Home›Repair guides›Generac›Shutting Down the Unit

Generac MDE330 — Shutting Down the Unit

Operation · Generator

For the Generac MDE330, from the Generac owner's manual.

Applies to: Generac MDE330, Perkins 1706J-E93TAG2 engine

Procedure

  1. Remove all loads by opening all circuit breakers.
  2. Allow engine to run approximately five minutes to cool down.
  3. Press the red engine STOP/RESET (O) button.
  4. Wait for the battery disconnect LED to turn off.
  5. Switch the battery disconnect switch to OFF.

Specs & values

  • ECU must run 90 seconds after shutdown to purge DEF

Full service-parts list: Generac MDE330 →

Source: Generac owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.