Home›Repair guides›Caterpillar›Exciter Field Static Flashing

Caterpillar SR4B — Exciter Field Static Flashing

Repair & overhaul

For the Caterpillar SR4B, from the Caterpillar service manual.

Applies to: Caterpillar SR4B

Before you start

  • Only for self-excited generators
  • Do not flash PMPE generators

Procedure

  1. Stop the engine
  2. Disconnect wires F1 GEN and F2 GEN from voltage regulator
  3. Connect positive cable of 6 VDC source to wire F1 GEN
  4. Momentarily apply negative cable to wire F2 GEN (2-3 times)
  5. Do not hold negative cable longer than 1-2 seconds each time
  6. Reconnect wires F1 and F2 to voltage regulator

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • 6 VDC source
  • Brief 1-2 second contacts

Full service-parts list: Caterpillar SR4B →

Source: Caterpillar service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.