Home›Repair guides›Generac›Perform a Load Test on the Battery

Generac G9.0L G26 — Perform a Load Test on the Battery

Testing & diagnosis

For the Generac G9.0L G26, from the Generac service manual.

Applies to: Generac 130 kW PME, Generac 150 kW PME, Generac 9.0L Gaseous Engine (G26) engine

Before you start

  • Explosion. Batteries emit explosive gases. Always disconnect negative battery cable first to avoid spark.

Procedure

  1. Remove 7.5 amp fuse from the controller.
  2. Remove the T1 fuse from the transfer switch.
  3. Disconnect both negative and positive cables; disconnect negative cable first.
  4. Using a suitable load tester, test the load capability of the battery.
  5. Follow the load tester manufacturer's instructions carefully.
  6. Reconnect both positive and negative cables; reconnect positive cable first.

Tools required

  • Conductance battery load tester Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • If DMM indicated less than 10.5 VDC, remove battery and recharge with automotive battery charger.

Source: Generac service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Generac repair guides →