Generac 130 kW PME Generator Set

The Generac 130 kW PME is a 130 kW gaseous standby generator set powered by a Generac 9.0L Gaseous Engine (G26) engine. It is available at 120/240 V, 120/208 V and 277/480 V.

130 kW
Standby
9.0 L
Displacement
1
Document types

How to read your Generac serial & model number →

Specifications

Fuelgaseous
Standby power130 kW
ControllerPower Zone 410 (PZ410)
AlternatorPME
Voltage options120/240 V, 120/208 V, 277/480 V

Engine

Generac 9.0L Gaseous Engine (G26)
Displacement9.0 L

Maintenance & consumables

for the Generac 9.0L Gaseous Engine (G26)
ItemSpecCapacityPart #Interval
Battery—
CoolantFill to the bottom of the filler neck—
Spark plug0.015 in. (0.381 mm)—

Service intervals

2
ItemActionHoursMonthsNotes
BatteryInspect12 mo"Inspect Battery" is a one year auto generated alarm
Exercise (with transfer)Test3 moSet Exercise interval options: never, 3, 6, 9, 12 months

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

60
TypeItemValueUnitCondition
GapSpark plug gap – 9.0L engine0.015in. (0.381 mm)
PressureEngine compression – minimum120psi (8.4 kg/cm2)at 350 rpm
PressureEngine compression – standard160psi (12.1 kg/cm2)at 350 rpm
PressureEngine oil pressure58–90psi (399-620 kPa)running
PressureGaseous fuel pressure at generator fuel inlet – maximum14in. water columnstatic or running
PressureGaseous fuel pressure at generator fuel inlet – minimum5in. water columnstatic or running
PressureLow fuel pressure switch trigger5.2in. water column +/- 0.4
PressureLow oil pressure switch actuation8–12psi
PressureMaximum allowed fuel pressure deviation (no-load to full load)1in. of water column
ResistanceAir/fuel solenoid coil27Ω (+/- 5%)
ResistanceCAN bus resistance pins 744 to 743120ohms
ResistanceCold start fuel solenoid coil6.7Ω (+/- 5%)
ResistanceCoolant sensor resistance at high temperature alarm102ohms (±2.6%)at 246 ºF (119 °C)
ResistanceExcitation (DPE) resistance – 130/150 kW 1-phase 120/2400.3433–0.3989Ω
ResistanceExcitation (DPE) resistance – 130/150 kW 3-phase0.4664–0.5420Ω
ResistanceFlywheel sensor (MPU1)700–1000ohms
ResistanceFuel solenoid (FS1/FS2) across Wire 14 and Wire 010ohms
ResistanceICM pins 744 to 743 resistance138Ohms
ResistanceLow coolant level sensor test resistor1000Ohm, ¼ Watt
ResistanceMain fuel solenoid coil15Ω (+/- 5%)
ResistanceOxygen sensor heater5.4Ω (+/- 5%)
ResistancePower resistance – 130 kW 1-phase 120/240, line-to-line (11-44)0.0070–0.0082Ω
ResistancePower resistance – 130 kW 3-phase 120/208, line-to-line parallel-wye0.0092–0.0107Ω
ResistancePower resistance – 130 kW 3-phase 277/480, line-to-line series-wye0.0464–0.0536Ω
ResistancePower resistance – 150 kW 3-phase 277/480, line-to-line series-wye0.0512–0.0596Ω
ResistanceRotor minimum insulation resistance1.5Megohms
ResistanceRotor resistance2.09–2.31Ω
ResistanceStarter contactor coil4.6Ω (+/- 5%)
ResistanceThrottle motor resistance2.8ohms ± 15%
ResistanceTransfer relay coil110Ω (+/- 5%)
SpeedCrank termination / engine speed sensing600–800rpmcontroller deactivates crank circuit
SpeedLow speed exercise – 1800 rpm units1500rpmlow speed exercise enabled
TemperatureController temperature rating-40 to +70°Cenvironmental chamber life test
TemperatureGenerator drying air temperature maximum185°F (85 °C)
TemperatureHigh coolant temperature alarm246ºF (119 ºC)for 1 second
TemperatureHigh coolant temperature sensor resistance at 70 °F2.6K ohmat 70 °F (21 °C)
TemperatureHigh oil temperature alarm>320°Fwhile engine running, 10 second hold-off
Torque130 kW PME alternator – Screw HHC M12-1.75 x 100 PC8.858 ft-lbs (78 Nm)ft-lbs (Nm)
Torque130 kW PME alternator – Screw HHC M12-1.75 x 45 C8.8 (apply LocTite 242)64 ft-lbs (87 Nm)ft-lbs (Nm)
Torque130 kW PME alternator – Screw HHC M16-2.0 x 45 C8.8 (apply LocTite 242)144 ft-lbs (195 Nm)ft-lbs (Nm)
Torque130 kW PME alternator – Screw HHC M8-1.25 x 115 C8.8222 in-lbs (25 Nm)in-lbs (Nm)
Torque150 kW PME alternator – Screw HHC M10-1.5 x 40 C8.837 ft-lbs (50 Nm)ft-lbs (Nm)
Torque150 kW PME alternator – Screw HHC M14-1.5 X 35 C10.9 (apply LocTite 242)83 ft-lbs (113 Nm)ft-lbs (Nm)
Torque150 kW PME alternator – Screw HHC M16-2.0 x 45 C8.8 (apply LocTite 242)144 ft-lbs (195 Nm)ft-lbs (Nm)
TorqueSpark plug18ft-lbs (24.4 Nm)
VoltageBattery charger charge voltage14.6Vcharge cycle
VoltageBattery charger float voltage14.1Vbelow approximately 40 °F (4 °C)
VoltageBattery charger start voltage12.6Vbattery voltage drops below
VoltageBattery problem threshold>16Vor charge current >600mA at end of 26 hour charge cycle
VoltageBattery voltage – low battery alarm12.1Vbelow for greater than 60 seconds
VoltageBattery voltage – very low battery alarm9.0Vless than, for 60 seconds
VoltageCAN bus Wire 743 to ground2.57VDCsystem active
VoltageCAN bus Wire 744 to ground1.67VDCsystem active
VoltageCoolant sensor circuit open voltage3.3VDC (+/- 0.2)sensor connector disconnected
VoltageCoolant sensor voltage at high temperature alarm2.1VDCat 246 ºF (119 °C)
VoltageGovernor actuator feedback supply (Wires 765 to 767)3VDC ±15%
VoltageGovernor actuator feedback – LMS0.467V ± 10%throttle plate at lower mechanical stop
VoltageGovernor actuator feedback – Rest0.482V ± 10%throttle plate at rest position
VoltageGovernor actuator feedback – UMS3.000V ± 10%throttle plate at upper mechanical stop
VoltageLow oil pressure switch during crank0VDCcranking; rises to ~5 VDC above 10 psi

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
FuelNatural Gas or LP Vapor (gaseous)Minimum 5 in. water column / maximum 14 in. water column at generator fuel inlet connection. No leakage permitted.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

80
CodeNameMeaningSeverityAction
1000Controller FaultThe system has experienced an internal fault.ShutdownContact an IASD.
1001Controller FaultInternal Harness Loop Broken—harness connecting external display board to main board disconnected.ShutdownContact an IASD.
1005Watchdog TimeoutAn internal watchdog timeout occurred.ShutdownController reboots and resumes operation.
1006Controller FaultAn Exception Occurred.ShutdownController reboots and resumes operation.
1100OvercrankEngine/Starter Problem. Default for overcrank alarm.ShutdownReset alarm (set switch to OFF and press ENTER); check engine/start circuit.
1200OverspeedProlonged—Over 72 Hz for three seconds. Possible cause: broken stepper wire.ShutdownCheck stepper wire.
1205OverspeedInstantaneous—Over 75 Hz for one second. Possible cause: broken stepper wire.ShutdownCheck stepper wire.
1207OverspeedInstantaneous—Over 75 Hz for 150 milliseconds based on zero cross to zero cross times.Shutdown
1208OverspeedFrequency (DPE measured) > 20% of target frequency for 5 seconds.Shutdown
1300Low Oil PressureOccurred while running—Default extended alarm for low oil pressure.ShutdownCheck the oil level.
1301Low Oil PressureOccurred while running—Default extended alarm for low oil pressure.WarningCheck the oil level.
134Emissions/Airfuel DTCO2 sensor stuck open/closed. DTC logged in EEPROM.WarningWarning will clear after engine runs with no DTC codes 3 times.
1400High TemperatureAir flow impeded / flow issue. Coolant temp greater than 246 ºF (119 ºC) for 1 second.ShutdownCheck inlet/outlet for debris; check coolant sensor circuit.
1403Engine Coolant TemperatureHigh Coolant Temp—data valid but above normal operating range; least severe level.Warning
1404Engine Coolant TemperatureLow Coolant Temp—data valid but below normal operating range; least severe level.Warning
1405Engine Coolant Temperature Sensor OpenSensor not reporting any change; value stuck at minimum indicating wiring stuck open.Warning
1521RPM SensorMissing pulses during running; no tooth pulses for 75 consecutive milliseconds. Possible causes: starter motor, RPM sensor alignment, low battery.Shutdown
1522RPM SensorAfter crank command, RPM and DPE frequency both read 0. Possible cause - failed motor.Shutdown
1523RPM SensorAfter crank command flywheel teeth count and DPE frequency both read 0. Possible cause - failed motor.Shutdown
1600UnderspeedUnit Overloaded—<83.3% speed (60 Hz) or <66.6% (50 Hz) for 30 seconds. Possible cause: highly inductive loads.ShutdownCheck for overload.
1800OvervoltageVoltage has 5 sec hold-off on startup, then > 130% for 1/5 seconds or >110% for 3 seconds.Shutdown
1801OvervoltageInstantaneous—set by an instantaneous measurement 30% over nominal.Shutdown
1900UndervoltageProlonged—generator voltage below 80% of nominal for 10+ seconds; CPL/CD < 60% for 1/5 sec.Shutdown
1901UndervoltageInstantaneous—generator voltage less than 15V. Hold off time of two seconds.Shutdown
1902UndervoltageBoth Zero Crosses missing—faulty excitation winding, zero cross circuit. Possible cause: loose wiring, field boost hardware failure.Shutdown
1903UndervoltageLittle / No Voltage. Generator voltage less than 120V when undervoltage set. Possible cause: loose connections, broken wire.Shutdown
1904UndervoltageNo Field Current But Have DPE. Possible cause: wire loose, brush failure.Shutdown
1905UndervoltageLow Speed—generator running underspeed for > 30 seconds. Possible cause: fuel supply/control system, engine intake exhaust or mechanical issues.Shutdown
1906UndervoltageSingle Zero Cross missing for greater than 1.5 seconds. Possible cause: field boost hardware failure.Shutdown
1907UndervoltageAfter resuming from a load shed event, still undervoltage because of overload condition.Shutdown
2000Transfer Switch Position ErrorBoth Gen and Utility stuck open.Shutdown
2001Transfer Switch Position ErrorBoth Gen and Utility stuck closed.Shutdown
2002Transfer Switch Position ErrorGen stuck closed / Utility stuck open.Shutdown
2003Transfer Switch Position ErrorGen stuck open / Utility stuck closed.Shutdown
20603 Wire Switch Position Error3 Wire Start NO NC switches are not in desired position.Shutdown
2070Keypad MissingKeypad is missing.Shutdown
2098Wiring ErrorMiswired—Generator Xfer Enabled Output has been miswired.Shutdown
2099Wiring ErrorMiswired—Problem with customer connections.Shutdown
2100Overload Remove LoadOverload CT's output current measured value is above threshold. Possible cause: Overload.ShutdownRemove load.
2109Ground FaultGround + Neutral Current is above threshold.Shutdown
2111Overload OvercurrentCurrent exceeds 150% of rated current.Shutdown
2112Overload OvercurrentI2T based detection—output current above rated limit accumulates to 300% within 11 seconds.Shutdown
2501Governor FaultStuck Open—command and position feedback not matching. Possible causes: governor wire loose, governor module.Shutdown
2502Governor FaultStuck Closed—command and position feedback not matching. Possible cause: governor wire loose, governor module.Shutdown
2670CAN Bus ErrorProblem with CANBus interface; no message received for 1 second.Shutdown
267412/24V Battery Config ErrorDealer Config and the Digital Input for confirming a 12/24 V Battery Type system mismatch.Warning
2675I/O Extender 1 Loss Of CommNo response from I/O Extender for 3 seconds after 30 second hold-off.Warning
2676I/O Extender 2 Loss of CommNo response from I/O Extender for 3 seconds after 30 second hold-off.Warning
2677I/O Extender 3 Loss of CommNo response from I/O Extender for 3 seconds after 30 second hold-off.Warning
2678I/O Extender 4 Loss of CommNo response from I/O Extender for 3 seconds after 30 second hold-off.Warning
2679External Charger FailureExternal Charger enabled and External Charger Fail digital input is True for 3 seconds.Warning
2680Low Fuel LevelFuel level above 10% but lower than 20% for greater than 60 seconds; sensor triggers at 20% fuel remaining.Warning
2681Extremely Low Fuel LevelFuel Level is less than 10%.Shutdown
2682Diesel High Fuel LevelHigh Diesel Fuel Level.Warning
2683External Warning - 1Common warning indicator true for 1 second from configured external source (I/O Extender).Warning
2684External Warning - 2Common warning indicator true for 1 second from configured external source (I/O Extender).Warning
2685Fluid Basin OverfillFluid basin overfill indicator true for 1 second from configured external source.Warning
2686Fluid Basin MissingFluid basin overfill indicator true for 5 seconds from configured external source.Warning
2687MLCB Aux ContactMain Line Circuit Breaker is open or tripped.Warning
2688Enclosure Damper Actuator Aux ContactEnclosure Damper Actuator is stuck.Shutdown
2690Low Fuel PressureLow fuel pressure detected for greater than 60 seconds; switch triggers below 5.2" water column +/- 0.4" (below 0.19 psi).Warning
2710Ruptured TankSystem detected fuel in the outer basin tank.Shutdown
2720Low CoolantLow coolant digital input detected for greater than five seconds.ShutdownCheck coolant level.
2725High Oil TemperatureTriggers when oil temperature is > 320 °F while engine running; 10 second hold-off.Shutdown
2735Low Oil LevelTriggers when oil level is below limit, detected after 60 sec hold-off since power-on.Shutdown
2740Check EngineIf O2 sensor exists and is faulted (stuck open/closed) for 90 seconds. Warning clears after engine runs with no O2 sensor fault for 4 minutes.Warning
2745Lid Open/Theft AlarmLid or door is open.Warning
2746SPI Flash AbuseController wrote to the SPI Flash more than 500 times in less than 4 minutes.Warning
2750Low BatteryBattery voltage below 12.1V for greater than 60 seconds.Warning
2751Very Low BatteryBattery voltage level less than 9.0 for 60 seconds.Shutdown
2760Battery ProblemBattery is >16V or charge current is >600mA at end of 26 hour charge cycle.WarningBattery may be bad.
2770Charger WarningBattery voltage is <12.5V after 26 hour charge cycle.Warning
2780Charger Missing ACDuring charging, AC input to battery charger missing for greater than 5 minutes.Warning
2790SEEPROM AbuseController wrote to the EEPROM more than 500 times in less than 4 minutes.Warning
2793Config EEPROM CRC MismatchConfig computed CRC unequal to stored EEPROM CRC.Warning
2800ESTOP PressedE-Stop button was pressed and shutdown; detected when pressed for greater than 300 ms.Shutdown
2801Auxiliary ShutdownAuxiliary Shutdown button was pressed and shutdown; detected when pressed for greater than 300 ms.Shutdown
2802External Common Alarm - 1Common shutdown alarm indicator true for 1 second from configured I/O Extender module.Shutdown
2803External Common Alarm - 2Common shutdown alarm indicator true for 1 second from configured I/O Extender module.Shutdown
2804External Common Alarm - 3Common shutdown alarm indicator true for 1 second from configured I/O Extender module.Shutdown

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Calibrate Voltage Regulator adjustment

⚠ Do not adjust calibration factor below 990 or above 1040.

Tools: Digital multimeter (DMM)

  1. Set DMM to measure AC voltage at the input side of the breaker.
  2. Open the main line circuit breaker (MLCB).
  3. Use voltage adjust (Evolution) or calibration (Nexus) menu to set unit voltage.
  4. Set AUTO-OFF-MANUAL switch to MANUAL.
  5. While running, use up or down arrows to adjust the calibration setting.
  6. Press ENTER to save the new setting.
Check Engine Compression and Condition diagnostic

Tools: Automotive compression tester

  1. Warm up the engine, if it will start and run.
  2. Shut engine down and remove all spark plugs.
  3. Use an automotive compression tester to check engine compression.
  4. If low, pour a small amount of clean engine oil into the spark plug opening and retest.
Check Flywheel Sensor (MPU1) diagnostic

Tools: 0G41800SRV Breakout Harness, Needle probes, Digital multimeter (DMM)

  1. Disconnect flywheel sensor (MPU1) from the engine harness.
  2. Set DMM to measure resistance between Wire 79 Pin 3 and Wire 79A Pin 2.
  3. Set DMM to measure AC voltage.
  4. Connect breakout harness (P/N 0G41800SRV) in-line with engine control harness.
  5. Set AUTO-OFF-MANUAL switch to MANUAL and measure voltage.
Check Fuel System diagnostic

⚠ Explosion and fire. Fuel and vapors are extremely flammable and explosive. No leakage of fuel is permitted. Keep fire and spark away.

Tools: Water manometer or gauge calibrated in inches of water column, Fuel pressure tester kit

  1. Turn off fuel to primary regulator.
  2. Connect a manometer to test port B.
  3. Turn fuel supply on and record Static Pressure (not running).
  4. Set AUTO-OFF-MANUAL switch to MANUAL and record Running Pressure.
Perform Starter Circuit Voltage Drop Test diagnostic

⚠ Automatic start-up. Disconnect normal power source and render unit inoperable before working on unit.

Tools: Digital multimeter (DMM)

  1. De-energize the T1 circuit.
  2. Set a DMM to measure DC voltage.
  3. Connect red lead to positive battery post, black lead to negative post.
  4. Turn off fuel source and remove Wire 14 from fuel solenoid.
  5. Set controller to MANUAL and measure voltage at test points A, B, and C.
Perform a Load Test on the Battery diagnostic

⚠ Explosion. Batteries emit explosive gases. Always disconnect negative battery cable first to avoid spark.

Tools: Conductance battery load tester

  1. Remove 7.5 amp fuse from the controller.
  2. Remove the T1 fuse from the transfer switch.
  3. Disconnect both negative and positive cables; disconnect negative cable first.
  4. Using a suitable load tester, test the load capability of the battery.
  5. Follow the load tester manufacturer's instructions carefully.
  6. Reconnect both positive and negative cables; reconnect positive cable first.
Test Low Coolant Level Sensor diagnostic

Tools: 1 – 1000 Ohm, ¼ Watt Resistor

  1. Locate and disconnect the low coolant level switch from the radiator.
  2. Install the 1000 ohm resistor between wires 573 and 573A on the engine harness side.
Test Switch Operation diagnostic

⚠ Shutdown switches are not the primary means to shut down the generator under normal conditions. Accidental activation prevents operation during a power outage.

  1. Verify rocker switches are ON.
  2. Press MANUAL key on control panel keypad to start engine.
  3. With engine running, press one shutdown switch OFF; engine should shut down immediately.
  4. Clear alarm and restart engine to verify normal operation.
  5. Repeat for the second switch.
Firmware Update (if required) installation

Tools: USB drive with current firmware

  1. Connect negative battery terminal and tighten nut.
  2. Install 7.5 A fuse and configure install wizard.
  3. With generator controller OFF, enter Edit menu.
  4. Select Update Firmware and press Enter.
  5. Insert USB drive with current firmware and follow prompts.
  6. Press Escape until sub menu screen displays.
  7. Enter dealer menu, select Dealer/Edit, select Auxiliary Stop Setting.
  8. Select Auxiliary Shutdown, then press Escape until submenu displays.
Drying the Generator maintenance

⚠ Never spray water to clean unit. Do not introduce water into generator windings, terminals, or fuel system.

  1. Open the generator main circuit breaker with no electrical loads applied.
  2. Disconnect all wires so the alternator is completely disconnected.
  3. Blow warm, dry air through the generator interior around rotor and stator windings.
  4. Do not exceed 185 °F (85 °C).
  5. Connect stator lead.
  6. Start the generator and let it run for two or three hours.
  7. Shut down the generator and repeat the insulation resistance tests.
Activate Engine Shutdown Functionality operation

⚠ Shutdown mechanism, when activated, requires a mechanical reset.

  1. Verify controller is powered and generator is OFF.
  2. Turn rocker switches ON to verify switches are disengaged.
  3. Turn one rocker switch OFF; controller should display Auxiliary Shutdown.
  4. If alarm appears, turn rocker switch ON and clear alarm.
  5. If no alarm, verify firmware version and wiring, then contact technical support.
  6. Repeat steps 1–3 for second rocker switch.
Modify a Page Setting operation
  1. Verify the desired setting is highlighted on the page and press ENTER.
  2. Press ENTER again to highlight the value if needed.
  3. Use the navigation arrows to change the value.
  4. Press ENTER to confirm, or ESCAPE to cancel.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What size generator is the Generac 130 kW PME?

The Generac 130 kW PME is rated 130 kW standby.

Which engine powers the Generac 130 kW PME?

The Generac 130 kW PME is powered by the Generac 9.0L Gaseous Engine (G26) engine.

What fuel type does the Generac 130 kW PME take?

The Generac 130 kW PME runs on gaseous.

What voltages is the Generac 130 kW PME available in?

The Generac 130 kW PME is offered in 120/240 V, 120/208 V, 277/480 V.

Which alternator is fitted to the Generac 130 kW PME?

The Generac 130 kW PME uses a PME alternator.

Parts

18
Part #DescriptionQtySystem
013001Startup Delay Return Delay Util Loss Volts Util Pickup Volts Dealer Edit: 013002 Crank Pause Time Cooldown Time Warmup Time Run Hours Dealer Edit: 013003 Select Batt. Voltage Reset Maintenance Low Coolant Temp. Select Fuel Dealer Edit: 013004 Enable Theft Alarm Enable Dual Fuel I/O Ext. Config. Preheat Mode Preheat Time Select Wire Setting Dealer Edit: 013067 I/O Ext. 1 Digital Inputs Digital Outputs Dealer Edit: Low Oil Pressure Parameter Group Voltage Code Fuel Level Indicators Dealer Edit: 013006 AMF Mode 1/2 Wire Actuation Ground Fault Dealer Edit: 013007 Reset Controller Factory Reset Update ECU Firmware Save/Load Config. Dealer Edit: 013008ECM / ECU Amazon
013000Dealer MenuService part / kit Amazon
013009Dealer Test: Perform Quiet Test Dealer Test: Gen. Volts A Gen. Volts B Gen. Volts C Dealer Calibrate: Gen. Amps A Gen. Amps B Gen. Amps C Dealer Calibrate: Util. Volt A Util. Volt B Util. Volt CService part / kit Amazon
013010Dealer Test: Perform Quiet Test Dealer Test: Gen. Volts A Gen. Volts B Gen. Volts C Dealer Calibrate: Gen. Amps A Gen. Amps B Gen. Amps C Dealer Calibrate: Util. Volt A Util. Volt B Util. Volt CService part / kit Amazon eBay
013011Dealer Test: Perform Quiet Test Dealer Test: Gen. Volts A Gen. Volts B Gen. Volts C Dealer Calibrate: Gen. Amps A Gen. Amps B Gen. Amps C Dealer Calibrate: Util. Volt A Util. Volt B Util. Volt CService part / kit Amazon
013012Dealer Test: Perform Quiet Test Dealer Test: Gen. Volts A Gen. Volts B Gen. Volts C Dealer Calibrate: Gen. Amps A Gen. Amps B Gen. Amps C Dealer Calibrate: Util. Volt A Util. Volt B Util. Volt CService part / kit Amazon
013013Dealer Test: Perform Quiet Test Dealer Test: Gen. Volts A Gen. Volts B Gen. Volts C Dealer Calibrate: Gen. Amps A Gen. Amps B Gen. Amps C Dealer Calibrate: Util. Volt A Util. Volt B Util. Volt CService part / kit Amazon
013014Status Command Gateway 013016 01: 04/19/21 10:59pm Very Low Battery ECODE 2751 Alarm Log: 013017 01: 04/19/21 10:59pm Stopped With Alarm Run Log: 013018 01: No Log To Display Maintenance Log: 013019 Generator: NOT ACTIVATED Serial No: Run Hours xxx:xxh:m SERVICE UNIT General Info 013020 Battery Condition: CHECK BATTERY General Info 013021Service part / kit Amazon
013015Alarm Log Run Log Maintenance Log General 04/19/21 88F 013016 01: 04/19/21 10:59pm Very Low Battery ECODE 2751 Alarm Log: 013017 01: 04/19/21 10:59pm Stopped With Alarm Run Log: 013018 01: No Log To Display Maintenance Log: 013019 Generator: NOT ACTIVATED Serial No: Run Hours xxx:xxh:m SERVICE UNIT General Info 013020 Battery Condition: CHECK BATTERY General Info 013021Service part / kit Amazon
013016Alarm Log Run Log Maintenance Log General 04/19/21 88F 013016 01: 04/19/21 10:59pm Very Low Battery ECODE 2751 Alarm Log: 013017 01: 04/19/21 10:59pm Stopped With Alarm Run Log: 013018 01: No Log To Display Maintenance Log: 013019 Generator: NOT ACTIVATED Serial No: Run Hours xxx:xxh:m SERVICE UNIT General Info 013020 Battery Condition: CHECK BATTERY General Info 013021Service part / kit Amazon
013017Alarm Log Run Log Maintenance Log General 04/19/21 88F 013016 01: 04/19/21 10:59pm Very Low Battery ECODE 2751 Alarm Log: 013017 01: 04/19/21 10:59pm Stopped With Alarm Run Log: 013018 01: No Log To Display Maintenance Log: 013019 Generator: NOT ACTIVATED Serial No: Run Hours xxx:xxh:m SERVICE UNIT General Info 013020 Battery Condition: CHECK BATTERY General Info 013021Service part / kit Amazon
013018Alarm Log Run Log Maintenance Log General 04/19/21 88F 013016 01: 04/19/21 10:59pm Very Low Battery ECODE 2751 Alarm Log: 013017 01: 04/19/21 10:59pm Stopped With Alarm Run Log: 013018 01: No Log To Display Maintenance Log: 013019 Generator: NOT ACTIVATED Serial No: Run Hours xxx:xxh:m SERVICE UNIT General Info 013020 Battery Condition: CHECK BATTERY General Info 013021Service part / kit Amazon
013019Alarm Log Run Log Maintenance Log General 04/19/21 88F 013016 01: 04/19/21 10:59pm Very Low Battery ECODE 2751 Alarm Log: 013017 01: 04/19/21 10:59pm Stopped With Alarm Run Log: 013018 01: No Log To Display Maintenance Log: 013019 Generator: NOT ACTIVATED Serial No: Run Hours xxx:xxh:m SERVICE UNIT General Info 013020 Battery Condition: CHECK BATTERY General Info 013021Service part / kit Amazon
013020Alarm Log Run Log Maintenance Log General 04/19/21 88F 013016 01: 04/19/21 10:59pm Very Low Battery ECODE 2751 Alarm Log: 013017 01: 04/19/21 10:59pm Stopped With Alarm Run Log: 013018 01: No Log To Display Maintenance Log: 013019 Generator: NOT ACTIVATED Serial No: Run Hours xxx:xxh:m SERVICE UNIT General Info 013020 Battery Condition: CHECK BATTERY General Info 013021Service part / kit Amazon eBay
013021Alarm Log Run Log Maintenance Log General 04/19/21 88F 013016 01: 04/19/21 10:59pm Very Low Battery ECODE 2751 Alarm Log: 013017 01: 04/19/21 10:59pm Stopped With Alarm Run Log: 013018 01: No Log To Display Maintenance Log: 013019 Generator: NOT ACTIVATED Serial No: Run Hours xxx:xxh:m SERVICE UNIT General Info 013020 Battery Condition: CHECK BATTERY General Info 013021Service part / kit Amazon
0G7172Piercing probes (alternative)1Service part / kit Amazon eBay
0J09460SRVflexible pin leads1Service part / kit Amazon eBay $80.00
A0000683522Flexible pin leads for use with AMP connector plugs1Service part / kit Amazon

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Available documents

Service manual — Generac Diagnostic Repair Manual Power Zone A0003109811 (Generac)

This page was generated from the 1 manufacturer document above by automated extraction; every figure shown is copied from one of them. How the data is compiled.