Kohler — Controller Setup Procedure (Decision-Maker 550)
Installation · Decision-Maker 550 Controller
From a Kohler service manual covering: 1300REZCK, APM802, Decision-Maker 550, M340, MCP 3000, MPAC 1000, MPAC 1500, PM340. Check it applies to your exact model before use.
Applies to: Kohler 1300REZCK
Procedure
- Go to Menu 14—Programming Mode; enter local programming mode.
- Enter the controller access code.
- Go to Menu 13—Communications.
- Select Protocol Modbus0 or Modbus1.
- Enter Yes at the Modbus Online Y/N display.
- Choose Single or Converter connection type.
- Choose RS-232 or RS-485 for the primary port.
- Enter the network address (1-246).
- Select the same baud rate for all devices.
- Choose remote, local, or off programming mode.
- Enter the controller access code.
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.