Generac G9.0L G26 — Activate Engine Shutdown Functionality
Operation · Auxiliary Engine Shutdown Switches
For the Generac G9.0L G26, from the Generac service manual.
Applies to: Generac 130 kW PME, Generac 150 kW PME, Generac 9.0L Gaseous Engine (G26) engine
Before you start
- Shutdown mechanism, when activated, requires a mechanical reset.
Procedure
- Verify controller is powered and generator is OFF.
- Turn rocker switches ON to verify switches are disengaged.
- Turn one rocker switch OFF; controller should display Auxiliary Shutdown.
- If alarm appears, turn rocker switch ON and clear alarm.
- If no alarm, verify firmware version and wiring, then contact technical support.
- Repeat steps 1–3 for second rocker switch.
Specs & values
- Generators 15 kW and larger require two engine shutdown switches.
Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.