| 1000 | Controller Fault | The system has experienced an internal fault. | Shutdown | Contact an IASD. |
| 1001 | Controller Fault | Internal Harness Loop Broken—harness connecting external display board to main board disconnected. | Shutdown | Contact an IASD. |
| 1005 | Watchdog Timeout | An internal watchdog timeout occurred. | Shutdown | Controller reboots and resumes operation. |
| 1006 | Controller Fault | An Exception Occurred. | Shutdown | Controller reboots and resumes operation. |
| 1100 | Overcrank | Engine/Starter Problem. Default for overcrank alarm. | Shutdown | Reset alarm (set switch to OFF and press ENTER); check engine/start circuit. |
| 1200 | Overspeed | Prolonged—Over 72 Hz for three seconds. Possible cause: broken stepper wire. | Shutdown | Check stepper wire. |
| 1205 | Overspeed | Instantaneous—Over 75 Hz for one second. Possible cause: broken stepper wire. | Shutdown | Check stepper wire. |
| 1207 | Overspeed | Instantaneous—Over 75 Hz for 150 milliseconds based on zero cross to zero cross times. | Shutdown | |
| 1208 | Overspeed | Frequency (DPE measured) > 20% of target frequency for 5 seconds. | Shutdown | |
| 1300 | Low Oil Pressure | Occurred while running—Default extended alarm for low oil pressure. | Shutdown | Check the oil level. |
| 1301 | Low Oil Pressure | Occurred while running—Default extended alarm for low oil pressure. | Warning | Check the oil level. |
| 134 | Emissions/Airfuel DTC | O2 sensor stuck open/closed. DTC logged in EEPROM. | Warning | Warning will clear after engine runs with no DTC codes 3 times. |
| 1400 | High Temperature | Air flow impeded / flow issue. Coolant temp greater than 246 ºF (119 ºC) for 1 second. | Shutdown | Check inlet/outlet for debris; check coolant sensor circuit. |
| 1403 | Engine Coolant Temperature | High Coolant Temp—data valid but above normal operating range; least severe level. | Warning | |
| 1404 | Engine Coolant Temperature | Low Coolant Temp—data valid but below normal operating range; least severe level. | Warning | |
| 1405 | Engine Coolant Temperature Sensor Open | Sensor not reporting any change; value stuck at minimum indicating wiring stuck open. | Warning | |
| 1521 | RPM Sensor | Missing pulses during running; no tooth pulses for 75 consecutive milliseconds. Possible causes: starter motor, RPM sensor alignment, low battery. | Shutdown | |
| 1522 | RPM Sensor | After crank command, RPM and DPE frequency both read 0. Possible cause - failed motor. | Shutdown | |
| 1523 | RPM Sensor | After crank command flywheel teeth count and DPE frequency both read 0. Possible cause - failed motor. | Shutdown | |
| 1600 | Underspeed | Unit Overloaded—<83.3% speed (60 Hz) or <66.6% (50 Hz) for 30 seconds. Possible cause: highly inductive loads. | Shutdown | Check for overload. |
| 1800 | Overvoltage | Voltage has 5 sec hold-off on startup, then > 130% for 1/5 seconds or >110% for 3 seconds. | Shutdown | |
| 1801 | Overvoltage | Instantaneous—set by an instantaneous measurement 30% over nominal. | Shutdown | |
| 1900 | Undervoltage | Prolonged—generator voltage below 80% of nominal for 10+ seconds; CPL/CD < 60% for 1/5 sec. | Shutdown | |
| 1901 | Undervoltage | Instantaneous—generator voltage less than 15V. Hold off time of two seconds. | Shutdown | |
| 1902 | Undervoltage | Both Zero Crosses missing—faulty excitation winding, zero cross circuit. Possible cause: loose wiring, field boost hardware failure. | Shutdown | |
| 1903 | Undervoltage | Little / No Voltage. Generator voltage less than 120V when undervoltage set. Possible cause: loose connections, broken wire. | Shutdown | |
| 1904 | Undervoltage | No Field Current But Have DPE. Possible cause: wire loose, brush failure. | Shutdown | |
| 1905 | Undervoltage | Low Speed—generator running underspeed for > 30 seconds. Possible cause: fuel supply/control system, engine intake exhaust or mechanical issues. | Shutdown | |
| 1906 | Undervoltage | Single Zero Cross missing for greater than 1.5 seconds. Possible cause: field boost hardware failure. | Shutdown | |
| 1907 | Undervoltage | After resuming from a load shed event, still undervoltage because of overload condition. | Shutdown | |
| 2000 | Transfer Switch Position Error | Both Gen and Utility stuck open. | Shutdown | |
| 2001 | Transfer Switch Position Error | Both Gen and Utility stuck closed. | Shutdown | |
| 2002 | Transfer Switch Position Error | Gen stuck closed / Utility stuck open. | Shutdown | |
| 2003 | Transfer Switch Position Error | Gen stuck open / Utility stuck closed. | Shutdown | |
| 2060 | 3 Wire Switch Position Error | 3 Wire Start NO NC switches are not in desired position. | Shutdown | |
| 2070 | Keypad Missing | Keypad is missing. | Shutdown | |
| 2098 | Wiring Error | Miswired—Generator Xfer Enabled Output has been miswired. | Shutdown | |
| 2099 | Wiring Error | Miswired—Problem with customer connections. | Shutdown | |
| 2100 | Overload Remove Load | Overload CT's output current measured value is above threshold. Possible cause: Overload. | Shutdown | Remove load. |
| 2109 | Ground Fault | Ground + Neutral Current is above threshold. | Shutdown | |
| 2111 | Overload Overcurrent | Current exceeds 150% of rated current. | Shutdown | |
| 2112 | Overload Overcurrent | I2T based detection—output current above rated limit accumulates to 300% within 11 seconds. | Shutdown | |
| 2501 | Governor Fault | Stuck Open—command and position feedback not matching. Possible causes: governor wire loose, governor module. | Shutdown | |
| 2502 | Governor Fault | Stuck Closed—command and position feedback not matching. Possible cause: governor wire loose, governor module. | Shutdown | |
| 2670 | CAN Bus Error | Problem with CANBus interface; no message received for 1 second. | Shutdown | |
| 2674 | 12/24V Battery Config Error | Dealer Config and the Digital Input for confirming a 12/24 V Battery Type system mismatch. | Warning | |
| 2675 | I/O Extender 1 Loss Of Comm | No response from I/O Extender for 3 seconds after 30 second hold-off. | Warning | |
| 2676 | I/O Extender 2 Loss of Comm | No response from I/O Extender for 3 seconds after 30 second hold-off. | Warning | |
| 2677 | I/O Extender 3 Loss of Comm | No response from I/O Extender for 3 seconds after 30 second hold-off. | Warning | |
| 2678 | I/O Extender 4 Loss of Comm | No response from I/O Extender for 3 seconds after 30 second hold-off. | Warning | |
| 2679 | External Charger Failure | External Charger enabled and External Charger Fail digital input is True for 3 seconds. | Warning | |
| 2680 | Low Fuel Level | Fuel level above 10% but lower than 20% for greater than 60 seconds; sensor triggers at 20% fuel remaining. | Warning | |
| 2681 | Extremely Low Fuel Level | Fuel Level is less than 10%. | Shutdown | |
| 2682 | Diesel High Fuel Level | High Diesel Fuel Level. | Warning | |
| 2683 | External Warning - 1 | Common warning indicator true for 1 second from configured external source (I/O Extender). | Warning | |
| 2684 | External Warning - 2 | Common warning indicator true for 1 second from configured external source (I/O Extender). | Warning | |
| 2685 | Fluid Basin Overfill | Fluid basin overfill indicator true for 1 second from configured external source. | Warning | |
| 2686 | Fluid Basin Missing | Fluid basin overfill indicator true for 5 seconds from configured external source. | Warning | |
| 2687 | MLCB Aux Contact | Main Line Circuit Breaker is open or tripped. | Warning | |
| 2688 | Enclosure Damper Actuator Aux Contact | Enclosure Damper Actuator is stuck. | Shutdown | |
| 2690 | Low Fuel Pressure | Low fuel pressure detected for greater than 60 seconds; switch triggers below 5.2" water column +/- 0.4" (below 0.19 psi). | Warning | |
| 2710 | Ruptured Tank | System detected fuel in the outer basin tank. | Shutdown | |
| 2720 | Low Coolant | Low coolant digital input detected for greater than five seconds. | Shutdown | Check coolant level. |
| 2725 | High Oil Temperature | Triggers when oil temperature is > 320 °F while engine running; 10 second hold-off. | Shutdown | |
| 2735 | Low Oil Level | Triggers when oil level is below limit, detected after 60 sec hold-off since power-on. | Shutdown | |
| 2740 | Check Engine | If O2 sensor exists and is faulted (stuck open/closed) for 90 seconds. Warning clears after engine runs with no O2 sensor fault for 4 minutes. | Warning | |
| 2745 | Lid Open/Theft Alarm | Lid or door is open. | Warning | |
| 2746 | SPI Flash Abuse | Controller wrote to the SPI Flash more than 500 times in less than 4 minutes. | Warning | |
| 2750 | Low Battery | Battery voltage below 12.1V for greater than 60 seconds. | Warning | |
| 2751 | Very Low Battery | Battery voltage level less than 9.0 for 60 seconds. | Shutdown | |
| 2760 | Battery Problem | Battery is >16V or charge current is >600mA at end of 26 hour charge cycle. | Warning | Battery may be bad. |
| 2770 | Charger Warning | Battery voltage is <12.5V after 26 hour charge cycle. | Warning | |
| 2780 | Charger Missing AC | During charging, AC input to battery charger missing for greater than 5 minutes. | Warning | |
| 2790 | SEEPROM Abuse | Controller wrote to the EEPROM more than 500 times in less than 4 minutes. | Warning | |
| 2793 | Config EEPROM CRC Mismatch | Config computed CRC unequal to stored EEPROM CRC. | Warning | |
| 2800 | ESTOP Pressed | E-Stop button was pressed and shutdown; detected when pressed for greater than 300 ms. | Shutdown | |
| 2801 | Auxiliary Shutdown | Auxiliary Shutdown button was pressed and shutdown; detected when pressed for greater than 300 ms. | Shutdown | |
| 2802 | External Common Alarm - 1 | Common shutdown alarm indicator true for 1 second from configured I/O Extender module. | Shutdown | |
| 2803 | External Common Alarm - 2 | Common shutdown alarm indicator true for 1 second from configured I/O Extender module. | Shutdown | |
| 2804 | External Common Alarm - 3 | Common shutdown alarm indicator true for 1 second from configured I/O Extender module. | Shutdown | |