Home›Repair guides›Generac›ATS Manual Operation

Generac — ATS Manual Operation

Operation · Transfer switch

From a Generac owner's manual covering: GH-410, GT-530, GT-990, GT-999. Check it applies to your exact model before use.

Applies to: Generac GH-410, Generac GH-410 engine, Generac GT-530 engine, Generac GT-990 engine, Generac GT-999 engine

Before you start

  • Do NOT manually transfer under load.
  • Do not use excessive force when operating manually.

Procedure

  1. Turn generator AUTO/OFF/MANUAL switch to OFF.
  2. Turn OFF UTILITY SERVICE DISCONNECT circuit breaker.
  3. Attach manual handle to moveable contact carrier arm.
  4. Move handle UP for UTILITY (NORMAL) position.
  5. Move handle DOWN for GENERATOR (STANDBY) position.
  6. Remove handle and return to storage bracket when finished.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Full service-parts list: Generac GH-410 →

Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.