Kohler — RDO Setup Procedure

Adjustments · Relay driver outputs

From a Kohler service manual covering: Decision-Maker 550, M340, PM340. Check it applies to your exact model before use.

Browse Kohler generators & specs →

Procedure

  1. Select the Relay Driver Output data window.
  2. Choose Data Window>Setup or right-click on the data window and choose Setup.
  3. Double-click on the line for the RDO to define.
  4. Select the item to define as an RDO from the drop-down list.
  5. Click OK to apply the changes or Cancel to discard them.

Specs & values

  • Defined Common Fault is the default for RDO 18
  • If NFPA 110 defaults are set, RDOs 1--13 Amazon Amazon Amazon, 19, 22, and 23 cannot be changed

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.