Home›Kohler›Kohler PM340

Kohler PM340 Generator Set

Kohler PM340 generator set: . Specifications, engine details, filters, oil capacity and 3 document types.

3
Document types

How to read your Kohler serial & model number →

Specifications

Ratings spec sheet not in our library yet — see the documents below.

Service specifications

13
TypeItemValueUnitCondition
OtherAvailable hard drive space for installation5MB
OtherData bits8bitsdefault
OtherDevices per RS-485 local area network128devices
OtherExtended memory8MB
OtherNetwork address range1--128
OtherParityNonedefault
OtherProcessor486 or Pentium, 33 MHz clock speed
OtherRS-232 cable length15.2mfrom PC serial port (50 ft.)
OtherRS-485 cable length1220m4000 ft. total length
OtherSerial COM port baud rate1200, 2400, or 9600baud
OtherSerial COM port baud rate2400, 4800, or 9600baud
OtherStop bits1bitsdefault
OtherSystem ID number maximum digits6digits

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

80
CodeNameMeaningSeverityAction
0No faults presentDecision-Maker 3+ Shutdown Fault CodeInfo
0/0/0/0No errorDecision-Maker 8000 Error List
0/0/1/6Illegal accessRead (write) of the communication object. Object intended only for write (read).
0/0/2/6Comm. Object nonexistentDecision-Maker 8000 Error List
1Master switch not in auto (warning)Decision-Maker 3+ Shutdown Fault CodeWarning
2Master switch errorDecision-Maker 3+ Shutdown Fault CodeShutdown
3OvercrankDecision-Maker 3+ Shutdown Fault CodeShutdown
4Locked rotorDecision-Maker 3+ Shutdown Fault CodeShutdown
5OverspeedDecision-Maker 3+ Shutdown Fault CodeShutdown
6Low oil pressure prealarm (warning)Decision-Maker 3+ Shutdown Fault CodeWarning
7Low oil pressure shutdownDecision-Maker 3+ Shutdown Fault CodeShutdown
8High coolant temperature prealarm (warning)Decision-Maker 3+ Shutdown Fault CodeWarning
9High coolant temperature shutdownDecision-Maker 3+ Shutdown Fault CodeShutdown
10Low coolant temperature (warning)Decision-Maker 3+ Shutdown Fault CodeWarning
11Aux. delayDecision-Maker 3+ Shutdown Fault Code
12Aux. immediateDecision-Maker 3+ Shutdown Fault Code
13MDEC/ADEC yellow alarm (warning)Decision-Maker 3+ Shutdown Fault CodeWarning
14MDEC/ADEC red alarmDecision-Maker 3+ Shutdown Fault CodeShutdown
15Loss of ECM commsDecision-Maker 3+ Shutdown Fault CodeShutdown
16kW OverloadDecision-Maker 340 Alert Code
17Under Frequency WarningDecision-Maker 340 Alert CodeWarning
18High Battery VoltageDecision-Maker 340 Alert Code
19Coolant Temperature Signal LossDecision-Maker 340 Alert Code
20Oil Pressure Signal LossDecision-Maker 340 Alert Code
21Ground Fault DetectedDecision-Maker 340 Alert Code
22Over CurrentDecision-Maker 340 Alert Code
23Engine CooldownDecision-Maker 340 Alert Code
24Time Delay Engine StartDecision-Maker 340 Alert Code
25Generator RunningDecision-Maker 340 Alert Code
26NFPA 110 Common AlarmDecision-Maker 340 Alert Code
27Starting AidDecision-Maker 340 Alert Code
28Low Oil PressureDecision-Maker 340 Alert Code
29High Coolant TemperatureDecision-Maker 340 Alert Code
30OvercrankDecision-Maker 340 Alert Code
31OverspeedDecision-Maker 340 Alert Code
32Emergency StopDecision-Maker 340 Alert Code
33Not In AutoDecision-Maker 340 Alert Code
34System ReadyDecision-Maker 340 Alert Code
35Low Battery VoltageDecision-Maker 340 Alert Code
36Battery Charger FaultDecision-Maker 340 Alert Code
37Low FuelDecision-Maker 340 Alert Code
38High Coolant Temperature WarningDecision-Maker 340 Alert CodeWarning
39Low Oil Pressure WarningDecision-Maker 340 Alert CodeWarning
40Low Coolant TemperatureDecision-Maker 340 Alert Code
41Weak BatteryDecision-Maker 340 Alert Code
42Load Shed UnderfrequencyDecision-Maker 340 Alert Code
43Load Shed Excess kWDecision-Maker 340 Alert Code
44Low AC OutputDecision-Maker 340 Alert Code
45Overvoltage L1-L2Decision-Maker 340 Alert Code
46Overvoltage L2-L3Decision-Maker 340 Alert Code
46-66Digital Input 01-21Decision-Maker 550/6000 System Event Code
47Overvoltage L3-L1Decision-Maker 340 Alert Code
48Overvoltage L1-L0Decision-Maker 340 Alert Code
49Overvoltage L2-L0Decision-Maker 340 Alert Code
50Overvoltage L3-L0Decision-Maker 340 Alert Code
51Undervoltage L1-L2Decision-Maker 340 Alert Code
52Undervoltage L2-L3Decision-Maker 340 Alert Code
53Undervoltage L3-L1Decision-Maker 340 Alert Code
54Undervoltage L1-L0Decision-Maker 340 Alert Code
55Undervoltage L2-L0Decision-Maker 340 Alert Code
56Undervoltage L3-L0Decision-Maker 340 Alert Code
57Master Switch Open (OFF/RESET)Decision-Maker 340 Alert Code
58Power-Down ErrorDecision-Maker 340 Alert Code
59Overfrequency ShutdownDecision-Maker 340 Alert CodeShutdown
74-81Reserved for additional inputDecision-Maker 550/6000 System Event Code
75ECMCommunicationLossDecision-Maker 3000 Event Code 75; ECM FaultShutdown
82Defined Common FaultDecision-Maker 550/6000 System Event Code
99Genset Parameter WarningDecision-Maker 550/6000 System Event CodeWarning
100Genset S/N Mismatch WarningDecision-Maker 550/6000 System Event CodeWarning
101Genset S/N Mismatch ShutdownDecision-Maker 550/6000 System Event CodeShutdown
103Protective Relay OvervoltageDecision-Maker 550/6000 System Event Code
104Protective Relay Under VoltageDecision-Maker 550/6000 System Event Code
105Protective Relay OverfrequencyDecision-Maker 550/6000 System Event Code
106Protective Relay UnderfrequencyDecision-Maker 550/6000 System Event Code
107Protective Relay Reverse PowerDecision-Maker 550/6000 System Event Code
108Protective Relay Over PowerDecision-Maker 550/6000 System Event Code
109Protective Relay Loss of FieldDecision-Maker 550/6000 System Event Code
110Protective Relay Overcurrent VrDecision-Maker 550/6000 System Event Code
111Reverse Power ShutdownDecision-Maker 550/6000 System Event CodeShutdown
112Over Power ShutdownDecision-Maker 550/6000 System Event CodeShutdown

Showing the first 80 of 295 codes.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Analog Input Setup Procedure adjustment
  1. Select Data Window>Add Window.
  2. Select the Decision-Maker 550 controller and Analog Input Setup; click OK.
  3. Select Data Window>Setup or right-click in the window and select Setup.
  4. Type the analog input description and units, 20 characters maximum.
  5. Enter shutdown values, warning values, and time delays within the limits.
  6. Click OK to accept the changes or Cancel to discard them.
Digital Input Setup Procedure adjustment
  1. Choose Add Window>Digital Inputs.
  2. Select Data Window>Setup to enter the setup mode.
  3. Enter the description in the first column, 20 characters maximum.
  4. Click in the Enabled column to toggle between Yes and No.
  5. Enter the Inhibit and Time Delay values in seconds.
  6. Select the function from the drop-down list in the last column.
  7. Click OK to apply the changes or Cancel to discard them.
RDO Setup Procedure adjustment
  1. Select the Relay Driver Output data window.
  2. Choose Data Window>Setup or right-click on the data window and choose Setup.
  3. Double-click on the line for the RDO to define.
  4. Select the item to define as an RDO from the drop-down list.
  5. Click OK to apply the changes or Cancel to discard them.
Trip Point Setup Procedure adjustment
  1. Select the Trip Point data window.
  2. Select Data Window>Setup or right-click in the data window and choose Setup.
  3. Enter the values for the pickup and dropout settings in the boxes.
  4. Set over trip points higher than under trip points.
  5. Maintain at least a 2% difference between dropout and pickup settings.
  6. Click OK to apply the changes or Cancel to discard them.
APM802 Connection Procedure (RS-485 or Ethernet) installation

⚠ Hazardous voltage. Will cause severe injury or death. Disconnect all power sources before opening the enclosure.

Tools: Belden #9841 or equivalent shielded twisted-pair cable

  1. Disable the generator set per safety precautions.
  2. Turn off and disconnect power to all devices in the system.
  3. Connect to RS-485 connections on TB10 or to the RJ45 port labeled Ethernet 3.
  4. Verify that the controller is OFF.
  5. Reconnect the engine starting battery, negative (--) lead last.
  6. Reconnect power to the battery charger, if equipped.
Controller Setup Procedure (Decision-Maker 550) installation
  1. Go to Menu 14—Programming Mode; enter local programming mode.
  2. Enter the controller access code.
  3. Go to Menu 13—Communications.
  4. Select Protocol Modbus0 or Modbus1.
  5. Enter Yes at the Modbus Online Y/N display.
  6. Choose Single or Converter connection type.
  7. Choose RS-232 or RS-485 for the primary port.
  8. Enter the network address (1-246).
  9. Select the same baud rate for all devices.
  10. Choose remote, local, or off programming mode.
  11. Enter the controller access code.
Decision-Maker 3000 Connection Procedure installation

⚠ Accidental starting can cause severe injury or death.

  1. Press the OFF button on the controller.
  2. Disconnect the power to the battery charger, if equipped.
  3. Disconnect the engine starting battery(ies), negative (--) lead first.
  4. Turn off and disconnect power to all devices in the system.
  5. Connect to communication port P21.
  6. Verify that the controller is OFF.
  7. Reconnect the engine starting battery, negative (--) lead last.
  8. Reconnect power to the battery charger, if equipped.
Decision-Maker 3500 Connection Procedure installation

⚠ Accidental starting can cause severe injury or death.

  1. Press the OFF button on the controller.
  2. Disconnect the power to the battery charger, if equipped.
  3. Disconnect the engine starting battery(ies), negative (--) lead first.
  4. Turn off and disconnect power to all devices in the system.
  5. Connect to communication port on TB12 (located in the junction box).
  6. Verify that the controller is OFF.
  7. Reconnect the engine starting battery, negative (--) lead last.
  8. Reconnect power to the battery charger, if equipped.
Device Setup Procedure installation

Tools: Device keypad and display

  1. Enable the local programming mode at the device.
  2. Enter the menu containing the programming mode settings.
  3. Enter the communications settings menu on the device keypad.
  4. For the 550 controller, choose the KBUS protocol.
  5. Choose Yes for the Online setting (KBUS Online for the 550).
  6. Enter the connection type for your connection.
  7. Enter primary port, network address, system ID number, and baud rate.
  8. Set the programming mode for each device to the required settings.
Local Connections Setup Procedure installation
  1. Open the Options menu and verify Configure Mode is not checked.
  2. Select Screen>New Screen.
  3. Click the Local Connection button in the Connection Selection window.
  4. Click the Comm Port Setup button.
  5. Select the COM port (1--16) used to connect to the device.
  6. Enter a baud rate matching all devices at the site.
  7. Leave Data Bits, Parity, and Stop Bits at 8, None, and 1.
  8. Enter the highest network address used, or 0 if no LAN is used, then click OK.
Modbus/Ethernet Converter Setup (MCP 3000) installation
  1. Set IP Address 192.168.255.33.
  2. Set Protocol to Modbus/RTU, Master attached.
  3. Connect the Ethernet port on the MCP PLC to the Ethernet side of the converter.
Modem Setup Procedure installation
  1. Click the Modem Connections button on the Connection Selection dialog box.
  2. Click the Modem Setup button.
  3. Select the modem manufacturer from the list on the left side.
  4. Select the modem model from the list on the right side.
  5. Enter the COM port number for the modem in the Comm Port box.
  6. Click the OK button; the program configures the modem.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
APM802 RS-485 connections on TB10Connector 7 (--) Blue; Connector 8 (+) Green. Shield: do not connect at TB10 or base module; tape to insulate unused end.120 ohm resistor located on the base module.
Decision-Maker 3+ RS-485 connection (TB5)Connect A to --, B to +, and GND to shield.Use Belden #9841 or equivalent cable. Termination resistor X-6058-27 (121 ohms) connect + to -- on last device in network.
Decision-Maker 3500 TB12 RS-485 connectionCOM (+) White; COM (--) Black. Shield: do not connect at TB12 or DEC 3500; connect shield at RSA III P27 connection only.Use Belden #9844 or equivalent cable.
Decision-Maker 550 / 6000 RS-485 connectorConnect + to +, -- to --, GND to shield between devices. Use Belden #9841 or equivalent cable.Termination resistor X-6058-27 (121 ohms) connect + to -- on last device in network.
Decision-Maker 8000 RS-485 connections (customer connection area, bottom panel)Blue, high (H) or positive (+), wire connects to the A terminal; Green, low (L) or negative (--), wire connects to the B terminal. COM terminal also present.Pull up jumper, pull down jumper, and 120 ohm resistor for RS-485 are located on the controller base box.