Kohler — Analog Input Setup Procedure
Adjustments · Decision-Maker 550 analog inputs
From a Kohler service manual covering: Decision-Maker 550, M340, PM340. Check it applies to your exact model before use.
Browse Kohler generators & specs →
Procedure
- Select Data Window>Add Window.
- Select the Decision-Maker 550 controller and Analog Input Setup; click OK.
- Select Data Window>Setup or right-click in the window and select Setup.
- Type the analog input description and units, 20 characters maximum.
- Enter shutdown values, warning values, and time delays within the limits.
- Click OK to accept the changes or Cancel to discard them.
Specs & values
- Up to 7 analog inputs
- Description maximum 20 characters
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.