Cummins/Onan 2100 Series — Generator/Base Board Isolation Procedure

Testing & diagnosis · Generator and Base board

For the Cummins/Onan 2100 Series, from the Cummins/Onan service manual.

Applies to: Cummins/Onan DGBB, Cummins/Onan DGBC, Cummins/Onan DGCA, Cummins/Onan DGCB, Cummins/Onan DGCG, Cummins/Onan DGDA, Cummins/Onan DGDB, Cummins/Onan DGDK, Cummins/Onan DGFA, Cummins/Onan DGFB, Cummins/Onan DGFC

Before you start

  • This test involves unregulated excitation; disconnect all loads.
  • HAZARDOUS VOLTAGE.

Procedure

  1. Throw line circuit breaker OFF and shut down the set.
  2. Remove control housing side cover; disconnect exciter stator X and XX leads from AC harness.
  3. Prepare to measure output voltage across generator terminals while set runs.
  4. Connect a 12V battery jumper positive (+) to X lead (Field +).
  5. Check polarity again; polarity must be correct.
  6. Start the set and connect battery negative (-) jumper to XX lead.
  7. If rated output voltage or higher and all phases balanced, generator is likely OK.
  8. If unbalanced troubleshoot main stator; if uniformly low troubleshoot exciter and field circuits.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Normal excitation voltage approximately 10 VDC no-load to 40 VDC full-load