Generac MDE330 Generator Set

The Generac MDE330 is a 290 kW (363 kVA) diesel standby generator set powered by a Perkins 1706J-E93TAG2 engine. It is available at 208/120 V, 240/120 V, 480/277 V and 600/346 V, 3-phase, 60 Hz and rated 917 A. It holds about 30 L (7.9 gal) of oil and 37.8 L (10.0 gal) of coolant, with a maximum ambient rating of 43 °C. Starting uses 2 group-31 batteries rated 950 CCA at 24 V. The set measures 5890×2400×2920 mm (231.9×94.5×115.0 in), weighs about 6248 kg (13774 lb) and produces 75 dBA at 7 m. An integrated tank holds 1593 L (420.8 gal), roughly 26.2 hours of runtime.

290 kW
Standby
9.3 L
Displacement
30.0 L
Oil capacity
3
Document types

How to read your Generac serial & model number →

Typical fuel consumption for 290–295 kW Diesel generators →

Compare with other 290–295 kW Diesel generators →

Service parts for the MDE330

Grouped by system, with how many of each the parts manual calls for.

Electrical

1 required
A0001944388Batterysee priceAmazon

Prices captured from merchant listings; some links are affiliate links. Confirm against your serial number before ordering.

Specifications

Fueldiesel
Frequency60.0 Hz
Standby power290 kW
Standby kVA363
Prime power264 kW
EmissionsTier 4 Final
ControllerDSE8610 MKII, Electronics 8610 MKII, PowerZone Pro Sync
Oil capacity30.0 L
AlternatorLeroy-Somer LSA 46.3 L10
Voltage options208/120 V, 240/120 V, 480/277 V, 600/346 V
Phase3
Rated current917 A
Power factor0.8
Circuit breaker1000 A
Battery group31
Battery cranking950 CCA
Battery voltage24 V
Battery quantity2
Coolant capacity37.8 L
Max ambient43 °C
Dimensions (L×W×H)5890×2400×2920 mm
Dry weight6248 kg
Wet weight7696 kg
Sound level75.0 dBA @ 7 m
Fuel tank1593.0 L
Tank runtime26.2 hr

Engine

Perkins 1706J-E93TAG2
Oil capacity30.0 L
Coolant capacity37.8 L
Displacement9.3 L
AspirationTurbocharged & Aftercooled
Rated speed1800 rpm

Maintenance & consumables

for the Perkins 1706J-E93TAG2
ItemSpecCapacityPart #Interval
Air filterPaper Element Air Filter—
Fuel filterTwo Fuel Filters—
Oil filterSpin-On Cartridge Oil Filter—250 hr
BatteryTwo 12 V, 950 CCA, Wet Cell BatteriesA0001944388 Amazon eBay
BeltDirect Drive Fan—
Coolant—
Coolant filter—
OilEngine Oil30.0 L—
Spark plugN/A—

Service intervals

2
ItemActionHoursMonthsNotes
filterChange500 hrStandard 500-hour oil and filter service interval on both MDE330 and MDE570
oilChange500 hrStandard 500-hour oil and filter service interval on both MDE330 and MDE570

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

35
TypeItemValueUnitCondition
OtherDEF urea concentration31.8-33.2%
OtherFuel fill level below fill neck0.25in (6.4 mm)
OtherFull prime power altitude limit1,640ft (500 m)above that, 2% derate per 820 ft (250 m)
OtherLift pump flow capacity127GPH (480 LPH)
OtherLink board lockout / lug connectionseries 16 taper nose 400 A, 600 Vcam lock plugs rotate one-half turn right
OtherMaximum fill rate, fuel tank fill neck65GPM (246 LPM)nozzles up to 1.5 in. (38 mm)
OtherMaximum pumping height without additional lift pump (3-way fuel valve)1.5m (60 in.)
PressureAir filter minder replacement setpoint20in. H2Oyellow bar reaches red section
PressureAuxiliary fuel lift pump maximum supply pressure100kPa (14.7 PSI)
PressureFuel system low pressure shutdown / leak check-27kPamax restriction at filter head
PressureLow oil pressure threshold5psi (34.5 kPa)within five seconds of restart
PressureMaximum pressure restriction at filter head-27kPamust not be greater
SpeedLow idle speed1,100rpm
SpeedMaximum recommended highway towing speed65mph (105 km/h)
SpeedOperating speed1,800rpm
SpeedPositive air shutoff (PAS) activation speed2,200RPM (73 Hz)engine over speed
SpeedRecommended off-road towing speed10mph (16 km/h) or less
TemperatureDEF freezing point11.5F (-11.3 C)
TemperatureDEF storage temperature - expected life 18 monthsbelow 77F (25 C)
TemperatureDEF storage temperature - expected life 6 months86 to 95F (30 to 35 C)
TemperatureFull prime power ambient temperature limit109F (43 C)above that, 3.5% derate per 41 F (5 C)
TemperatureHeater distribution box thermostat setpoint100F
TemperatureHigh coolant temperature shutdown210F (99 C)
TemperatureOil pan heater thermostatON @270 F / OFF @300 FPhillips & Temro 1000 W, 120 V
TemperatureThermostat setpoint (heater distribution box)@100 F2250 W, 120 V block heater
TorqueConnection lug set screws30ft-lb (41 Nm)
TorqueFuel box positive stud (FB+)40 +/- 5in-lb
TorqueGenerator drive plate bolt44ft-lb (56.9 Nm)
TorqueLink board cover panel bolts10ft-lb (13.6 Nm)
TorqueLink board nuts40ft-lb (54.2 Nm)
TorqueTrailer wheel bearing clear plastic cap25ft-lb
TorqueWheel lug nuts, first pass50-60ft-lb (67-81 Nm)
TorqueWheel lug nuts, second pass150-200ft-lb (203-271 Nm)
TorqueWheel lug nuts, third pass275-325ft-lb (373-441 Nm)
VoltageBuck transformer relay voltage switchover point~137VACmeasured at coil

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
CoolantPerkins ELC or commercial heavy-duty anti-freeze meeting ASTM D6210ASTM D621010.0 galIncludes engine. 50/50 down to 0 F (-18 C); 60/40 for below. ELC service life 6,000 hrs/3 years; ASTM D6210 3,000 hrs/2 years
DefISO 22241-1, urea solution 32.5% (AdBlue / API certified)ISO 22241-156.6 galTwo DEF tanks; usable 49.4 gal (186 L). Freezes below 11.5 F (-11.3 C); store 23-86 F (-5-30 C)
Engine oilSAE viscosity per Figure 4-1 (Lubricant Viscosities)API CK-4; ACEA E9; ECF-37.9 galPerkins Diesel Engine Oil; do not use API FA-4; not approved: CC, CD, CD-2, CF-4, CG-4, CH-4, CI-4
FuelUltra-low-sulfur (15 ppm) diesel fuel421.0 galNo. 1 diesel at/below freezing; No. 2 above freezing; usable tank 381 gal (1,442 L). Do not use home heating oil or bio-diesel
Gear oilSAE 90, SAE 80W-90, or SAE 75W-90Trailer wheel oil bath bearings
GreaseAutomotive grease (jack internal gearing, lubrication points)Lightweight oil applied to jack handle; grease on coupler

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Fine Tuning the Voltage adjustment

⚠ Do not disable or modify connection box door safety switch.

  1. From Home page, press and hold CHECKMARK button to access configuration editor.
  2. Press UP or DOWN to scroll to Editor - Generator Voltage Adjust L-N.
  3. Press and release CHECKMARK so voltage starts to flash.
  4. Press UP or DOWN to change voltage.
  5. Press and release CHECKMARK to set and save the voltage setting.
  6. Press and hold CHECKMARK to exit the editor.
Using Two-Position Link Board adjustment

⚠ Never attempt to open link board panel when engine is running.

  1. Shut down the unit.
  2. Remove fasteners from link board cover panel.
  3. Loosen nuts securing link board plate to panel.
  4. Position link board for desired output voltage.
  5. Tighten nuts 40 ft-lb (54.2 Nm).
  6. Verify toggle switch is in correct position for desired voltage.
  7. Install link board cover panel; tighten bolts to 10 ft-lb (13.6 Nm).
Connecting to Lugs installation

⚠ Electrical backfeed. Use only approved switchgear to isolate generator.

Tools: Hex-wrench

  1. Verify main circuit breaker and battery disconnect switch are OFF.
  2. Route power cables through opening in bottom of door.
  3. Connect cables using a hex-wrench.
  4. Tighten set screws on connection lug to 30 ft-lb (41 Nm).
Checking Generator Drive Plate Torque maintenance

⚠ Accidental Start-up. Disconnect the negative battery cable first.

  1. Disconnect battery.
  2. Remove generator fan guard.
  3. Tighten each drive plate bolt to 44 ft-lb (56.9 Nm).
  4. Install generator fan guard.
  5. Connect battery.
DEF Tank Cleaning maintenance

⚠ Equipment Damage. Clean surfaces contacting DEF with water.

  1. Drain DEF tank into a suitable container.
  2. Flush DEF tank with distilled water.
  3. Fill with new or good DEF.
Fuel System Priming maintenance

⚠ Engine cannot be started while priming function is running.

Tools: Perkins Service Tool

  1. Ensure engine off, controller in STOP mode, battery disconnect ON.
  2. Simultaneously press and hold MANUAL MODE and ALARM MUTE buttons for 3 seconds.
  3. Fuel priming starts and runs for 2 minutes.
  4. Alternatively use the Perkins Service Tool.
Resetting Maintenance Alarms maintenance
  1. With unit shut down, rotate battery disconnect switch to ON.
  2. Press arrow to display the maintenance pages.
  3. Simultaneously press CHECKMARK and O to display Configuration menu.
  4. Scroll to Maintenance group; press RIGHT to display sections and highlight Maintenance.
  5. Press RIGHT to display parameters; highlight the alarm requiring reset.
  6. Press CHECKMARK to select editable parameters; highlight RESET.
  7. Press CHECKMARK to reset the selected maintenance alarm.
  8. Press and hold CHECKMARK five seconds to save changes.
Adding Fuel operation

⚠ Explosion and Fire. Do not overfill fuel tank.

  1. Place unit on a firm, level surface in a well ventilated area.
  2. Verify unit is OFF.
  3. Remove fuel fill cap.
  4. Fill tank with diesel fuel to 0.25 in (6.4 mm) from bottom of fill neck.
  5. Install fuel fill cap.
Manually Starting the Unit operation

⚠ Asphyxiation. Running engines produce carbon monoxide.

⚠ Fire risk. Do not operate indoors.

  1. Switch the battery disconnect switch to ON.
  2. Press the AUTO/MANUAL mode button to start MANUAL mode.
  3. Press the green Engine START (I) button.
  4. If engine fails to start it pauses 15 seconds; three crank cycles total.
  5. If no start, press ENTER to clear fail-to-start alarm and reset controller.
  6. Low-idle switch: IDLE holds 1,100 rpm; RUN idles 10 seconds then 1,800 rpm.
  7. Inspect generator for excessive noise, vibration, and leaks.
  8. Switch main circuit breaker ON, then add loads at receptacle breakers.
Preparing Unit for Towing operation

⚠ Tighten wheel lug nuts after first 50 miles to factory specifications.

Tools: Grease gun

  1. Verify engine is OFF.
  2. Use the tongue jack to raise or lower the trailer onto the hitch.
  3. Lock the hitch coupling and attach the safety chains or cables.
  4. Raise the tongue jack to the highest position.
  5. Lubricate grease fittings on leveling jacks.
  6. Connect trailer wiring harness; verify directional and brake lights.
  7. Verify all doors and hoods are properly latched.
  8. Verify all tires are inflated to the correct pressure.
Shutting Down the Unit operation
  1. Remove all loads by opening all circuit breakers.
  2. Allow engine to run approximately five minutes to cool down.
  3. Press the red engine STOP/RESET (O) button.
  4. Wait for the battery disconnect LED to turn off.
  5. Switch the battery disconnect switch to OFF.
Using An External Battery Charger operation

⚠ Equipment damage. Do not make battery connections in reverse.

Tools: Heavy-duty jumper cables

  1. Connect battery charger to a power source.
  2. Switch the battery disconnect switch to ON.
  3. Connect POSITIVE (+) cable to the battery post connected to the starter (+) post.
  4. Connect NEGATIVE (-) cable to frame grounding lug below the BDS.
  5. Turn charger to correct voltage setting and charging current.
  6. Start the engine; disconnect jumper cables immediately after engine starts.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
208 VAC3Rocker switch UP + link board DOWNTable 3-2
208/120 VAC3T10/11/12 shorted together with buss bar at generator; 208VAC/240VAC shortT1-T9, T10-T12Link board wiring page 1 of 16; drawing A0002490373
240 VAC3Link board L0/T10, T11, T12Drawing A0002490373 page 1
240 VAC3Rocker switch UP + link board UPTable 3-2 Link Board Positions, Voltage Settings
480 VAC3Rocker switch DOWN + link board DOWNTable 3-2
480 VAC / 600 VAC3480VAC, 600VAC shortT1-T9, T10-T12Link board wiring page 1 of 16; T10/11/12 shorted with buss bar
600 VAC3Rocker switch DOWN + link board UPTable 3-2; if unit does not have 600 VAC capability, defaults to 480 VAC

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What is the power rating of the Generac MDE330?

The Generac MDE330 is rated 290 kW standby (363.0 kVA).

What engine is in the Generac MDE330?

The Generac MDE330 is powered by the Perkins 1706J-E93TAG2 engine.

Is the Generac MDE330 diesel or gas?

The Generac MDE330 runs on diesel.

What's the oil capacity on a Generac MDE330?

The Perkins 1706J-E93TAG2 engine in the Generac MDE330 has an oil capacity of 30.0 liters.

What is the coolant capacity of the Generac MDE330?

The Generac MDE330 cooling system holds 37.8 liters (10.0 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.

What is the prime power rating of the Generac MDE330?

The Generac MDE330 is rated 264 kW prime (330 kVA), against 290 kW standby.

How loud is the Generac MDE330?

The Generac MDE330 is rated at 75.0 dBA at 7 m, per the manufacturer specification sheet.

What is the dry weight of the Generac MDE330?

The Generac MDE330 has a dry weight of 6248 kg (13774 lb).

What size fuel tank does the Generac MDE330 have?

The Generac MDE330 has a 1593 liter (421 US gallon) fuel tank, giving about 26.2 hours of runtime.

What voltages is the Generac MDE330 available in?

The Generac MDE330 is offered in 208/120 V, 240/120 V, 480/277 V, 600/346 V, 3-phase.

What battery does the Generac MDE330 use?

The Generac MDE330 uses 2 batteryies, 24 V each, 950 CCA, group 31, per the manufacturer specification sheet.

Which alternator is fitted to the Generac MDE330?

The Generac MDE330 uses a Leroy-Somer LSA 46.3 L10 alternator.

Troubleshooting

4

Symptoms & remedies

SymptomCauseRemedy
Low Load indicator LED is illuminated.Genset has operated at less than 30% capacity for more than 15 minutes.Increase electrical load. If unable to operate genset at more than 30% load, use a smaller generator.
Lug Door Open indicator LED is illuminated.Lug-box door is open.Close lug-box door. If condition remains unresolved, inspect lug-box door safety switch for proper operation.
Emergency Stop indicator LED is illuminated.Emergency Stop switch is active (pushed in).Deactivate (pull out) Emergency Stop switch.
Shutdown indicator LED is illuminated.Resolve shutdown condition.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Parts

12
Part #DescriptionQtySystem
010418Fuel filter1Controller screen Amazon eBay $22.46
014011Equipment damage. Do not attempt to start or operate a unit in need of repair or scheduled maintenance.Battery Amazon eBay
0A9881TRIM VINYL SEAL1Seal Amazon eBay
0C2655GASKET, M8 HINGE2Gasket Amazon eBay
MK1019A02STRIP, LOCK WINDOW (38 INCHES)1Seal Amazon eBay
MK1019A03GASKET, LOCKING, 1.05X.25X.06 (38 INCHES)1Gasket Amazon eBay
014012Link board positions, voltage settingsService part / kit Amazon eBay
14509FIRE EXTINGUISHER - 5 LBS.1Service part / kit Amazon eBay
18900ZCRod, door prop1Service part / kit Amazon eBay
A0001003208ROD CAM 2 POINT LATCH2Service part / kit Amazon eBay
A0001944388DECAL BATTERY DISCONNECT MOBILE1Service part / kit Amazon eBay
A0002424889ST05 ENCL ROOF EXHAUST GRATE1Service part / kit Amazon eBay

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Fuel consumption

RatingLoadL/hgal/h
Prime25%5.822.0
Prime50%38.210.1
Prime75%54.914.5
Prime100%74.619.7
Prime110%22.083.1

Available documents

Reference — MDE-330-and-570-Final-1-2 (Generac)Owner's manual — mde330-owners-manual (Generac)Parts manual — A0001531048 (Generac)Parts manual — mde330 diesel gen ss (Generac)