Generac GT-990 — Break-in Procedure
Operation · Generator
For the Generac GT-990, from the Generac owner's manual.
Applies to: Generac GT-990 engine
Procedure
- Set AUTO/OFF/MANUAL switch to AUTO.
- Turn OFF utility power to the transfer switch.
- Unit starts and transfer switch transfers to standby.
- Run one hour at 25% rated load.
- Run one hour at 50% rated load.
- Run one hour at 75% rated load.
- Run one hour at 100% rated load.
- Turn ON utility power; unit runs one minute then shuts down.
- Allow unit to cool.
- Set switch to OFF, remove 7.5A and 15A fuses, disconnect battery cables.
- Drain oil and replace the oil filter; refill with synthetic oil.
- Reconnect battery cables and insert fuses into control panel.
Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.