Home›Repair guides›Caterpillar›Generator Set Functional Test

Caterpillar — Generator Set Functional Test

Testing & diagnosis

From a Caterpillar owner's manual covering: 3306B, 3406, 3406E, 3412C, SR4B. Check it applies to your exact model before use.

Applies to: Caterpillar 3306B, Caterpillar 3406, Caterpillar 3406E, Caterpillar 3412C, Caterpillar SR4B

Before you start

  • Do not operate the generator set at a speed higher than one-half of the rated speed.

Procedure

  1. Stop the generator. Connect the potential transformer's high voltage winding to generator terminals T1 and T2. Connect the voltmeter to the low voltage winding.
  2. Disconnect wires F1+ and F2- from the voltage regulator. Disconnect the generator from the load.
  3. Connect a 12 VDC automotive battery to wires F1+ and F2-.
  4. Operate the generator set at half the rated speed.
  5. Measure the AC voltage across the low voltage terminals corresponding to T1-T2, T2-T3, and T3-T1. Record the voltages.
  6. Monitor the voltage between any two locations, then decrease the generator set speed by 10 percent and increase it by 10 percent.
  7. The measured voltages should be nearly equal and should measure a minimum of 85 VAC.
  8. When speed is decreased by 10 percent the voltages should decrease by 10 percent; when increased by 10 percent the voltages should increase by 10 percent.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Minimum 85 VAC

Full service-parts list: Caterpillar 3406 →, Caterpillar 3406E →, Caterpillar 3412C →, Caterpillar SR4B →

Source: Caterpillar owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Caterpillar repair guides →