| AUXILIARY SHUTDOWN | Auxiliary Shutdown | Unit will not start | Shutdown | Set auxiliary shutdown switch(es) to CLOSED (I); clear alarm |
| BATERÍA BAJA | BATERÍA BAJA | Indicador LED amarillo encendido en cualquier estado. | Warning | Borre la alarma. Navegue hasta BATTERY MENU del MAIN MENU para revisar la batería. Si indica GOOD, comuníquese con un IASD. Si indica CHECK BATTERY, reemplace la batería. |
| BATTERY PROBLEM | Battery Problem | Yellow LED illuminated | Warning | Contact servicing dealer |
| Battery Problem | Battery Fault | Battery condition poor or battery charger issue | Warning | Inspect battery condition and connections. Contact IASD if needed. |
| CARGADOR SIN CA | CARGADOR SIN CA | Indicador LED amarillo encendido en cualquier estado. | Warning | Comuníquese con un IASD. |
| CHARGER MISSING AC | Charger Missing AC | Yellow LED illuminated in any state | Warning | Contact an IASD |
| CHARGER WARNING | Charger Warning | Yellow LED illuminated | Warning | Contact servicing dealer |
| Controller Fault | Control Module Failure | Internal controller fault detected | Shutdown | Contact IASD for assistance |
| CONTROLLER FAULT | Controller Fault | Alarm message listed on controller menu. | Shutdown | Contact an IASD. |
| DESCONEXIÓN AUXILIAR | DESCONEXIÓN AUXILIAR | La unidad no arranca. | Shutdown | Coloque los interruptores de desconexión auxiliar en posición CERRADA (I). |
| EMERGENCY STOP | Emergency Stop | Alarm message listed on controller menu. | Shutdown | Check emergency shutdown switch and reset. |
| EXERCISE SET ERROR | Exercise Set Error | Exercise timer setting error | Warning | |
| Exercise Set Error | Exercise Set Error | Warning; displayed if the exercise period becomes corrupted | Warning | Reset the exercise period to clear |
| EXERCISER NOT SET | Exerciser not set | Indicates the exercise timer has not been set. | Info | Set the exercise timer per Section 3.6. |
| FUEL PRESSURE | Fuel Pressure | Fuel pressure warning | Warning | |
| FUSE PROBLEM | Fuse Problem | Unit will not start in AUTO with utility loss | Warning | Check 7.5amp fuse, replace with ATO 7.5Amp fuse if bad |
| High Engine Temperature | High Engine Temperature | Shutdown alarm, auto reset; 10 second delay on start-up and 1 second delay before shutdown; contacts close if temperature exceeds approximately 144 °C (293 °F) | Shutdown | Auto reset when condition clears and restart engine if a valid start signal is present |
| HIGH TEMP. | High temperature | High temperature switch contacts close if temperature exceeds approximately 140 C (284 F). | Shutdown | Allow unit to cool; generator restarts and LED resets once temperature returns to a safe level. |
| HIGH TEMPERATURE | High Temperature | Unit shuts down during operation | Shutdown | Check ventilation around generator, intake, exhaust and rear of generator |
| High Temperature | Overheat | Engine operating temperature too high | Shutdown | Inspect ventilation around generator, intake, exhaust, and rear. Ensure no obstructions present. |
| INSPECCIONE LA BATERÍA | INSPECCIONE LA BATERÍA | Indicador LED amarillo encendido en cualquier estado. | Warning | Inspeccione la batería. Presione ENTER para borrar. |
| INSPECT BATTERY | Inspect Battery | Battery inspection reminder | Info | Inspect battery; press ENTER to clear. |
| INTERNAL FAULT | Internal Fault | Internal controller fault | Shutdown | Contact servicing dealer. |
| Internal Fault | Internal Fault | Shutdown alarm; this alarm cannot be cleared | Shutdown | Call service dealer |
| LOW BATTERY | Low Battery | Yellow LED illuminated | Warning | Clear alarm; check battery via control panel BATTERY MENU; if GOOD contact dealer, else replace battery |
| Low Battery | Battery Voltage Low | Starting battery voltage below acceptable level | Warning | Inspect battery and battery cables. Charge or replace battery if necessary. |
| LOW OIL | Low oil pressure | Low oil pressure switch contacts close when oil pressure drops below the 8 psi range. | Shutdown | Add oil; turn AUTO/OFF/MANUAL switch to OFF and then back to AUTO. |
| LOW OIL PRESSURE | Low Oil Pressure | Unit will not start in AUTO with utility loss | Shutdown | Check oil level / add oil per Owners Manual |
| Low Oil Pressure | Low Oil Level or Pressure | Insufficient oil pressure in engine | Shutdown | Check engine oil level and top up if necessary. Contact IASD if problem persists. |
| LOW VOLTS REMOVE LOAD | Low Volts Remove Load | Unit will not start in AUTO with utility loss | Shutdown | Clear alarm and remove household loads, put back in AUTO and restart |
| Maintenance Message | Maintenance Message | Maintenance alert; displayed when a maintenance period expires | Info | Press Enter to confirm reset; clears the alert and resets maintenance counters |
| MISWIRE | Miswire | Unit will not start in AUTO with utility loss | Shutdown | Contact servicing dealer |
| NO UTILITY SENSE | No utility sense | Flashing LEDs indicate utility sense voltage is not connected or is below 168 volts AC. | Info | Verify utility sense voltage connection. |
| NOT ACTIVATED | Not Activated | Unit will not start in AUTO with utility loss | Warning | Refer to activation section in owners manual |
| OVER CRANK | Overcrank | Unit cranks and rests for a preset time limit then stops cranking when it cannot start. | Shutdown | Set AUTO/OFF/MANUAL switch to OFF and back to AUTO to reset the control board. |
| Over Crank | Over Crank | Shutdown alarm; occurs if the engine has not started within the specified crank cycle | Shutdown | Reset the control board and restart up to two more times if necessary |
| OVER SPEED | Overspeed | Protection shuts the unit down if it runs faster than the preset limit. | Shutdown | Contact the nearest Authorized Dealer. |
| Over Speed | Over Speed | Shutdown alarm; 4320 RPM for three (3) seconds or 4500 RPM immediately | Shutdown | Contact the nearest Dealer if this failure occurs |
| OVER VOLTAGE | Over Voltage | Overvoltage alarm | Shutdown | Contact servicing dealer. |
| OVERCRANK | Overcrank | Unit will not start in AUTO with utility loss | Shutdown | Check fuel line shutoff valve ON, clear alarm, attempt manual start |
| Overcrank | Extended Cranking | Engine failing to start after extended crank attempts | Shutdown | Check fuel supply, spark plugs, and fuel system. Contact IASD for further diagnosis. |
| Overload | Overload Detected | Electrical load exceeds generator capacity | Shutdown | Remove household electrical loads from generator |
| OVERLOAD REMOVE LOAD | Overload Remove Load | Unit shuts down during operation | Shutdown | Clear alarm, remove household loads, put back in AUTO and restart |
| OVERLOAD WARNING | Aviso de sobrecarga | Aviso de sobrecarga. | Warning | Remova as cargas domésticas do gerador. |
| OVERSPEED | Overspeed | Unit will not start in AUTO with utility loss | Shutdown | Contact servicing dealer |
| Overspeed | RPM Overspeed | Engine running at excessive RPM | Shutdown | Contact IASD for assistance |
| OVERVOLTAGE | Overvoltage | Unit will not start in AUTO with utility loss | Shutdown | Contact servicing dealer |
| Overvoltage | Output Voltage High | Generator voltage exceeding nominal rating | Shutdown | Reduce electrical load and restart. Contact IASD if issue persists. |
| PROBLEMA DE BATERÍA | PROBLEMA DE BATERÍA | Indicador LED amarillo encendido en cualquier estado. | Warning | Comuníquese con un IASD. |
| RPM SENSE LOSS | RPM Sense Loss | Unit was running and shuts down, attempts to restart | Shutdown | Clear alarm, remove household loads, put back in AUTO and restart; may be fuel issue, contact servicing dealer |
| RPM Sense Loss | RPM Sense Loss | Shutdown alarm; if no valid RPM signal within three (3) seconds during cranking, or lost for one (1) second while running | Shutdown | Control board shuts down, waits 15 seconds, then re-cranks; may re-crank once more before latching out |
| RPM Sensor Loss | RPM Signal Loss | RPM sensor signal not detected | Shutdown | Contact IASD for assistance |
| SERVICE A | Service A | Yellow LED illuminated, maintenance due | Info | Perform SERVICE A maintenance, hit ENTER to clear |
| SERVICE B | Service B | Yellow LED illuminated, maintenance due | Info | Perform SERVICE B maintenance, hit ENTER to clear |
| SHUTDOWN SWITCH | Shutdown Switch | Unit will not start. Flashing red LED. | Shutdown | Check emergency shutdown switches. Set switch(es) to CLOSED (I). Clear alarm. |
| STEPPER OVER CURRENT | Stepper Over Current | Stepper motor over current | Shutdown | Contact servicing dealer. |
| STEPPER OVERCURRENT | Stepper Overcurrent | Unit will not start in AUTO with utility loss | Shutdown | Contact servicing dealer |
| UNDER VOLTAGE | Under Voltage | Undervoltage alarm | Shutdown | Contact servicing dealer. |
| Under-frequency | Under-frequency | Shutdown alarm; if generator stays under frequency for more than 30 seconds; setting is 50 Hz | Shutdown | Check generator output |
| UNDERSPEED | Underspeed | Unit will not start in AUTO with utility loss | Shutdown | Contact servicing dealer |
| Underspeed | Engine Speed Too Low | Engine RPM below nominal specification | Shutdown | Contact IASD for assistance |
| UNDERVOLTAGE | Undervoltage | Unit will not start in AUTO with utility loss | Shutdown | Contact servicing dealer |
| Undervoltage | Output Voltage Low | Generator voltage below nominal rating | Shutdown | Reduce electrical load and restart. Contact IASD if issue persists. |
| USB WARNING | Aviso de USB | Aviso relacionado ao dispositivo USB. | Warning | Tente novamente com USB de melhor qualidade. Os nomes dos ficheiros no USB não podem ter mais de 8 caracteres. |
| Wiring Error | Electrical Wiring Fault | Wiring configuration error detected | Shutdown | Contact IASD for assistance |
| WIRING ERROR | Wiring Error / Miswire | Controller wiring error | Shutdown | Contact servicing dealer. |