Kohler — Local Connections Setup Procedure
Installation · Monitor II software local connection
From a Kohler service manual covering: Decision-Maker 550, M340, PM340. Check it applies to your exact model before use.
Browse Kohler generators & specs →
Procedure
- Open the Options menu and verify Configure Mode is not checked.
- Select Screen>New Screen.
- Click the Local Connection button in the Connection Selection window.
- Click the Comm Port Setup button.
- Select the COM port (1--16) used to connect to the device.
- Enter a baud rate matching all devices at the site.
- Leave Data Bits, Parity, and Stop Bits at 8, None, and 1.
- Enter the highest network address used, or 0 if no LAN is used, then click OK.
Specs & values
- Flow Control set to Hardware
- Set DTR line high checked
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.