Kohler — Decision-Maker 3500 Connection Procedure
Installation · Decision-Maker 3500 Controller
From a Kohler service manual covering: 1300REZCK, APM802, Decision-Maker 550, M340, MCP 3000, MPAC 1000, MPAC 1500, PM340. Check it applies to your exact model before use.
Applies to: Kohler 1300REZCK
Before you start
- Accidental starting can cause severe injury or death.
Procedure
- Press the OFF button on the controller.
- Disconnect the power to the battery charger, if equipped.
- Disconnect the engine starting battery(ies), negative (--) lead first.
- Turn off and disconnect power to all devices in the system.
- Connect to communication port on TB12 (located in the junction box).
- Verify that the controller is OFF.
- Reconnect the engine starting battery, negative (--) lead last.
- Reconnect power to the battery charger, if equipped.
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.