Generac GT-999 Engine

The Generac GT-999 is a 1 L 2-cylinder naturally aspirated engine rated at 3600 rpm. It powers generator sets from Generac, including the 15 kW EcoGen, 20 kW Synergy, 8.1 GN and G0070420. It holds 1.8 L (0.5 gal) of oil.

Also known as: GT-999, Generac GT-999

0.999 L
Displacement
2
Cylinders
3600 rpm
Rated speed
1.8 L
Oil capacity

Engine specifications

Oil capacity1.8 L
Displacement0.999 L
Cylinders2
AspirationNaturally aspirated
Rated speed3600 rpm

Common problems

15
  • Unit will not start in AUTO with utility loss
    Cause: Start delay countdown
    Fix: If the start up delay is greater than expected, contact servicing dealer to adjust from 2 to 1500 seconds.
  • Engine cranks but won't start
    Cause: Fuel supply and pressure faulty
    Fix: Test 66 - Check fuel supply and pressure; find and correct cause of no fuel or low pressure
  • Engine cranks but will not start
    Cause: No fuel
    Fix: Replenish fuel / turn on fuel valve.
  • No transfer to standby after utility source failure
    Cause: MLCB (generator disconnect) is OFF (OPEN)
    Fix: Reset generator disconnect to ON (CLOSED).
  • Engine starts hard and runs rough
    Cause: Air cleaner plugged or damaged
    Fix: Check and clean air cleaner.
  • Unit consumes large amounts of oil
    Cause: Excessive engine oil
    Fix: Adjust oil to proper level.
  • Engine will not crank
    Cause: Blown fuse
    Fix: Correct short circuit condition by replacing 7.5 amp fuse in generator control panel. Contact an Independent Authorized Service Dealer (IASD) if fuse continues to blow.
  • Yellow LED illuminated in any state LOW BATTERY
    Fix: Clear alarm. Check the battery using the control panel under the MAIN menu using the BATTERY MENU option. If it states battery is GOOD contact servicing dealer. If it states CHECK BATTERY replace the battery.
  • Engine will not crank when AUTO-OFF-MANUAL switch is set to "MANUAL"
    Cause: Battery faulty
    Fix: Test 61 - Check battery; replace
  • Unit will not start in AUTO with utility loss. NOT ACTIVATED
    Cause: Unit not activated
    Fix: Refer to activation section in owners manual.
  • Generator produces zero voltage or residual voltage (12-20 kW)
    Cause: Main circuit breaker open or failed
    Fix: Reset to "ON" or replace if bad
  • Engine starts hard and runs rough / lacks power / backfires
    Cause: Fuel supply and pressure faulty
    Fix: Test 66 - Check fuel supply and pressure; find and correct cause of no fuel or low pressure
  • No AC output from generator
    Cause: Main line circuit breaker (MLCB) (generator disconnect) is OFF (OPEN)
    Fix: Reset generator disconnect to ON (CLOSED).
  • Unit will not start in AUTO with utility loss — LED RED LOW OIL PRESSURE
    Cause: Check LEDs / screen for alarms
    Fix: Check oil level and add oil as needed. If oil level is correct, contact an IASD
  • Unit will not start in AUTO with utility loss — LED: RED LOW OIL PRESSURE
    Fix: Check oil level and add oil as needed. If oil level is correct, contact an IASD.

Compiled from service & troubleshooting documentation across every generator set that uses the Generac GT-999.

Maintenance schedule

ItemSpecCapacityPart #Interval
Air filter0J84781000 hr Amazon eBay $20.00 NAPA $24.32 KuduParts $15.00
Oil filterAmerican Petroleum Institute (API) Service Class SJ, SL or better070185E500 hr Amazon eBay $30.00 NAPA $9.09 FridayParts $45.99
Battery0H3421S Amazon eBay $283.32
OilSAE 30 (above 32°F), 10W-30 (40°F to -10°F), Synthetic 5W-30 (all temperatures)3.55 liters—500 hr
Spark plugRC12YC1000 hr Amazon eBay $12.90 NAPA $11.52 FridayParts $19.99

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Service intervals

40
ItemActionHoursMonthsNotes
OilChange200 hr24 moFirst service — Change oil after first eight (8) hours of operation
Oil filterChange200 hr24 moFirst service — Change oil filter after first eight (8) hours of operation
Aceite del motorChange25 hrFirst service — Después del período de asentamiento de 25 horas, se recomienda utilizar el aceite 5W-20 propiedad de Generac para uso continuo.
Oil and filterChange25 hrFirst service — After first 25 hours of operation
Valve ClearanceCheck400 hr6 moFirst service — Check/adjust after first 25 hours of operation
Engine governor oil levelCheck50 hrCheck prior to initial use and every 50 operating hours thereafter.
Change oilChange100 hrYearly or 100 hours
Engine oil and filterReplace100 hr12 moFirst service — After first 25 hours; then every 100 hours or 1 year. Cold weather (<4.4°C) or continuous hot (>29.4°C): every 100 hours or 1 year
Oil coolerClean100 hr20 kW models; Yearly or 100 hours
Coolant Level and HosesCheck125 hr12 moSchedule A; also daily if running continuously
Enclosure LouversCheck125 hr12 moSchedule A; also daily if running continuously
Fuel LinesCheck125 hr12 moSchedule A; also daily if running continuously
Lubricating Oil Level and Drain HoseCheck125 hr12 moSchedule A; also daily if running continuously
Lubricating Oil and Oil FilterReplace125 hr12 moFirst service — Schedule A
Radiator for CloggingCheck125 hr12 moSchedule A; also daily if running continuously
Air cleaner serviceClean150 hrYearly or hours shown
ExerciseTest168 hrWeekly exercise
Aceite de motor y filtro de aceiteChange200 hr24 moFirst service — Programa de mantenimiento A
Air cleanerReplace200 hr24 moInspect and replace as necessary; 2Y or 200 hours
Batería (condición, nivel de electrolito y estado de carga)Check200 hr24 moPrograma de mantenimiento A
Battery conditionCheck200 hr24 moSchedule A.
Battery condition and chargeCheck200 hr24 moSchedule A maintenance
Change Air FilterChange200 hr200 hours or 2 years
Change Oil & FilterChange200 hr200 hours or 2 years; 20kW: 100 hours or 2 years
Complete tune-upOther200 hr24 moTo be completed by a dealer; 2Y or 200 hours
Engine oilChange200 hr24 moFirst service — Up to a 2 year/200 hour oil change interval.
Huile à moteur et filtre à huileChange200 hr24 moFirst service — Calendrier A: tous les deux ans ou toutes les 200 heures. Changer l'huile et le filtre après les 25 premières heures. En conditions froides (moins de 4,4 °C/40 °F) ou fonctionnant en continu à plus de 29,4 °C/85 °F, changer annuellement ou toutes les 100 heures.
Inspect Air FilterInspect200 hr200 hours or 2 years
Inspect Spark PlugsInspect200 hr200 hours or 2 years
Oil filterReplace200 hr24 mo200 hours or 2 years, whichever occurs first
Replace filter (oil)Replace200 hr14 kW: Yearly or 200 hours; 20 kW: Yearly or 100 hours
Service Schedule AOther200 hr24 mo200 hours or 2 years
Óleo lubrificante e filtro de óleoChange200 hr24 moFirst service — Trocar após as primeiras 25 horas; Programação A (2 anos ou 200 h); em clima frio (<4,4 °C) ou quente contínuo (>29,4 °C) anualmente ou 100 h
Air cleaner serviceReplace300 hrYearly or hours shown; service more frequently under dusty/dirty conditions
Brushes and collector ringInspect300 hrYearly or 300 hours; authorized distributor/dealer only
Aceite del motor y filtro de aceiteReplace400 hr48 moFirst service — Programa B: cada cuatro años o 400 horas.
Air cleanerClean400 hrClean or replace as necessary; R = Replace as Necessary; 400 hours
Air cleanerInspect400 hr24 moInspect and change; every 400 hours
Air filterReplace400 hr48 moSchedule B maintenance
Battery condition, electrolyte level, and state of chargeInspect400 hr48 moSchedule B

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

60
TypeItemValueUnitCondition
ClearanceBelt deflection3/8 - 5/8in22 Ibs (10 kgf) force midway between water pump and alternator pulleys
ClearanceBelt deflection7.6 - 12.7mm22 Ibs (10 kgf) force midway between water pump and alternator pulleys
ClearanceValve clearance0.002 - 0.004 inch (0.05 - 0.1 mm)inch (mm)engine cool
GapArmature Air Gap0.008-0.012inch
GapBreaker Point Gap0.018-0.022inch
GapFolga da vela de ignição0,020pol
GapFolga da vela de ignição0,040pol
GapFolga da vela de ignição0,508mm
GapFolga da vela de ignição1,02mm
GapIgnition magneto air gap0.008-0.012inch
GapIgnition magneto air gap0.008-0.012 inch (0.20-0.30 mm)gapV-twin engines; fixed non-adjustable on single cylinder
GapIgnition magneto air gap (V-twin)0.008-0.012 inch (0.20-0.30 mm)inch / mm
GapIgnition magneto gap to flywheel (replacement)0.010 inchinch
GapSeparación de electrodos de bujía (11 kW)0.030in (0.76 mm)
GapSeparación de electrodos de bujía (16/20/22 kW)0.040in (1.02 mm)
GapSeparación de electrodos de bujía (9 kW)0.020in (0.508 mm)
GapSeparación de las bujías0.508mm (0.020 pulg.)
GapSeparación de las bujías1.02mm (0.040 pulg.)
GapSpark Plug Gap0.030in (0.76 mm)11 kW (GTH-530)
GapSpark Plug Gap0.031-0.035inch
GapSpark Plug Gap0.040in. (1.02 mm)
GapSpark Plug Gap (1.5L engines, 25/30 kW)0.9mm
GapSpark Plug Gap (2.4L engines, 22/27/36/45 kW)1.07-1.17mm
GapSpark Plug Gap (32/38 kW and 60 kW)0.71mm
GapSpark plug gap0.020in (0.508 mm)
GapSpark plug gap0.020 in (0.508 mm)in (mm)
GapSpark plug gap0.040 in (1.02 mm)in (mm)
GapSpark plug gap0.508mm
GapSpark plug gap0.76mm (0.030 inch)
GapSpark plug gap0.76 mm (0.030 inch)gap410 cc and 530 cc engines
GapSpark plug gap1.02mm (0.040 inch)
GapSpark plug gap1.02 mm (0.040 inch)gap990 cc and 999 cc engines
GapSpark plug gap (10 kW)0.020in (0.508 mm)
GapSpark plug gap (11 kW)0.030in (0.76 mm)
GapSpark plug gap (12/14/16/17/20 kW)1.02mm
GapSpark plug gap (14-24 kW)0.040in (1.02 mm)
GapSpark plug gap (14–24 kW)0.040in (1.02 mm)cold
GapSpark plug gap (16/20/22 kW)0.040in (1.02 mm)
GapSpark plug gap (8/10 kW)0.76mm
GapSpark plug gap (9 kW)0.020in (0.508 mm)
GapSpark plug gap 10kW0.030 inchinch
GapSpark plug gap 13/14/15/16/17kW0.040 inchinch
GapSpark plug gap 20kW0.030 inchinch
GapSpark plug gap 8kW0.030 inchinch
GapÉcartement des électrodes des bougies d'allumage0.508mm (0,020 po)
GapÉcartement des électrodes des bougies d'allumage0.76mm (0,030 po)
GapÉcartement des électrodes des bougies d'allumage1.02mm (0,040 po)
OtherCold Smart Start fixed temperature20 F (-7 C)F (C)22-26 kW
OtherCold Smart Start fixed temperature50 F (10 C)F (C)10-20 kW
OtherCompression Ratio (1.5L)11:1
OtherCompression Ratio (2.4L)9.5:1
OtherCompression Ratio GH-4108.6:1
OtherCompression Ratio GT-5309.5:1
OtherCompression Ratio GT-9909.5:1
OtherCompression Ratio GT-9999.5:1
OtherCompression difference maximum between cylinders25 percentpercent
OtherCompression ratio8.6:1
OtherCompression ratio9.5:1
OtherCylinder leak down acceptable leakage20percent
OtherExercise time length (16-22 kW)5minutes

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Coolant50 percent soft water and 50 percent ethylene glycol base anti-freezelow silicate anti-freeze2.0 U.S. gallonsDo not use chromate base rust inhibitor or high silicate anti-freeze boosters.
Coolant50/50 ethylene glycolGenerac 50/50 ethylene glycol type coolant9.5 litersUse demineralized or distilled water; do not use propylene glycol. Coolant mix 40-60% volume.
Engine oil10W-30API Service Class SJ, SL or betterFor expected operating temperatures between 40 °F and -10 °F
Engine oil30 weight organic oil (factory fill)Units run and tested at factory prior to shipping, no break-in required
Engine oil5W-20Generac proprietary 5W-20 Synthetic (after 30 hour break-in)3.8 litersFactory filled with 5W-20; 60 kW capacity 5.25 quarts (5 liters). Do not use special additives.
Engine oil5W-20 (Generac proprietary)API Service Class SJ, SL, or better1.03 LOil capacity including filter. Use for continuous use after the 25 hour break-in period; specifically formulated for gaseous powered Generac generators. Do not use special additives. Change every year or 100 hours in cold weather (below 40 F) or continuous hot weather (above 85 F).
Engine oil5W-30Aceite orgánico 5W-30 (la unidad se entrega de fábrica llena con este aceite)Compruebe el nivel de aceite y, de ser necesario, añada la cantidad apropiada con la viscosidad correcta. No llene en exceso. Consulte 'Recomendaciones para el aceite de motor' para tipo/viscosidad.
Engine oil5W-30 (factory fill) / 5W-20 GEO (continuous)Generac proprietary gaseous engine oil (GEO)Unit comes filled with 5W-30 organic oil; after 25 hour break-in use 5W-20 GEO
Engine oil5W-30 or 10W-30API Service Class SG, SH, or SJ synthetic oil1.8 L14 kW models; capacity 1.8 L (1.9 qt.)
Engine oilSAE 10W-30RM92-8M0086220U6 / RM92-8M0086221U3
Engine oilSAE 15W-40RM92-8M0096794U3; diesel engines
Engine oilSAE 25W-40RM92-8M0086227U3 / RM92-8M0086224U3
Engine oilSAE 30API Service Class SJ, SL or betterFor expected operating temperatures above 32 °F
Engine oilSAE 30 above 32°F; 10W-30 between 40°F and -10°F; Synthetic 5W-30 10°F and belowAPI Service Class SJ, SL or better; use no special additives1.5 QtsOil capacity including filter
Engine oilSAE 40 above 86 F; SAE 30 32-85 F; SAE 20W below 32 F; SAE 10W-30 all seasonsAPI Service SC, SD, SE or SF3.0 U.S. quartsLiquid-cooled 1.2 liter engine with filter change; 2.5 U.S. quarts without filter change.
Engine oilSAE 5W-30 SyntheticAPI Service Class SJ, SL or betterDo not use special additives
Engine oilSAE 5W-30 sintéticoAPI SJ, SL o mejor1.03 l9 kW; no usar aditivos especiales
Engine oilSAE 5W-30 synthetic; SAE 30 above 60 F; SAE 10W-30 20-59 F; SAE 5W-20/5W-30 below 20 FAPI Service SF, SF/CC, or SF/CD1.5 U.S. quartsAir-cooled V-Twin engine crankcase capacity about 1.5 U.S. quarts. Oil makeup tank capacity about 2.5 U.S. quarts on Model 9067.
Engine oilSAE 5W-30 synthétiqueAPI classe de service SJ, SL ou supérieureHuile SAE 5W-30 synthétique pour toutes les plages de température. N'utilisez aucun additif spécial.
Engine oilSynthetic 5W-30API Service Class SJ, SL or betterFor expected operating temperatures 10 °F and below
Engine oilSynthetic SAE 5W-30API SJ, SL, or better3.75 Quarts (3.55 Liters)For all temperature ranges; do not use special additives
Engine oilTC-W3TC-W32-cycle outboard oil; RM92-858026QB1U6 / RM92-858027QB1U3 / RM92-858037QB1U3
FuelGas natural: contenido de BTU de por lo menos 1000 BTU/ft3 (37,26 MJ/m3). Gas LP: por lo menos 2500 BTU/ft3 (93,15 MJ/m3)250.0 gal (946 l)Tamaño mínimo del tanque de LP es 250 gal (946 l), salvo que los cálculos de la unidad indiquen uno mayor. Solo sistema de extracción de vapor para LP.
FuelGas naturalmínimo 1000 BTU por pie cúbico (37.26 megajulios por metro cúbico)Reducciones típicas de gas natural 10-20 % respecto a LP
FuelGaz naturel37.26 mégajoules par mètre cube (1 000 BTU par pied cube) minimumTeneur en BTU minimale du gaz naturel.
FuelGaz naturel d'au moins 37,26 mégajoules par mètre cube (1 000 BTU par pied cube)NFPA 54
FuelGaz propane liquide (gazeux)93.15 mégajoules par mètre cube (2 500 BTU par pied cube) minimumCapacité de réservoir de gaz propane liquide minimum recommandée de 946 litres (250 gallons).
FuelGaz propane liquide d'au moins 93,15 mégajoules par mètre cube (2 500 BTU par pied cube)NFPA 58 / ICC IFGCRéservoir de gaz propane liquide d'une capacité minimale de 946 litres (250 gallons).
FuelLP (vapor)mínimo 2500 BTU por pie cúbico (93.15 megajulios por metro cúbico)946.0 lSe recomienda tanque de LP de 250 gal. (946 l) de tamaño mínimo si se convierte de NG a LP
FuelLP Gasat least 2,520 Btus per cubic footVapor withdrawal; required pressure 10-12 inches water column

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

80
CodeNameMeaningSeverityAction
1048VSCF OverloadUnit shuts down during operationShutdownAlternator, AVR or wiring damaged. Contact servicing dealer.
1049VSCF OverloadUnit shuts down during operationShutdownGenerator output shorted or severely overloaded; clear overload and restart
1051VSCF High BatteryYellow LED illuminated in any stateWarningVoltage supply to AVR is high; check external battery charger installation or contact servicing dealer
1052VSCF DC OvervoltageUnit shuts down during operationShutdownGenerator temporarily overloaded or output shorted; try restart
1053VSCF Gate FaultUnit shuts down during operation or startingShutdownAVR is damaged; contact servicing dealer
1054VSCF IGBT Overtemp.Unit shuts down during operation or startingShutdownReplace AVR filter, inspect fan, check intake/exhaust, check ambient temperature; contact servicing dealer
1055VSCF Phase ErrorUnit shuts down during startingShutdownCheck stepper motor, linkage, gas pressure; contact servicing dealer if alternator damaged
1056VSCF UndervoltageUnit shuts down during operation or startingShutdownLoad too large, remove and restart; or alternator/AVR damage, contact servicing dealer
1057VSCF OvervoltageUnit shuts down during operation or startingShutdownGenerator overloaded; remove load and restart
1058VSCF DC UndervoltageUnit shuts down during operation or startingShutdownAlternator damage; contact servicing dealer
1059VSCF Field LossUnit shuts down during startingShutdownAlternator damage; contact servicing dealer
1060Big Fan FailureUnit shuts down during operationShutdownAVR electronics exceeded 70°C; replace AVR filter, check intake/exhaust/ambient temp; contact servicing dealer
1061VSCF Field LossUnit shuts down during operationShutdownAlternator damage; contact servicing dealer
1065OverfrequencyUnit shuts down during operationShutdownOverload, RPM sensor failure, or stepper motor problem; contact servicing dealer
1066VSCF Speed mismatchUnit shuts down during operation or startingShutdownFuel pressure loss, large overload, or throttle/engine problem; contact servicing dealer
1070Small fan failureSmall fan failure displayed; continues 80 minutes without fan if running in AUTOWarningCheck fan wiring/mechanical, check AVR filter for blocked air path
1100OvercrankEngine Cranks but will not Start (5 crank attempts)ShutdownProblem 17
1200OverspeedProlonged over specified Hz for 3 secondsShutdownTest 12
1205OverspeedInstantaneous over specified Hz for 0.1 secondShutdownTest 12
1207OverspeedMonitors zero cross timing of AVR; 150 ms of 4500 rpm or higherShutdownTest 64 and Test 60
1300Low Oil PressureOccurred while running; check oil level and pressureShutdownTest 61
1400High TemperatureAir flow impeded; check inlet/outlet for debrisShutdownTest 62
1501RPM SensorTwin Cylinder+Running; RPM sensor lossShutdownTest 50 and Test 64
1505RPM SensorTwin Cylinder+Cranking; RPM sensor lossShutdownIf engine cranks, Test 64. If not crank, Problem 15.
1511RPM SensorSingle Cylinder+Running; RPM sensor lossShutdownTest 50 and Test 64
1515RPM SensorSingle Cylinder+Cranking; RPM sensor lossShutdownIf engine cranks, Test 64. If not crank, Problem 15.
1600UnderspeedUnit is overloaded, slowing engine speed, fuel supply low or throttle control problemShutdownProblem 3, or Test 50, or Test 12
1800OvervoltageProlonged over-voltageShutdown
1900UndervoltageProlonged under-voltage; below 80% for 10+ secondsShutdownPreliminary Output Voltage Test
1901UndervoltageInstantaneous under-voltage due to sudden loss of voltageShutdownPreliminary Output Voltage Test
1902UndervoltageBoth zero crosses missing; faulty excitation winding or zero cross circuitShutdownPreliminary Output Voltage Test
1906UndervoltageSingle zero cross missing; faulty excitation winding or zero cross circuitShutdownPreliminary Output Voltage Test
2099Wiring ErrorMis-wired; customer connection low voltage and high voltage wires crossedShutdownCheck customer connection in generator
2100Overload Remove LoadOverloaded - Default; one or both CTs detecting overloadShutdownRemove Load
2299Undervoltage OverloadUnit was overloaded and attempted to start with large loadShutdownRemove Load
2399Stepper OvercurrentCurrent flow in stepper coil(s) above specificationShutdownTest 12
2400Fuse ProblemMissing or damaged 7.5 amp controller fuseShutdownTest 44
2800Aux ShutdownExternal shut down circuit is openShutdownCheck continuity of harness and operation of switch(es). Repair/replace as needed.
AC Sens Loss ShutdwnLoss of AC sensing shutdownController shut down the generator because there was less than 5% of rated voltage measured on Phase A for 3 seconds, only in AUTO.ShutdownCheck for loose wiring and connections. Check all AC leads. Troubleshoot alternator.
AC Sens Loss WarningLoss of AC sensing warningController measured less than 5% of rated voltage on Phase A for 1 second, 10 seconds after crank disconnect.WarningCheck for loose wiring and connections. Check all AC leads. Troubleshoot alternator.
Aux Input ShutdwnAuxiliary input shutdownDigital input for a custom shutdown (AuxiliaryInputShutdown - PIM) was activated (low).ShutdownCheck customer equipment connected to the PIM module.
AUXILIARY SHUTDOWNAuxiliary ShutdownUnit will not startShutdownSet auxiliary shutdown switch(es) to CLOSED (I); clear alarm
BATERÍA BAJABATERÍA BAJAIndicador LED amarillo encendido en cualquier estado.WarningBorre la alarma. Navegue hasta BATTERY MENU del MAIN MENU para revisar la batería. Si indica GOOD, comuníquese con un IASD. Si indica CHECK BATTERY, reemplace la batería.
Battery CRLow WarningBattery cranking low warningBattery voltage dropped to 11 VDC or less for 30 seconds or more.WarningCheck engine starting battery. Check battery charger DC output voltage from RDC2.
Battery High WarningBattery high warningBattery voltage above the high warning setting for 10 seconds or more.WarningCheck engine starting battery.
Battery Low WarningBattery low warningBattery voltage below the low warning setting for 90 seconds or more.WarningCheck engine starting battery. Check battery charger DC output voltage from RDC2.
BATTERY PROBLEMBattery ProblemYellow LED illuminatedWarningContact servicing dealer
Battery ProblemBattery FaultBattery condition poor or battery charger issueWarningInspect battery condition and connections. Contact IASD if needed.
CARGADOR SIN CACARGADOR SIN CAIndicador LED amarillo encendido en cualquier estado.WarningComuníquese con un IASD.
CHARGER MISSING ACCharger Missing ACAC power unavailable for battery chargingWarningRestore AC power supply or check generator AC output.
CHARGER WARNINGCharger WarningYellow LED illuminatedWarningContact servicing dealer
Controller FaultControl Module FailureInternal controller fault detectedShutdownContact IASD for assistance
CONTROLLER FAULTController FaultAlarm message listed on controller menu.ShutdownContact an IASD.
DESCONEXIÓN AUXILIARDESCONEXIÓN AUXILIARLa unidad no arranca.ShutdownColoque los interruptores de desconexión auxiliar en posición CERRADA (I).
DOWNLOAD FAILUREDownload FailureFirmware download or update failedWarningRetry firmware update. Contact authorized service dealer if problem persists.
Emerg Stop ShutdwnEmergency stop shutdownOptional emergency stop button pressed or emergency stop leads ESS and/or ESN are not connected.ShutdownReset the emergency stop button and clear the fault; check ESS and ESN connections; if no E-stop, connect ESS and ESN together.
EMERGENCY STOPEmergency StopAlarm message listed on controller menu.ShutdownCheck emergency shutdown switch and reset.
Engine M/N Invalid ShutdwnEngine model number invalid shutdownGenerator model number has not been entered.ShutdownEnter the generator set model number from the RDC2 keypad, or use SiteTech to select the genset model number.
Engine Speed High ShutdwnEngine speed high shutdownEngine speed, calculated from AC frequency, was above the high speed setting for 0.3 seconds or more.ShutdownTroubleshoot engine operation per the engine service manual.
Engine Speed Low ShutdwnEngine speed low shutdownEngine speed below the low speed setting for 3 seconds or more after crank disconnect; enclosure thermostat may have tripped.ShutdownTroubleshoot engine per engine service manual. Check for high enclosure temperatures and reset the thermostat.
EXERCISE SET ERRORExercise Set ErrorExercise timer setting errorWarning
Exercise Set ErrorExercise Set ErrorWarning; displayed if the exercise period becomes corruptedWarningReset the exercise period to clear
Frequency High ShutdwnFrequency high shutdownFrequency measured on Phase A exceeded the high frequency setting for 10 seconds, 10 seconds or more after crank disconnect.ShutdownTroubleshoot engine operation per the engine service manual.
Frequency Low ShutdwnFrequency low shutdownFrequency on Phase A was less than the low limit for 10 seconds, or 10 Hz or more less than rated for 60 seconds or more.ShutdownTroubleshoot engine per engine service manual. Check for high enclosure temperatures and reset the thermostat.
FUEL PRESSUREFuel PressureFuel pressure warningWarning
FUSE PROBLEMFuse ProblemUnit will not start in AUTO with utility lossWarningCheck 7.5amp fuse, replace with ATO 7.5Amp fuse if bad
High Engine TemperatureHigh Engine TemperatureShutdown alarm, auto reset; 10 second delay on start-up and 1 second delay before shutdown; contacts close if temperature exceeds approximately 144 °C (293 °F)ShutdownAuto reset when condition clears and restart engine if a valid start signal is present
High Lube Oil Temperature ShutdownHigh lube oil temperature shutdownOil temperature higher than 325 F (163 C).ShutdownSee Overheats in the troubleshooting charts in Section 5.14.
High Lube Oil Temperature WarningHigh lube oil temperature warningOil temperature higher than 300 F (149 C).WarningSee Overheats in the troubleshooting charts in Section 5.14.
HIGH TEMPERATUREHigh TemperatureUnit shuts down during operationShutdownCheck ventilation around generator, intake, exhaust and rear of generator
High TemperatureOverheatEngine operating temperature too highShutdownInspect ventilation around generator, intake, exhaust, and rear. Ensure no obstructions present.
INSPECCIONE LA BATERÍAINSPECCIONE LA BATERÍAIndicador LED amarillo encendido en cualquier estado.WarningInspeccione la batería. Presione ENTER para borrar.
INSPECT BATTERYInspect BatteryBattery inspection reminderInfoInspect battery; press ENTER to clear.
INTERNAL FAULTInternal FaultInternal controller faultShutdownContact servicing dealer.
Internal FaultInternal FaultShutdown alarm; this alarm cannot be clearedShutdownCall service dealer
Lo Crank Vlt WarningLow cranking voltage warningDuring cranking, battery voltage measured less than 60% (7.2V or 14.4V) for 6 seconds or more.WarningCheck cranking battery.
Locked Rotor ShutdwnLocked rotor shutdownNo rotation of the engine or alternator was detected for 3 seconds or more during cranking.ShutdownCheck cranking circuit. Troubleshoot the engine and alternator. Check alternator connections to controller and auxiliary winding circuit breaker.
LOW BATTERYLow BatteryYellow LED illuminatedWarningClear alarm; check battery via control panel BATTERY MENU; if GOOD contact dealer, else replace battery
Low BatteryBattery Voltage LowStarting battery voltage below acceptable levelWarningInspect battery and battery cables. Charge or replace battery if necessary.
LOW OIL PRESSURELow Oil PressureUnit will not start in AUTO with utility lossShutdownCheck oil level / add oil per Owners Manual

Showing the first 80 of 127 codes.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Adjust Magneto Flywheel Gap adjustment

Tools: 0.008-0.012 inch thickness gauge, screwdriver

  1. Rotate flywheel until magnet under module.
  2. Insert 0.008-0.012 inch non-metallic thickness gauge.
  3. Loosen mounting screws.
  4. Let magnet pull magneto against gauge.
  5. Tighten screws.
  6. Remove gauge by rotating flywheel.
Adjust Valve Clearance adjustment

⚠ Allow engine to cool before adjusting valve clearance

⚠ AVR fan operates for 80 minutes after shutdown

Tools: 13mm wrench, 10mm Allen wrench, Feeler gauge

  1. Remove spark plug wires and spark plugs
  2. Remove four screws attaching valve cover, discard gasket
  3. Verify piston at top dead center (TDC) of compression stroke
  4. Loosen rocker jam nut with 13mm wrench
  5. Turn pivot ball stud with 10mm Allen wrench while checking clearance with feeler gauge
  6. Tighten jam nut to 174 in-lbs (19.68 Nm) while holding pivot ball stud
  7. Recheck valve clearance
  8. Install new valve cover gasket and valve cover, torque fasteners to 60 in-lbs (6.8 Nm) in cross pattern
  9. Install spark plugs, torque to 18 ft-lbs (25 Nm)
  10. Connect AVR fan and 4-pin connector
  11. Install AVR filter housing, torque to 50-96 in-lbs (6-11 Nm)
  12. Repeat for other cylinder if necessary
Adjust ignition magneto air gap — V-twin adjustment

Tools: 0.008-0.012 inch thickness gauge

  1. Rotate flywheel until magnet is under module laminations.
  2. Place 0.008-0.012 inch (0.20-0.30mm) thickness gauge between magnet and laminations.
  3. Loosen mounting screws and let magnet pull magneto against gauge.
  4. Tighten both mounting screws.
  5. Rotate flywheel to remove thickness gauge.
  6. Repeat for second magneto.
Adjusting GH-410/GT-530/990/999 Valve Clearance adjustment

⚠ The engine should be cool before checking.

Tools: Feeler gauge, 10mm allen wrench, Socket wrench

  1. Remove spark plug wires and position wires away from plugs.
  2. Remove spark plugs.
  3. Make sure the piston is at Top Dead Center (TDC) of its compression stroke.
  4. Make sure the engine is at 60 to 80 F.
  5. Remove the four screws attaching the valve cover.
  6. Loosen the rocker jam nut.
  7. Use a 10mm allen wrench to turn the pivot ball stud while checking clearance between the rocker arm and valve stem with a feeler gauge.
  8. When valve clearance is correct, hold the pivot ball stud in place and tighten the rocker arm jam nut to 174 in/lbs torque.
  9. Recheck valve clearance.
  10. Install new valve cover gasket and re-attach the valve cover.
  11. Install spark plugs and re-attach the spark plug wire.
  12. On the GT-530 and GT-990/999, repeat the process for the other cylinder.
Adjusting Magneto Flywheel Gap adjustment

⚠ Air gap between ignition magneto and flywheel on single cylinder engines is not adjustable.

Tools: 0.008-0.012 inch thickness gauge

  1. Rotate the flywheel until the magnet is under the module (armature) laminations.
  2. Place a 0.008-0.012 inch (0.20-0.30mm) thickness gauge between flywheel magnet and module laminations.
  3. Loosen the mounting screws and let the magnet pull the magneto down against the thickness gauge.
  4. Tighten both mounting screws.
  5. To remove the thickness gauge, rotate the flywheel.
  6. Repeat the above procedure for the second magneto.
Adjusting Valve Clearance adjustment

⚠ Risk of Burn. Allow the engine to cool before performing the following procedure.

Tools: Feeler gauge, 10 mm wrench, 13 mm wrench, 14 mm wrench, 10 mm hex key

  1. Allow engine to cool before adjusting valve clearance.
  2. Remove spark plug wire(s) away from plugs and remove spark plug(s).
  3. Remove the four screws attaching the valve cover; remove and discard gasket.
  4. Verify piston is at TDC of its compression stroke (both valves closed).
  5. Loosen rocker jam nut using a 10 mm wrench (10 kW) or 13 mm wrench (20–22 kW).
  6. Turn pivot ball stud with a 14 mm wrench (10 kW) or 10 mm hex key (20–22 kW) while checking clearance with a feeler gauge.
  7. Hold pivot ball stud and tighten rocker arm jam nut to specification.
  8. After tightening jam nut, verify valve clearance did not change.
  9. Install new valve cover gasket and valve cover; tighten fasteners in a cross pattern.
  10. Install spark plugs and tighten to 18 ft-lbs (25 Nm).
  11. Attach spark plug wire to spark plug.
  12. Repeat process for other cylinder if equipped.
Adjusting Valve Clearance GH-410/GT-530/990/999 adjustment

⚠ Check valve clearance after first six (6) months of operation.

Tools: 10mm allen wrench, Feeler gauge, Socket and socket wrench

  1. Engine should be cool before checking; clearance 0.002-0.004 inch needs no adjustment.
  2. Remove spark plug wires and spark plugs.
  3. Set piston at Top Dead Center of its compression stroke.
  4. Remove four screws attaching the valve cover.
  5. Loosen rocker jam nut; turn pivot ball stud with 10mm allen wrench.
  6. Set clearance to 0.002-0.004 inch (0.05-0.1 mm).
  7. Hold pivot ball stud and tighten jam nut to 174 in/lbs torque.
  8. Install new valve cover gasket and re-attach valve cover.
Adjusting the Fuel Regulator - 7kW (Natural Gas Only) adjustment

⚠ Do not make any unnecessary adjustments. Factory settings are correct for most applications.

Tools: frequency meter

  1. Start the generator; let it stabilize and warm up at no-load.
  2. Connect a frequency meter across the generator's AC output leads.
  3. Turn the primary adjust screw to obtain a frequency reading.
Ajustar a folga das válvulas adjustment

⚠ Risco de queimaduras. Deixe o motor esfriar antes de executar o procedimento.

Tools: Chave de 10 mm, Chave de 13 mm, Chave de 14 mm, Chave sextavada de 10 mm, Calibrador

  1. Remova os fios das velas de ignição e remova as velas de ignição.
  2. Remova os quatro parafusos que prendem a tampa da válvula; descarte a junta.
  3. Verifique se o pistão está no TDC do seu curso de compressão.
  4. Solte a contraporca do balanceiro (C) com chave de 10 mm ou 13 mm.
  5. Gire o pino de esfera articulada (D) com chave de 14 mm ou sextavada de 10 mm e ajuste a folga.
  6. Aperte a contraporca do braço oscilante e inspecione a folga novamente.
  7. Instale a nova junta e as tampas das válvulas; aperte em padrão transversal.
  8. Instale as velas e aperte a 25 Nm; conecte os fios das velas.
Ajuste de la luz de válvulas adjustment

⚠ Dejar enfriar el motor antes de ajustar.

⚠ Iniciar los cuatro tornillos antes de apretar.

Tools: Calibre de espesores, Llaves de 8/10/13/14 mm, Llave de casquillo, Casquillo grande

  1. Cerrar la válvula de combustible y desconectar la batería.
  2. Retirar cable(s) de bujía y alejarlos.
  3. Retirar la(s) bujía(s).
  4. Llevar el pistón al PMS de la carrera de compresión.
  5. Retirar los cuatro tornillos de la cubierta de válvulas y desechar la junta.
  6. Aflojar la contratuerca del balancín.
  7. Girar el prisionero de bola pivote para ajustar la luz con calibre.
  8. Sostener el prisionero y apretar la contratuerca; verificar y reinstalar con junta nueva.
Ajuste de la separación de la válvula adjustment

⚠ Deje que el motor se enfríe antes del procedimiento.

⚠ Desconecte el cable negativo y luego el positivo de la batería.

⚠ No necesario en unidades 14 o 18 kW con motor de 816 cc.

Tools: Llave de 10 mm, Llave de 13 mm, Llave de 14 mm, Llave hexagonal de 10 mm, Galga de espesores

  1. Retire los hilos de las bujías y las bujías.
  2. Retire los cuatro tornillos de la cubierta de la válvula y deseche la junta.
  3. Verifique que el pistón esté en el PMS de su carrera de compresión.
  4. Suelte la contratuerca del balancín (llave 10 mm en 10 kW, 13 mm en 20 a 24 kW).
  5. Gire el espárrago del pivote (llave 14 mm en 10 kW, hexagonal 10 mm en 20 a 24 kW) ajustando la separación.
  6. Sostenga el espárrago y apriete la contratuerca del balancín.
  7. Inspeccione la separación para verificar que no cambió.
  8. Instale una junta nueva y la cubierta de la válvula; apriete en patrón cruzado.
  9. Instale las bujías y apriete a 25 Nm (18 lb-pie).
  10. Conecte los hilos de las bujías.
Check and Adjust Accessory / Drive Belt adjustment

Tools: Belt deflection gauge

  1. Inspect belt for cracks, fraying, excessive wear or other damage.
  2. Verify belt is free of grease and oil; replace if contaminated.
  3. Using a suitable gauge, apply 22 Ibs (10 kgf) force midway between water pump and alternator pulleys.
  4. Loosen DC alternator tension bracket screw.
  5. Rotate alternator outward to reduce belt deflection.
  6. Rotate inward to increase belt deflection.
  7. Tighten DC alternator tension bracket screw to 17-22 ft-lbs (23-30 Nm).
  8. Recheck belt deflection and repeat steps as necessary.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
0 – c.c. (-)NOIR no 3Fil de mise à la terre normal; obligatoire si jumelé à un commutateur de transfert de gestion intelligente de l'alimentation de Generac.
23BLANCO Núm. 5Cable de señal lógica del control de transferencia
23 (White #5)ETransfer Control Signal Wire
Control system interconnectionsN1, N2, 0, 15B, 23Can be run in same conduit as AC power if length < 35 feet and all wiring rated 600V
Generator control wiring - 1-115 ft (1-35 m)N1, N2, T1, 23, 194No. 18 AWG
Generator control wiring - 116-185 ft (36-56 m)N1, N2, T1, 23, 194No. 16 AWG
Generator control wiring - 186-295 ft (57-89 m)N1, N2, T1, 23, 194No. 14 AWG
Generator control wiring - 296-460 ft (90-140 m)N1, N2, T1, 23, 194No. 12 AWG
Longueur de fil 1 à 35 m (1 à 115 pi)Calibre 18 AWGConducteurs en cuivre seulement.
Longueur de fil 35 à 56 m (115 à 185 pi)Calibre 16 AWGConducteurs en cuivre seulement.
Longueur de fil 56 à 89 m (185 à 295 pi)Calibre 14 AWGConducteurs en cuivre seulement.
Longueur de fil 89 à 140 m (295 à 460 pi)Calibre 12 AWGConducteurs en cuivre seulement.
Neutral for battery chargerWHITE NEU/00Must be connected to keep battery charged whether unit is running or not
1Connect a 2008 and later load center switch to a pre-2008 air-cooled generator: Wire 0 will not be utilized. Remove battery charger from the transfer switch. Connect N1 (BLU) to N1 (YEL), N2 (YEL) to N2 (YEL), 23 (BRN) to 23 (WHT), 194 (ORG) to 15B (RED) using UL approved wire nuts.N1, N2, 23, 194, 15B, 0Battery charger in transfer switch will not be utilized in operation of the generator.
1Connect a pre-2008 load center switch to a current or future air-cooled generator: Wire 0 will not be utilized. Connect N1 (BLU) to N1 (YEL), N2 (YEL) to N2 (YEL), 23 (BRN) to 23 (WHT), 194 (ORG) to 15B (RED) using UL approved wire nuts.N1, N2, 23, 194, 15B, 0Wire 194 changed to 15B on current model air-cooled generators.
1Single-phase leads 1-2, 3-41, 2, 3, 44-lead generator sets are not reconnectable
3Three-phase leads 1-4, 2-5, 3-6, 7-10, 8-11, 9-121-1212-lead generator sets are reconnectable to voltages shown on the generator set specification sheet
0 VCC0NEGRO Núm. 3CC (-) Cable común de conexión a tierra. Requerido si el generador está apareado con un interruptor de transferencia de gestión de alimentación inteligente Generac.
12 V c.c.194 – c.c. (+)ROUGE no 4Pour les commandes de transfert.
12 VCC194ROJO núm. 4CC (+) para los controles de transferencia
12 VDC194 (Red #4)DDC (+) 12 VDC for Transfer Controls
12 VDCDC (+) 12 VDC for transfer controlsRED 194
12 VDCDC (-) common ground wireBLACK 0
12 VDCTransfer control signal wireWHITE 23Required if generator is paired with optional Digital Power Management (DPM) smart technology
1201Battery charger AC input to generator backed-up 120VAC circuit120VAC hot, neutralConnect via wire nuts
120 V c.a.T1BLEU no 3Avec fusible 120 V c.a. pour le chargeur de la batterie; doit être branché pour que la batterie demeure chargée.
120 VACFused 120 VAC for battery chargerBLUE T1Must be connected to keep battery charged whether unit is running or not
120 VACT1 (White #3)BFused 120VAC for Battery Charger
120 VCAT1AZUL Núm. 3Con fusible para el cargador de baterías (debe estar conectado para mantener la batería cargada, esté o no funcionando la unidad)
120/2083WyeVoltage configuration (Figure 4-12)

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What is the oil capacity of the Generac GT-999?

The Generac GT-999 engine has an oil capacity of 1.8 liters.

What is the displacement of the Generac GT-999?

The Generac GT-999 has a displacement of 0.999 liters with 2 cylinders.

Which generators use the Generac GT-999 engine?

The Generac GT-999 powers 4 generator set(s), including Generac 15 kW EcoGen, Generac 20 kW Synergy, Generac 8.1 GN, Generac G0070420.

How often should you change the oil in the Generac GT-999?

The Generac GT-999 oil change interval is every 500 hours.

What is a common problem with the Generac GT-999 engine?

A commonly reported issue on generators using the Generac GT-999 is: Unit will not start in AUTO with utility loss. Cause: Start delay countdown. Fix: If the start up delay is greater than expected, contact servicing dealer to adjust from 2 to 1500 seconds..