Kohler — Trip Point Setup Procedure
Adjustments · M340 and M340+ ATS controller trip points
From a Kohler service manual covering: Decision-Maker 550, M340, PM340. Check it applies to your exact model before use.
Browse Kohler generators & specs →
Procedure
- Select the Trip Point data window.
- Select Data Window>Setup or right-click in the data window and choose Setup.
- Enter the values for the pickup and dropout settings in the boxes.
- Set over trip points higher than under trip points.
- Maintain at least a 2% difference between dropout and pickup settings.
- Click OK to apply the changes or Cancel to discard them.
Specs & values
- Normal and Emergency Over/Under Voltage and Frequency (accessory 34-J) must show ENABLED to enter optional settings
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.