| Clearance | Air shutoff damper plunger distance A - replace plunger | 18.3 | mm (0.72 inch) | replace plunger if distance A is less than this value |
| Clearance | Cooling system coolant level below bottom of filler pipe (no sight gauge) | 13 | mm (0.5 inch) | maintain coolant within this tolerance |
| Clearance | Crankshaft vibration damper fluid viscosity degradation limit | 20 | percent | typical limit used by Hasse & Wrede GmbH |
| Clearance | Radiator cleaning - air nozzle distance from fins | 6 | mm (0.25 inch) | hold nozzle approximately this distance |
| Gap | Air inlet filter differential pressure switch - clean filter | 15.2 | mm (0.6 inch) of water | if differential pressure rises above this value |
| Other | Rating condition (diesel 7 L and higher) | 99 kPa (29.31 in Hg) dry barometer, 25°C (77°F) | | SAE J1995 inlet air standard |
| Other | Rating condition (diesel up to 6.6 L) | 100 kPa (29.5 in Hg) total barometric pressure, 1 kPa (.295 in Hg) vapor pressure, 25°C (77°F) | | ISO/TR14396 inlet air standard |
| Other | Rating condition (gas) | 100 kPa (29.61 in Hg) and 25°C (77°F) | | SAE J1349 standard |
| Pressure | Air nozzle cleaning pressure (aftercooler core) | 205 | kPa (30 psi) | maximum air pressure at nozzle |
| Pressure | Air starting motor air supply pressure | 620 to 1550 | kPa (90 to 225 psi) | minimum 620 kPa (90 psi); maximum must not exceed 1550 kPa (225 psi) |
| Pressure | Air starting motor normal air pressure | 758 to 965 | kPa (110 to 140 psi) | normal operating air pressure |
| Pressure | Compressed air cleaning pressure (aftercooler, air cleaner element) | 207 | kPa (30 psi) | maximum |
| Pressure | Crankcase pre-lube oil pressure before start | 70 | kPa (10 psi) | crank engine with fuel off until oil pressure gauge indicates this |
| Pressure | Engine oil filter differential pressure limit | 103 | kPa (15 psi) | replace oil filter elements |
| Pressure | Fuel filter differential pressure limit | 103 | kPa (15 psi) | replace secondary fuel filter elements |
| Pressure | Radiator cleaning water pressure | 275 | kPa (40 psi) | maximum; less than 275 kPa (40 psi) |
| Resistance | Generator insulation resistance minimum (severely contaminated) | 1 | megohm | minimum reading expected with severely contaminated generators |
| Resistance | L1 Exciter Field winding resistance - 1400 Frame | 11 | ohms | at room temperature |
| Resistance | L1 Exciter Field winding resistance - 1600 Frame | 10 | ohms | at room temperature |
| Resistance | L1 Exciter Field winding resistance - 1800 Frame | 10.9 | ohms | at room temperature |
| Resistance | L2 Exciter Rotor winding resistance - 1400 Frame | 0.06 | ohms | at room temperature |
| Resistance | L2 Exciter Rotor winding resistance - 1600 Frame | 0.06 | ohms | at room temperature |
| Resistance | L2 Exciter Rotor winding resistance - 1800 Frame | 0.05 | ohms | at room temperature |
| Resistance | Main Field for the Rotor (L3) - 1400 Frame | .35 | ohms | at room temperature |
| Resistance | Main Field for the Rotor (L3) - 1600 Frame | .5 | ohms | at room temperature |
| Resistance | Main Field for the Rotor (L3) - 1800 Frame | .9 | ohms | at room temperature |
| Resistance | Main field (rotor) (L3) | 0.35 to 1.2 | ohms | use multimeter |
| Resistance | Main stator (L4) | less than 0.1 | ohm | use milliohmmeter |
| Resistance | Pilot exciter stator (L5) | less than 0.1 | ohm | use milliohmmeter |
| Resistance | Varistor CR7 resistance between positive and negative rectifier terminals | minimum 15000 | ohms | negative rectifier block |
| Speed | Low idle setting for electric sets (50 Hz) | 80 | percent of full speed | 50 Hz units |
| Speed | Low idle setting for electric sets (60 Hz) | 66 | percent of full speed | 60 Hz units |
| Temperature | Cooling System Coolant (ELC) flush temperature | 49 to 66 | °C (120 °F to 150 °F) | operate engine until this temperature is reached |
| Temperature | Cooling system cleaning - minimum coolant temperature | 82 | °C (180 °F) | during cleaning with Fast Acting Cooling System Cleaner |
| Temperature | Crankshaft vibration damper temperature | 100 | °C (212 °F) | if reached, consult Caterpillar dealer |
| Temperature | Generator bearing grease temperature limits - 2S-3230 bearings | -29 to 80 | °C (-20.2 °F to 176 °F) | minimum/maximum |
| Temperature | Generator bearing grease temperature limits - roller bearings (Mobilith SHC220) | -40 to 80 | °C (-40 °F to 176 °F) | minimum/maximum |
| Temperature | Generator bearing temperature - alarm | 85 | °C (185 °F) | EMCP 3.2/3.3 alarm |
| Temperature | Generator bearing temperature - shutdown | 95 | °C (203 °F) | EMCP 3.2/3.3 shutdown |
| Temperature | Generator winding temperature maximum during drying | 85 | °C (185.0 °F) | do not exceed |
| Temperature | Jacket water coolant temperature maintained by jacket water heater at 0 °C (32 °F) ambient | 32 | °C (90 °F) | ambient 0 °C (32 °F) |
| Temperature | Oven drying of generator | 65 | °C (149 °F) | forced air drying oven for four hours |
| Torque | Engine air cleaner service indicator | 2 | N·m (18 lb in) | tighten when installing new service indicator |
| Voltage | Generator set functional test minimum measured voltage | 85 | VAC | nearly equal across T1-T2, T2-T3, T3-T1 |
| Voltage | Space heater external source | 115 or 230 | VAC single phase | 200 VAC must be used when source is 50 hertz |