Generac G9.0L G26 — Perform Starter Circuit Voltage Drop Test

Testing & diagnosis

For the Generac G9.0L G26, from the Generac service manual.

Applies to: Generac 130 kW PME, Generac 150 kW PME, Generac 9.0L Gaseous Engine (G26) engine

Before you start

  • Automatic start-up. Disconnect normal power source and render unit inoperable before working on unit.

Procedure

  1. De-energize the T1 circuit.
  2. Set a DMM to measure DC voltage.
  3. Connect red lead to positive battery post, black lead to negative post.
  4. Turn off fuel source and remove Wire 14 from fuel solenoid.
  5. Set controller to MANUAL and measure voltage at test points A, B, and C.

Tools required

  • Digital multimeter (DMM) Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • 0.00–0.10 VDC across a connection
  • 0.10–0.20 VDC on a ground connection
  • 0.20–0.30 VDC across a wire or cable
  • 0.20–0.30 VDC across a switch or starter contactor
  • 0.40–0.50 VDC across the entire circuit

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.