Home›Repair guides›Cummins/Onan›Fuel Transfer Pump / Day Tank Control Operation

Cummins/Onan 2100 Series — Fuel Transfer Pump / Day Tank Control Operation

Operation · Day tank control panel

For the Cummins/Onan 2100 Series, from the Cummins/Onan service manual.

Applies to: Cummins/Onan DGBB, Cummins/Onan DGBC, Cummins/Onan DGCA, Cummins/Onan DGCB, Cummins/Onan DGCG, Cummins/Onan DGDA, Cummins/Onan DGDB, Cummins/Onan DGDK, Cummins/Onan DGFA, Cummins/Onan DGFB, Cummins/Onan DGFC

Before you start

  • Continued operation with a HI FUEL fault can lead to fuel spillage.

Procedure

  1. Push control switch to ON for automatic operation; green SYSTEM READY light comes on.
  2. Pump fills tank between pump-on and pump-off float switches; green PUMP ON light indicates pump running.
  3. Push control switch to EMERGENCY RUN (momentary) to pump fuel if control fails.
  4. Press TEST switch to test indicator lights and pump operating circuits.
  5. Press reset button of AC or DC circuit breaker if tripped.

Full service-parts list: Cummins/Onan DGBB →, Cummins/Onan DGBC →, Cummins/Onan DGCA →, Cummins/Onan DGCB →, Cummins/Onan DGDA →, Cummins/Onan DGDB →, Cummins/Onan DGFA →, Cummins/Onan DGFB →, Cummins/Onan DGFC →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Cummins/Onan repair guides →