sets. Terminal T0 is the neutral lead. | |
| 3 | Wye - 6 lead | 6 | Terminals T4, T5, and T6 become neutral connections when the terminals are tied together. | |
| 240 | 3 | Delta - 12 lead | 12 | Terminals T6 and T9 become the neutral connections when tied together and grounded. T2 and T10 connection is the high phase. 240 V, 60 Hz, three-phase: 208 Volts between the high phase and neutral; 240 Volts between either of the low phases and neutral. |
| Four Lead Wye | Three-phase | T1/T2/T3 to loads, T0 to neutral | T1, T2, T3, T0 | Regulator leads 22, 24, 20 from T1, T2, T3 respectively |
| Six Lead Delta | Three-phase | T1/T6, T2/T4, T3/T5 series loop connections | T1, T2, T3, T4, T5, T6 | Delta configuration |
| Six Lead Wye | Three-phase | T1/T2/T3 to loads, T4/T5/T6 to neutral | T1, T2, T3, T4, T5, T6 | Regulator sensing from T1, T2, T3 |
| Ten Lead Wye High Voltage | Three-phase | T1/T2/T3 to loads with T4/T7, T5/T8, T6/T9 series connections | T1, T2, T3, T4, T5, T6, T7, T8, T9, T0 | High voltage configuration |
| Ten Lead Wye Low Voltage | Three-phase | T1/T7, T2/T8, T3/T9 parallel connections | T1, T2, T3, T4, T5, T6, T7, T8, T9, T0 | Low voltage configuration |
| Twelve Lead Delta | Three-phase | T1/T12, T2/T10, T3/T11 series loops with jumpers | T1, T2, T3, T4, T5, T6, T7, T8, T9, T10, T11, T12 | Delta configuration with 12 leads |
| Twelve Lead Wye High Voltage | Three-phase | T1/T2/T3 to loads with series connections | T1, T2, T3, T4, T5, T6, T7, T8, T9, T10, T11, T12 | High voltage configuration with 12 leads |
| Twelve Lead Wye Low Voltage | Three-phase | T1/T7, T2/T8, T3/T9 parallel connections | T1, T2, T3, T4, T5, T6, T7, T8, T9, T10, T11, T12 | Low voltage configuration with 12 leads |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
What is the power rating of the Caterpillar SR4B?
The Caterpillar SR4B is rated 650 kW standby (813.0 kVA).
What engine is in the Caterpillar SR4B?
The Caterpillar SR4B is powered by the Caterpillar C27 TA engine.
What fuel does the Caterpillar SR4B use?
The Caterpillar SR4B runs on Diesel.
What is the oil capacity of the Caterpillar SR4B?
The Caterpillar C27 TA engine in the Caterpillar SR4B has an oil capacity of 68.0 liters.
Which alternator is fitted to the Caterpillar SR4B?
The Caterpillar SR4B uses a SR4B alternator. Insulation class Class H.
What oil filter does the Caterpillar SR4B use?
The Caterpillar SR4B uses oil filter part number 3890434.
What fuel filter does the Caterpillar SR4B use?
The Caterpillar SR4B uses fuel filter part number 3890433.
What air filter does the Caterpillar SR4B use?
The Caterpillar SR4B uses air filter part number 101564109.
Troubleshooting
6Symptoms & remedies
| Symptom | Cause | Remedy |
|---|---|---|
| Low oil pressure indicator flashes, and the engine is shut down. | The engine oil pressure drops below the setpoints for low oil pressure shutdown that are programmed into the GSC. There are two low oil pressure setpoints. One setpoint is used when the engine is at idle speed. The other setpoint is used when the engine is at rated speed. | |
| Emergency stop indicator flashes, and the engine is shut down. | The operator presses the emergency stop push button (ESPB) on the front panel. | |
| High water temperature indicator flashes, and the engine is shut down. | The engine coolant temperature rises above the setpoint for high water temperature shutdown that is programmed into the GSC. | |
| Engine overspeed indicator flashes, and the engine is shut down. | The engine speed exceeds a certain threshold set in the GSC+. | Correct the condition by addressing any issues that caused the engine to overspeed. |
| Engine overcrank indicator flashes, and the engine is shut down. | The engine has been cranked for an extended period without starting. | Correct the condition by ensuring proper start-up procedures are followed. |
| The GSC+ detects an alarm fault | Fault alarm indicator (26) is accompanied by an alarm fault code that is shown on the upper display (29) when the alarm codes key (30) is pressed. |
Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing. Full Caterpillar SR4B troubleshooting guide (17 entries) →
Repair guides
1Step-by-step procedures compiled from the Caterpillar service manual for this model.
Parts
67| Part # | Description | Qty | System | |
|---|---|---|---|---|
| 101564109 | Air Shutoff | Air filter | Amazon eBay | |
| 1R-0762 | Fuel Secondary - ADV | 2 | Fuel filter | Amazon $23.49 eBay $33.99 eBay $34.95 FridayParts $30.63 |
| 1R-0770 | Fuel/Water Separator | 1 | Fuel filter | eBay $38.77 KuduParts $22.00 |
| 1R-1808 | Engine Oil - ADV | 2 | Oil filter | Amazon $70.99 eBay $141.00 eBay $59.99 KuduParts $80.00 |
| M-3675181 | Piston | Piston | Amazon eBay | |
| M-3758261 | Piston | Piston | Amazon eBay | |
| M-4599781 | Gasket Set - Oil Cooler & Lines | Gasket | Amazon eBay | |
| M-CK3675181P | Cylinder Kit | Cylinder kit | Amazon eBay | |
| M-CK3758261P | Cylinder Kit | Cylinder kit | Amazon eBay | |
| g00604696 | Alarm Module (If Equipped) | Alarm module | Amazon eBay | |
| g00630590 | Phase Rotation Meter (Using Three Light Bulbs) | Phase rotation meter | Amazon eBay | |
| g00633434 | Synchronizing Lights Module | Synchronizing lights module | Amazon eBay | |
| i01490119 | Space Heater - Check | Space heater | Amazon eBay | |
| i01490278 | Electronic Modular Control Panel II+ (EMCP II+) | Control panel | Amazon eBay | |
| 01908191 | Overspeed | Service part / kit | Amazon eBay | |
| 101147116 | Engine Operation with Active Diagnostic Codes | Service part / kit | Amazon eBay | |
| 101154196 | Engine Operation with Intermittent Diagnostic Codes | Service part / kit | Amazon eBay | |
| 101233590 | Before Starting Engine | Service part / kit | Amazon eBay | |
| 101446865 | Diagnostic Lamp | Service part / kit | Amazon eBay | |
| 101646248 | After Starting Engine | Service part / kit | Amazon eBay | |
| 102308903 | Starting with Jump Start Cables | Service part / kit | Amazon eBay | |
| 102327037 | Starting the Engine (EMCP II and EMCP II+ (If Equipped)) | Service part / kit | Amazon eBay | |
| 102512380 | Fault Logging | Service part / kit | Amazon eBay | |
| 130-3786 | Control Panel | 1 | Service part / kit | Amazon eBay |
| 2323232 | Connecting rod | Service part / kit | eBay $201.50 | |
| 301108737 | Cold Weather Starting | Service part / kit | Amazon eBay | |
| 5N-4478 | Coupling plate assembly | 1 | Service part / kit | eBay |
| 5N-4479 | Shim 0.8 mm for coupling plate | 6 | Service part / kit | eBay $32.86 |
| 5N-4685 | Varnished cambric tape 15000V | 1 | Service part / kit | eBay $66.33 |
| 5N-4686 | Vinyl plastic electrical tape | 1 | Service part / kit | eBay $21.75 |
| 9S-3263 | Compound for the shoulder of a new zinc rod | Service part / kit | eBay $30.78 | |
| CR1-CR6 | Diodes in bridge rectifier circuit | 6 | Service part / kit | Amazon eBay |
| R-20R2284 | C15/C18/C27/C32 ACERT Trim file (12-digit serial) | 1 | Service part / kit | Amazon eBay |
| R-20R2285 | C15/C18/C27/C32 ACERT Trim file (12-digit serial) | 1 | Service part / kit | Amazon eBay |
| g00104545 | Illustration 4 | 1 | Service part / kit | Amazon eBay |
| g00305862 | Emergency Stop Warning Label | Service part / kit | Amazon eBay | |
| g00306263 | Operation Warning Label | Service part / kit | Amazon eBay | |
| g00572840 | Illustration 9 | Service part / kit | Amazon eBay | |
| g00601027 | Serial Plate | Service part / kit | Amazon eBay | |
| g00604607 | tdown fuel system. | Service part / kit | Amazon eBay | |
| g00611596 | Illustration 14 | Service part / kit | Amazon eBay | |
| g00611770 | Illustration 7 | Service part / kit | Amazon eBay | |
| g00625906 | Illustration 8 | Service part / kit | Amazon eBay | |
| g00627416 | Illustration 31 | Service part / kit | Amazon eBay | |
| i01108098 | Cold Start Strategy | Service part / kit | Amazon eBay | |
| i01359666 | Crushing Prevention and Cutting Prevention | 1 | Service part / kit | Amazon eBay |
| i01372247 | Mounting and Dismounting | 1 | Service part / kit | Amazon eBay |
| i01462046 | Engine Stopping | 1 | Service part / kit | Amazon eBay |
| i01480768 | Burn Prevention | 1 | Service part / kit | Amazon eBay |
| i01489427 | Generator Description | Service part / kit | Amazon eBay | |
| i01489623 | Safety Signs and Labels - Electrical Distribution (Generator) | Service part / kit | Amazon eBay | |
| i01489943 | Engine Stopping | Service part / kit | Amazon eBay | |
| i01489957 | Electrical System | Service part / kit | Amazon eBay | |
| i01489970 | Generator Isolating for Maintenance | Service part / kit | Amazon eBay | |
| i01490002 | Reference Numbers | Service part / kit | Amazon eBay | |
| i01490046 | Voltage Connections | Service part / kit | Amazon eBay | |
| i01496776 | Fire Prevention and Explosion Prevention | 1 | Service part / kit | Amazon eBay |
| i01553111 | Generator Lead Connections | Service part / kit | Amazon eBay | |
| i01593543 | Generator Isolating for Maintenance | 1 | Service part / kit | Amazon eBay |
| i01658146 | Important Safety Information | Service part / kit | Amazon eBay | |
| i01805780 | Before Starting Engine | 1 | Service part / kit | Amazon eBay |
| i01830750 | Engine Maintenance Information | Service part / kit | Amazon eBay | |
| i01909882 | Engine Speed Governing | Service part / kit | Amazon eBay | |
| i02106213 | Electrical System | 1 | Service part / kit | Amazon eBay |
| i02136012 | Engine Starting | 1 | Service part / kit | Amazon eBay |
| i02879636 | Safety Messages | Service part / kit | Amazon eBay | |
| i07966018 | Important Safety Information | 1-UP | Service part / kit | Amazon eBay |
Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 136.5 | 36.1 | |
| Prime | 50% | 185.0 | 48.9 |
| Prime | 75% | 262.5 | 69.3 |
| Prime | 100% | 374.8 | 98.9 |
| Standby | 188.2 | 49.7 | |
| Standby | 50% | 122.2 | 32.3 |
| Standby | 75% | 171.6 | 45.3 |
| Standby | 100% | 216.6 | 57.2 |