| 1048 | VSCF Overload | Unit shuts down during operation | Shutdown | Alternator, AVR or wiring damaged. Contact servicing dealer. |
| 1049 | VSCF Overload | Unit shuts down during operation | Shutdown | Generator output shorted or severely overloaded; clear overload and restart |
| 1051 | VSCF High Battery | Yellow LED illuminated in any state | Warning | Voltage supply to AVR is high; check external battery charger installation or contact servicing dealer |
| 1052 | VSCF DC Overvoltage | Unit shuts down during operation | Shutdown | Generator temporarily overloaded or output shorted; try restart |
| 1053 | VSCF Gate Fault | Unit shuts down during operation or starting | Shutdown | AVR is damaged; contact servicing dealer |
| 1054 | VSCF IGBT Overtemp. | Unit shuts down during operation or starting | Shutdown | Replace AVR filter, inspect fan, check intake/exhaust, check ambient temperature; contact servicing dealer |
| 1055 | VSCF Phase Error | Unit shuts down during starting | Shutdown | Check stepper motor, linkage, gas pressure; contact servicing dealer if alternator damaged |
| 1056 | VSCF Undervoltage | Unit shuts down during operation or starting | Shutdown | Load too large, remove and restart; or alternator/AVR damage, contact servicing dealer |
| 1057 | VSCF Overvoltage | Unit shuts down during operation or starting | Shutdown | Generator overloaded; remove load and restart |
| 1058 | VSCF DC Undervoltage | Unit shuts down during operation or starting | Shutdown | Alternator damage; contact servicing dealer |
| 1059 | VSCF Field Loss | Unit shuts down during starting | Shutdown | Alternator damage; contact servicing dealer |
| 1060 | Big Fan Failure | Unit shuts down during operation | Shutdown | AVR electronics exceeded 70°C; replace AVR filter, check intake/exhaust/ambient temp; contact servicing dealer |
| 1061 | VSCF Field Loss | Unit shuts down during operation | Shutdown | Alternator damage; contact servicing dealer |
| 1065 | Overfrequency | Unit shuts down during operation | Shutdown | Overload, RPM sensor failure, or stepper motor problem; contact servicing dealer |
| 1066 | VSCF Speed mismatch | Unit shuts down during operation or starting | Shutdown | Fuel pressure loss, large overload, or throttle/engine problem; contact servicing dealer |
| 1070 | Small fan failure | Small fan failure displayed; continues 80 minutes without fan if running in AUTO | Warning | Check fan wiring/mechanical, check AVR filter for blocked air path |
| 1100 | Overcrank | Engine Cranks but will not Start (5 crank attempts) | Shutdown | Problem 17 |
| 1200 | Overspeed | Prolonged over specified Hz for 3 seconds | Shutdown | Test 12 |
| 1205 | Overspeed | Instantaneous over specified Hz for 0.1 second | Shutdown | Test 12 |
| 1207 | Overspeed | Monitors zero cross timing of AVR; 150 ms of 4500 rpm or higher | Shutdown | Test 64 and Test 60 |
| 1300 | Low Oil Pressure | Occurred while running; check oil level and pressure | Shutdown | Test 61 |
| 1400 | High Temperature | Air flow impeded; check inlet/outlet for debris | Shutdown | Test 62 |
| 1501 | RPM Sensor | Twin Cylinder+Running; RPM sensor loss | Shutdown | Test 50 and Test 64 |
| 1505 | RPM Sensor | Twin Cylinder+Cranking; RPM sensor loss | Shutdown | If engine cranks, Test 64. If not crank, Problem 15. |
| 1511 | RPM Sensor | Single Cylinder+Running; RPM sensor loss | Shutdown | Test 50 and Test 64 |
| 1515 | RPM Sensor | Single Cylinder+Cranking; RPM sensor loss | Shutdown | If engine cranks, Test 64. If not crank, Problem 15. |
| 1600 | Underspeed | Unit is overloaded, slowing engine speed, fuel supply low or throttle control problem | Shutdown | Problem 3, or Test 50, or Test 12 |
| 1800 | Overvoltage | Prolonged over-voltage | Shutdown | |
| 1900 | Undervoltage | Prolonged under-voltage; below 80% for 10+ seconds | Shutdown | Preliminary Output Voltage Test |
| 1901 | Undervoltage | Instantaneous under-voltage due to sudden loss of voltage | Shutdown | Preliminary Output Voltage Test |
| 1902 | Undervoltage | Both zero crosses missing; faulty excitation winding or zero cross circuit | Shutdown | Preliminary Output Voltage Test |
| 1906 | Undervoltage | Single zero cross missing; faulty excitation winding or zero cross circuit | Shutdown | Preliminary Output Voltage Test |
| 2099 | Wiring Error | Mis-wired; customer connection low voltage and high voltage wires crossed | Shutdown | Check customer connection in generator |
| 2100 | Overload Remove Load | Overloaded - Default; one or both CTs detecting overload | Shutdown | Remove Load |
| 2299 | Undervoltage Overload | Unit was overloaded and attempted to start with large load | Shutdown | Remove Load |
| 2399 | Stepper Overcurrent | Current flow in stepper coil(s) above specification | Shutdown | Test 12 |
| 2400 | Fuse Problem | Missing or damaged 7.5 amp controller fuse | Shutdown | Test 44 |
| 2800 | Aux Shutdown | External shut down circuit is open | Shutdown | Check continuity of harness and operation of switch(es). Repair/replace as needed. |
| AC Sens Loss Shutdwn | Loss of AC sensing shutdown | Controller shut down the generator because there was less than 5% of rated voltage measured on Phase A for 3 seconds, only in AUTO. | Shutdown | Check for loose wiring and connections. Check all AC leads. Troubleshoot alternator. |
| AC Sens Loss Warning | Loss of AC sensing warning | Controller measured less than 5% of rated voltage on Phase A for 1 second, 10 seconds after crank disconnect. | Warning | Check for loose wiring and connections. Check all AC leads. Troubleshoot alternator. |
| Aux Input Shutdwn | Auxiliary input shutdown | Digital input for a custom shutdown (AuxiliaryInputShutdown - PIM) was activated (low). | Shutdown | Check customer equipment connected to the PIM module. |
| AUXILIARY SHUTDOWN | Auxiliary Shutdown | Unit will not start | Shutdown | Set auxiliary shutdown switch(es) to CLOSED (I); clear alarm |
| BATERÍA BAJA | BATERÍA BAJA | Indicador LED amarillo encendido en cualquier estado. | Warning | Borre la alarma. Navegue hasta BATTERY MENU del MAIN MENU para revisar la batería. Si indica GOOD, comuníquese con un IASD. Si indica CHECK BATTERY, reemplace la batería. |
| Battery CRLow Warning | Battery cranking low warning | Battery voltage dropped to 11 VDC or less for 30 seconds or more. | Warning | Check engine starting battery. Check battery charger DC output voltage from RDC2. |
| Battery High Warning | Battery high warning | Battery voltage above the high warning setting for 10 seconds or more. | Warning | Check engine starting battery. |
| Battery Low Warning | Battery low warning | Battery voltage below the low warning setting for 90 seconds or more. | Warning | Check engine starting battery. Check battery charger DC output voltage from RDC2. |
| BATTERY PROBLEM | Battery Problem | Yellow LED illuminated | Warning | Contact servicing dealer |
| Battery Problem | Battery Fault | Battery condition poor or battery charger issue | Warning | Inspect battery condition and connections. Contact IASD if needed. |
| CARGADOR SIN CA | CARGADOR SIN CA | Indicador LED amarillo encendido en cualquier estado. | Warning | Comuníquese con un IASD. |
| CHARGER MISSING AC | Charger Missing AC | AC power unavailable for battery charging | Warning | Restore AC power supply or check generator AC output. |
| CHARGER WARNING | Charger Warning | Yellow LED illuminated | Warning | Contact servicing dealer |
| Controller Fault | Control Module Failure | Internal controller fault detected | Shutdown | Contact IASD for assistance |
| CONTROLLER FAULT | Controller Fault | Alarm message listed on controller menu. | Shutdown | Contact an IASD. |
| DESCONEXIÓN AUXILIAR | DESCONEXIÓN AUXILIAR | La unidad no arranca. | Shutdown | Coloque los interruptores de desconexión auxiliar en posición CERRADA (I). |
| DOWNLOAD FAILURE | Download Failure | Firmware download or update failed | Warning | Retry firmware update. Contact authorized service dealer if problem persists. |
| Emerg Stop Shutdwn | Emergency stop shutdown | Optional emergency stop button pressed or emergency stop leads ESS and/or ESN are not connected. | Shutdown | Reset the emergency stop button and clear the fault; check ESS and ESN connections; if no E-stop, connect ESS and ESN together. |
| EMERGENCY STOP | Emergency Stop | Alarm message listed on controller menu. | Shutdown | Check emergency shutdown switch and reset. |
| Engine M/N Invalid Shutdwn | Engine model number invalid shutdown | Generator model number has not been entered. | Shutdown | Enter the generator set model number from the RDC2 keypad, or use SiteTech to select the genset model number. |
| Engine Speed High Shutdwn | Engine speed high shutdown | Engine speed, calculated from AC frequency, was above the high speed setting for 0.3 seconds or more. | Shutdown | Troubleshoot engine operation per the engine service manual. |
| Engine Speed Low Shutdwn | Engine speed low shutdown | Engine speed below the low speed setting for 3 seconds or more after crank disconnect; enclosure thermostat may have tripped. | Shutdown | Troubleshoot engine per engine service manual. Check for high enclosure temperatures and reset the thermostat. |
| EXERCISE SET ERROR | Exercise Set Error | Exercise timer setting error | Warning | |
| Exercise Set Error | Exercise Set Error | Warning; displayed if the exercise period becomes corrupted | Warning | Reset the exercise period to clear |
| Frequency High Shutdwn | Frequency high shutdown | Frequency measured on Phase A exceeded the high frequency setting for 10 seconds, 10 seconds or more after crank disconnect. | Shutdown | Troubleshoot engine operation per the engine service manual. |
| Frequency Low Shutdwn | Frequency low shutdown | Frequency on Phase A was less than the low limit for 10 seconds, or 10 Hz or more less than rated for 60 seconds or more. | Shutdown | Troubleshoot engine per engine service manual. Check for high enclosure temperatures and reset the thermostat. |
| FUEL PRESSURE | Fuel Pressure | Fuel pressure warning | Warning | |
| FUSE PROBLEM | Fuse Problem | Unit will not start in AUTO with utility loss | Warning | Check 7.5amp fuse, replace with ATO 7.5Amp fuse if bad |
| High Engine Temperature | High Engine Temperature | Shutdown alarm, auto reset; 10 second delay on start-up and 1 second delay before shutdown; contacts close if temperature exceeds approximately 144 °C (293 °F) | Shutdown | Auto reset when condition clears and restart engine if a valid start signal is present |
| High Lube Oil Temperature Shutdown | High lube oil temperature shutdown | Oil temperature higher than 325 F (163 C). | Shutdown | See Overheats in the troubleshooting charts in Section 5.14. |
| High Lube Oil Temperature Warning | High lube oil temperature warning | Oil temperature higher than 300 F (149 C). | Warning | See Overheats in the troubleshooting charts in Section 5.14. |
| HIGH TEMPERATURE | High Temperature | Unit shuts down during operation | Shutdown | Check ventilation around generator, intake, exhaust and rear of generator |
| High Temperature | Overheat | Engine operating temperature too high | Shutdown | Inspect ventilation around generator, intake, exhaust, and rear. Ensure no obstructions present. |
| INSPECCIONE LA BATERÍA | INSPECCIONE LA BATERÍA | Indicador LED amarillo encendido en cualquier estado. | Warning | Inspeccione la batería. Presione ENTER para borrar. |
| INSPECT BATTERY | Inspect Battery | Battery inspection reminder | Info | Inspect battery; press ENTER to clear. |
| INTERNAL FAULT | Internal Fault | Internal controller fault | Shutdown | Contact servicing dealer. |
| Internal Fault | Internal Fault | Shutdown alarm; this alarm cannot be cleared | Shutdown | Call service dealer |
| Lo Crank Vlt Warning | Low cranking voltage warning | During cranking, battery voltage measured less than 60% (7.2V or 14.4V) for 6 seconds or more. | Warning | Check cranking battery. |
| Locked Rotor Shutdwn | Locked rotor shutdown | No rotation of the engine or alternator was detected for 3 seconds or more during cranking. | Shutdown | Check cranking circuit. Troubleshoot the engine and alternator. Check alternator connections to controller and auxiliary winding circuit breaker. |
| LOW BATTERY | Low Battery | Yellow LED illuminated | Warning | Clear alarm; check battery via control panel BATTERY MENU; if GOOD contact dealer, else replace battery |
| Low Battery | Battery Voltage Low | Starting battery voltage below acceptable level | Warning | Inspect battery and battery cables. Charge or replace battery if necessary. |
| LOW OIL PRESSURE | Low Oil Pressure | Unit will not start in AUTO with utility loss | Shutdown | Check oil level / add oil per Owners Manual |