Caterpillar 3516C / 3516C Generator Set — Air Shutoff - Test (ADEM III Engine Control Modules)
Testing & diagnosis · Air shutoff gates and switches
For the Caterpillar 3516C / 3516C Generator Set, from the Caterpillar operator's manual.
Applies to: Caterpillar 3516C, Caterpillar 3516C engine
Before you start
- Do not start the engine during the test
- Use EMERGENCY STOP switch to stop engine if it does not shut down
Procedure
- Ensure both air shutoff gates latched OPEN and switches connected; turn power ON.
- Activate EMERGENCY STOP switch; both gates should close.
- Reset EMERGENCY STOP to RUN; reset right side air shutoff OPEN.
- Select Run/Start; engine should fail to start.
- Reset EMERGENCY STOP; reset left side air shutoff OPEN; engine should fail to start.
- Start engine; disconnect right side air shutoff; gates should close and engine shut down.
- Start engine; disconnect left side air shutoff; gates should close and engine shut down.
- Reset both air shutoffs and EMERGENCY STOP switch; operate engine normally.