Kohler — Device Setup Procedure
Installation · Generator set, ATS, and power monitor controllers
From a Kohler service manual covering: Decision-Maker 550, M340, PM340. Check it applies to your exact model before use.
Browse Kohler generators & specs →
Procedure
- Enable the local programming mode at the device.
- Enter the menu containing the programming mode settings.
- Enter the communications settings menu on the device keypad.
- For the 550 controller, choose the KBUS protocol.
- Choose Yes for the Online setting (KBUS Online for the 550).
- Enter the connection type for your connection.
- Enter primary port, network address, system ID number, and baud rate.
- Set the programming mode for each device to the required settings.
Tools required
- Device keypad and display Amazon
Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.
Specs & values
- Network address 1--128
- System ID maximum six digits
- Enter the same baud rate for all devices on a network
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.