HomeControllersEMCP 3.3

EMCP 3.3 Controller

The EMCP 3.3 is a generator-set controller. It is used on generator sets from Caterpillar, including the C18 ACERT OILFIELD GENERATOR SET, C18-20' XQ600, C32-20' PM1000 and C32-30' XQ1000.

20
Generator sets
Caterpillar
Brand
484–2000 kW
Power range
Diesel
Fuel

Specifications

DisplayGraphical display with positive image, transflective LCD, adjustable white backlight/contrast, 64 x 240 pixel, 28 mm x 100 mm, white backlit graphical display
CommunicationsJ1939, J1939 #2, MODBUS RS-485
Digital inputs8 TOTAL (Emergency Stop, Remote Start, 6 Programmable)
Operating temperature-40° C to 70° C (-40° F to 158° F) for Display, -20° C to 70° C (-4° F to 158° F) for Monitoring Functionality & Controls
ProtectionsOvercrank, Low Coolant Temperature Warning, High Coolant Temperature Warning/Shutdown, Low Oil Pressure Warning/Shutdown, Overspeed, Control Switch Not In Auto, High/Low Battery Voltage, Emergency Stop Activated, Low Fuel Pressure Warning/Shutdown, High Fuel Pressure Warning/Shutdown, Fuel Filter Restriction Warning/Shutdown, High Intake Manifold Air Temperature Warning/Shutdown, High Fuel Tempera

Troubleshooting

14

Symptoms & remedies

Symptom
Overcrank
Low Coolant Temperature Warning
High Coolant Temperature Warning/Shutdown
Low Oil Pressure Warning/Shutdown
Overspeed
Control Switch Not In Auto
High/Low Battery Voltage
Emergency Stop Activated
Low Fuel Pressure Warning/Shutdown
High Fuel Pressure Warning/Shutdown
Fuel Filter Restriction Warning/Shutdown
High Intake Manifold Air Temperature Warning/Shutdown
High Fuel Temperature Warning/Shutdown
High Oil Temperature Warning/Shutdown

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Extracted directly from this controller's manual.

Generator sets using this controller

20
Caterpillar C18 ACERT OILFIELD GENERATOR SETCaterpillar C18-20' XQ600Caterpillar C32-20' PM1000Caterpillar C32-30' XQ1000Caterpillar DM9073Caterpillar DM9628Caterpillar EMCP 3.3Caterpillar SR4BCaterpillar SR4B GeneratorCaterpillar XQ 2000Caterpillar XQ1000

Troubleshooting

22

Fault codes

CodeMeaning
$0000Valid Data
$0001Error
$83Exception Response to Read Registers Query
$86Exception Response to Write Single Register Query
$90Exception Response to Write Multiple Registers Query
21Fault shutdown
22Fault alarm
2301A ControlWhen the engine oil pressure is increased beyond the low oil pressure setpoint, the GSC will inform the governor that the engine speed should be increased from IDLE to RATED rpm.
g00604607The fault alarm indicator (3) flashes when the GSC detects an alarm fault.

Symptoms & remedies

SymptomCauseRemedy
Emergency stop conditionOperator presses the Emergency Stop Push Button (ESPB) on the front panel.The emergency stop indicator FLASHES and the engine is shut down. The engine is not allowed to start until the condition is corrected.
Emergency stop indicator flashes, and the engine is shut down.The operator presses the emergency stop push button (ESPB) on the front panel.
Engine overcrank indicator flashes, and the engine is shut down.The engine has been cranked for an extended period without starting.Correct the condition by ensuring proper start-up procedures are followed.
Engine overspeedEngine speed exceeds the setpoint for engine overspeed that is programmed into the GSC+.The engine is shutdown and the engine is not allowed to start until the fault is corrected.
Engine overspeed indicator flashes, and the engine is shut down.The engine speed exceeds a certain threshold set in the GSC+.Correct the condition by addressing any issues that caused the engine to overspeed.
Generator parameters are not matched to the busIf the generator and bus voltages, frequencies and phases are in sync, the lamps will light continuously. If not, the associated lamp will flash.
High water temperatureEngine coolant temperature rises above the setpoint for high water temperature shutdown that is programmed into the GSC+.The engine is shutdown and the engine is not allowed to start until the fault is corrected.
High water temperature indicator flashes, and the engine is shut down.The engine coolant temperature rises above the setpoint for high water temperature shutdown that is programmed into the GSC.
Low oil pressureEngine oil pressure drops below the setpoints for low oil pressure shutdown that are programmed into the GSC+.The tow oil pressure indicator FLASHES, and the engine is shut down. The engine is not allowed to start until the fault is corrected.
Low oil pressure indicator flashes, and the engine is shut down.The engine oil pressure drops below the setpoints for low oil pressure shutdown that are programmed into the GSC. There are two low oil pressure setpoints. One setpoint is used when the engine is at idle speed. The other setpoint is used when the engine is at rated speed.
OvercrankEngine does not start within the setpoint for overcrank.
The GSC+ detects a shutdown faultThe engine will shut down if the engine is running. The engine will not be allowed to start.
The GSC+ detects an alarm faultFault alarm indicator (26) is accompanied by an alarm fault code that is shown on the upper display (29) when the alarm codes key (30) is pressed.

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.