Generac MDE330 — Using Two-Position Link Board
Adjustments
For the Generac MDE330, from the Generac owner's manual.
Applies to: Generac MDE330, Perkins 1706J-E93TAG2 engine
Before you start
- Never attempt to open link board panel when engine is running.
Procedure
- Shut down the unit.
- Remove fasteners from link board cover panel.
- Loosen nuts securing link board plate to panel.
- Position link board for desired output voltage.
- Tighten nuts 40 ft-lb (54.2 Nm).
- Verify toggle switch is in correct position for desired voltage.
- Install link board cover panel; tighten bolts to 10 ft-lb (13.6 Nm).
Specs & values
- Nuts 40 ft-lb (54.2 Nm)
- Cover bolts 10 ft-lb (13.6 Nm)
Full service-parts list: Generac MDE330 →
Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.