Caterpillar 3516C / 3516C Generator Set — Generator - Dry (Controlled Current Method)

Maintenance · Generator windings

For the Caterpillar 3516C / 3516C Generator Set, from the Caterpillar operator's manual.

Applies to: Caterpillar 3516C, Caterpillar 3516C engine

Before you start

  • Do not operate generator if windings are wet
  • Only qualified personnel should perform troubleshooting and repair

Procedure

  1. Make external power source per Illustration 91.
  2. Disconnect F1+ and F2- from voltage regulator; connect generator output leads T0, T1, T2, T3 together; install clamp-on ammeter on T1.
  3. Adjust rheostat to maximum resistance; connect external power source to F1+ and F2-.
  4. Start generator set; run at idle speed.
  5. Monitor phase current; gradually increase engine rpm with EMCP 3 control panel.
  6. Slowly turn rheostat until rated phase current is reached.
  7. Stop hourly; check insulation resistance; repeat until acceptable.

Tools required

  • 225-8266 Clamp-on ammeter (1200 amperes) Amazon
  • External power source circuit Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Do not exceed rated phase current on generator nameplate
  • Winding temperature must not exceed 85 °C (185.0 °F)

Full service-parts list: Caterpillar 3516C →, Caterpillar 3516C engine →

Source: Caterpillar operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.