Kohler — Trip Point Setup Procedure

Adjustments · M340 and M340+ ATS controller trip points

From a Kohler service manual covering: Decision-Maker 550, M340, PM340. Check it applies to your exact model before use.

Browse Kohler generators & specs →

Procedure

  1. Select the Trip Point data window.
  2. Select Data Window>Setup or right-click in the data window and choose Setup.
  3. Enter the values for the pickup and dropout settings in the boxes.
  4. Set over trip points higher than under trip points.
  5. Maintain at least a 2% difference between dropout and pickup settings.
  6. Click OK to apply the changes or Cancel to discard them.

Specs & values

  • Normal and Emergency Over/Under Voltage and Frequency (accessory 34-J) must show ENABLED to enter optional settings

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.