Perkins 1706J-E93TAG2 Engine

The Perkins 1706J-E93TAG2 is a 9.3 L 6-cylinder turbocharged & aftercooled engine rated at 1800 rpm, producing up to 307 kW. It powers generator sets from Generac, including the MDE330. It holds 30 L (7.9 gal) of oil and 37.8 L (10.0 gal) of coolant.

Also known as: Perkins 1706J-E93TAG2

9.3 L
Displacement
6
Cylinders
1800 rpm
Rated speed
307 kW
Gross power

Engine specifications

Oil capacity30.0 L
Coolant capacity37.8 L
Displacement9.3 L
Cylinders6
AspirationTurbocharged & Aftercooled
Rated speed1800 rpm
Gross power307 kW

Common problems

4
  • Shutdown indicator LED is illuminated.
    Fix: Resolve shutdown condition.
  • Lug Door Open indicator LED is illuminated.
    Cause: Lug-box door is open.
    Fix: Close lug-box door. If condition remains unresolved, inspect lug-box door safety switch for proper operation.
  • Low Load indicator LED is illuminated.
    Cause: Genset has operated at less than 30% capacity for more than 15 minutes.
    Fix: Increase electrical load. If unable to operate genset at more than 30% load, use a smaller generator.
  • Emergency Stop indicator LED is illuminated.
    Cause: Emergency Stop switch is active (pushed in).
    Fix: Deactivate (pull out) Emergency Stop switch.

Compiled from service & troubleshooting documentation across every generator set that uses the Perkins 1706J-E93TAG2.

Maintenance schedule

ItemSpecCapacityPart #Interval
Air filterPaper Element Air Filter
Fuel filterTwo Fuel Filters
Oil filterReplace oil filter every 250 hours or as needed250 hr
BatteryTwo 12 V, 950 CCA, Wet Cell BatteriesA0001944388 Amazon eBay
BeltDirect Drive Fan
Coolant
Coolant filter
OilEngine Oil30.0 L
Spark plugN/A

Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.

Service intervals

2
ItemActionHoursMonthsNotes
filterChange500 hrStandard 500-hour oil and filter service interval on both MDE330 and MDE570
oilChange500 hrStandard 500-hour oil and filter service interval on both MDE330 and MDE570

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

35
TypeItemValueUnitCondition
OtherDEF urea concentration31.8-33.2%
OtherFuel fill level below fill neck0.25in (6.4 mm)
OtherFull prime power altitude limit1,640ft (500 m)above that, 2% derate per 820 ft (250 m)
OtherLift pump flow capacity127GPH (480 LPH)
OtherLink board lockout / lug connectionseries 16 taper nose 400 A, 600 Vcam lock plugs rotate one-half turn right
OtherMaximum fill rate, fuel tank fill neck65GPM (246 LPM)nozzles up to 1.5 in. (38 mm)
OtherMaximum pumping height without additional lift pump (3-way fuel valve)1.5m (60 in.)
PressureAir filter minder replacement setpoint20in. H2Oyellow bar reaches red section
PressureAuxiliary fuel lift pump maximum supply pressure100kPa (14.7 PSI)
PressureFuel system low pressure shutdown / leak check-27kPamax restriction at filter head
PressureLow oil pressure threshold5psi (34.5 kPa)within five seconds of restart
PressureMaximum pressure restriction at filter head-27kPamust not be greater
SpeedLow idle speed1,100rpm
SpeedMaximum recommended highway towing speed65mph (105 km/h)
SpeedOperating speed1,800rpm
SpeedPositive air shutoff (PAS) activation speed2,200RPM (73 Hz)engine over speed
SpeedRecommended off-road towing speed10mph (16 km/h) or less
TemperatureDEF freezing point11.5F (-11.3 C)
TemperatureDEF storage temperature - expected life 18 monthsbelow 77F (25 C)
TemperatureDEF storage temperature - expected life 6 months86 to 95F (30 to 35 C)
TemperatureFull prime power ambient temperature limit109F (43 C)above that, 3.5% derate per 41 F (5 C)
TemperatureHeater distribution box thermostat setpoint100F
TemperatureHigh coolant temperature shutdown210F (99 C)
TemperatureOil pan heater thermostatON @270 F / OFF @300 FPhillips & Temro 1000 W, 120 V
TemperatureThermostat setpoint (heater distribution box)@100 F2250 W, 120 V block heater
TorqueConnection lug set screws30ft-lb (41 Nm)
TorqueFuel box positive stud (FB+)40 +/- 5in-lb
TorqueGenerator drive plate bolt44ft-lb (56.9 Nm)
TorqueLink board cover panel bolts10ft-lb (13.6 Nm)
TorqueLink board nuts40ft-lb (54.2 Nm)
TorqueTrailer wheel bearing clear plastic cap25ft-lb
TorqueWheel lug nuts, first pass50-60ft-lb (67-81 Nm)
TorqueWheel lug nuts, second pass150-200ft-lb (203-271 Nm)
TorqueWheel lug nuts, third pass275-325ft-lb (373-441 Nm)
VoltageBuck transformer relay voltage switchover point~137VACmeasured at coil

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
CoolantPerkins ELC or commercial heavy-duty anti-freeze meeting ASTM D6210ASTM D621010.0 galIncludes engine. 50/50 down to 0 F (-18 C); 60/40 for below. ELC service life 6,000 hrs/3 years; ASTM D6210 3,000 hrs/2 years
DefISO 22241-1, urea solution 32.5% (AdBlue / API certified)ISO 22241-156.6 galTwo DEF tanks; usable 49.4 gal (186 L). Freezes below 11.5 F (-11.3 C); store 23-86 F (-5-30 C)
Engine oilSAE viscosity per Figure 4-1 (Lubricant Viscosities)API CK-4; ACEA E9; ECF-37.9 galPerkins Diesel Engine Oil; do not use API FA-4; not approved: CC, CD, CD-2, CF-4, CG-4, CH-4, CI-4
FuelUltra-low-sulfur (15 ppm) diesel fuel421.0 galNo. 1 diesel at/below freezing; No. 2 above freezing; usable tank 381 gal (1,442 L). Do not use home heating oil or bio-diesel
Gear oilSAE 90, SAE 80W-90, or SAE 75W-90Trailer wheel oil bath bearings
GreaseAutomotive grease (jack internal gearing, lubrication points)Lightweight oil applied to jack handle; grease on coupler

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Fine Tuning the Voltage adjustment

⚠ Do not disable or modify connection box door safety switch.

  1. From Home page, press and hold CHECKMARK button to access configuration editor.
  2. Press UP or DOWN to scroll to Editor - Generator Voltage Adjust L-N.
  3. Press and release CHECKMARK so voltage starts to flash.
  4. Press UP or DOWN to change voltage.
  5. Press and release CHECKMARK to set and save the voltage setting.
  6. Press and hold CHECKMARK to exit the editor.
Using Two-Position Link Board adjustment

⚠ Never attempt to open link board panel when engine is running.

  1. Shut down the unit.
  2. Remove fasteners from link board cover panel.
  3. Loosen nuts securing link board plate to panel.
  4. Position link board for desired output voltage.
  5. Tighten nuts 40 ft-lb (54.2 Nm).
  6. Verify toggle switch is in correct position for desired voltage.
  7. Install link board cover panel; tighten bolts to 10 ft-lb (13.6 Nm).
Connecting to Lugs installation

⚠ Electrical backfeed. Use only approved switchgear to isolate generator.

Tools: Hex-wrench

  1. Verify main circuit breaker and battery disconnect switch are OFF.
  2. Route power cables through opening in bottom of door.
  3. Connect cables using a hex-wrench.
  4. Tighten set screws on connection lug to 30 ft-lb (41 Nm).
Checking Generator Drive Plate Torque maintenance

⚠ Accidental Start-up. Disconnect the negative battery cable first.

  1. Disconnect battery.
  2. Remove generator fan guard.
  3. Tighten each drive plate bolt to 44 ft-lb (56.9 Nm).
  4. Install generator fan guard.
  5. Connect battery.
DEF Tank Cleaning maintenance

⚠ Equipment Damage. Clean surfaces contacting DEF with water.

  1. Drain DEF tank into a suitable container.
  2. Flush DEF tank with distilled water.
  3. Fill with new or good DEF.
Fuel System Priming maintenance

⚠ Engine cannot be started while priming function is running.

Tools: Perkins Service Tool

  1. Ensure engine off, controller in STOP mode, battery disconnect ON.
  2. Simultaneously press and hold MANUAL MODE and ALARM MUTE buttons for 3 seconds.
  3. Fuel priming starts and runs for 2 minutes.
  4. Alternatively use the Perkins Service Tool.
Resetting Maintenance Alarms maintenance
  1. With unit shut down, rotate battery disconnect switch to ON.
  2. Press arrow to display the maintenance pages.
  3. Simultaneously press CHECKMARK and O to display Configuration menu.
  4. Scroll to Maintenance group; press RIGHT to display sections and highlight Maintenance.
  5. Press RIGHT to display parameters; highlight the alarm requiring reset.
  6. Press CHECKMARK to select editable parameters; highlight RESET.
  7. Press CHECKMARK to reset the selected maintenance alarm.
  8. Press and hold CHECKMARK five seconds to save changes.
Adding Fuel operation

⚠ Explosion and Fire. Do not overfill fuel tank.

  1. Place unit on a firm, level surface in a well ventilated area.
  2. Verify unit is OFF.
  3. Remove fuel fill cap.
  4. Fill tank with diesel fuel to 0.25 in (6.4 mm) from bottom of fill neck.
  5. Install fuel fill cap.
Manually Starting the Unit operation

⚠ Asphyxiation. Running engines produce carbon monoxide.

⚠ Fire risk. Do not operate indoors.

  1. Switch the battery disconnect switch to ON.
  2. Press the AUTO/MANUAL mode button to start MANUAL mode.
  3. Press the green Engine START (I) button.
  4. If engine fails to start it pauses 15 seconds; three crank cycles total.
  5. If no start, press ENTER to clear fail-to-start alarm and reset controller.
  6. Low-idle switch: IDLE holds 1,100 rpm; RUN idles 10 seconds then 1,800 rpm.
  7. Inspect generator for excessive noise, vibration, and leaks.
  8. Switch main circuit breaker ON, then add loads at receptacle breakers.
Preparing Unit for Towing operation

⚠ Tighten wheel lug nuts after first 50 miles to factory specifications.

Tools: Grease gun

  1. Verify engine is OFF.
  2. Use the tongue jack to raise or lower the trailer onto the hitch.
  3. Lock the hitch coupling and attach the safety chains or cables.
  4. Raise the tongue jack to the highest position.
  5. Lubricate grease fittings on leveling jacks.
  6. Connect trailer wiring harness; verify directional and brake lights.
  7. Verify all doors and hoods are properly latched.
  8. Verify all tires are inflated to the correct pressure.
Shutting Down the Unit operation
  1. Remove all loads by opening all circuit breakers.
  2. Allow engine to run approximately five minutes to cool down.
  3. Press the red engine STOP/RESET (O) button.
  4. Wait for the battery disconnect LED to turn off.
  5. Switch the battery disconnect switch to OFF.
Using An External Battery Charger operation

⚠ Equipment damage. Do not make battery connections in reverse.

Tools: Heavy-duty jumper cables

  1. Connect battery charger to a power source.
  2. Switch the battery disconnect switch to ON.
  3. Connect POSITIVE (+) cable to the battery post connected to the starter (+) post.
  4. Connect NEGATIVE (-) cable to frame grounding lug below the BDS.
  5. Turn charger to correct voltage setting and charging current.
  6. Start the engine; disconnect jumper cables immediately after engine starts.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
208 VAC3Rocker switch UP + link board DOWNTable 3-2
208/120 VAC3T10/11/12 shorted together with buss bar at generator; 208VAC/240VAC shortT1-T9, T10-T12Link board wiring page 1 of 16; drawing A0002490373
240 VAC3Link board L0/T10, T11, T12Drawing A0002490373 page 1
240 VAC3Rocker switch UP + link board UPTable 3-2 Link Board Positions, Voltage Settings
480 VAC3Rocker switch DOWN + link board DOWNTable 3-2
480 VAC / 600 VAC3480VAC, 600VAC shortT1-T9, T10-T12Link board wiring page 1 of 16; T10/11/12 shorted with buss bar
600 VAC3Rocker switch DOWN + link board UPTable 3-2; if unit does not have 600 VAC capability, defaults to 480 VAC

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What is the oil capacity of the Perkins 1706J-E93TAG2?

The Perkins 1706J-E93TAG2 engine has an oil capacity of 30.0 liters.

What is the displacement of the Perkins 1706J-E93TAG2?

The Perkins 1706J-E93TAG2 has a displacement of 9.3 liters with 6 cylinders.

Which generators use the Perkins 1706J-E93TAG2 engine?

The Perkins 1706J-E93TAG2 powers 1 generator set(s), including Generac MDE330.

What is a common problem with the Perkins 1706J-E93TAG2 engine?

A commonly reported issue on generators using the Perkins 1706J-E93TAG2 is: Shutdown indicator LED is illuminated.. Fix: Resolve shutdown condition..