Home›Cummins/Onan›Cummins/Onan lsg-875

Cummins/Onan lsg-875 Generator Set

The Cummins/Onan lsg-875 is a 70 kW (87.5 kVA) Natural Gas standby generator set powered by a Ford LSG-875-6005A engine. It is available at 120/240 V, 120/208 V, 127/220 V, 139/240 V, 240/416 V, 254/440 V, 277/480 V and 347/600 V, 3-phase, 60 Hz and rated 210 A. It holds about 6.2 L (1.6 gal) of oil and 28 L (7.4 gal) of coolant. Starting uses 1 group-SEE battery rated 259 CCA at 12 V. The set measures 1940×880×1940 mm (76.4×34.6×76.4 in) and weighs about 901 kg (1986 lb).

70 kW
Standby
7.5 L
Displacement
6.2 L
Oil capacity
1
Document types

How to read your Cummins/Onan serial & model number →

Compare with other 70–75 kW Natural Gas generators →

Service parts for the lsg-875

Grouped by system, with how many of each the parts manual calls for.

Belts

1 required

Prices captured from merchant listings; some links are affiliate links. Confirm against your serial number before ordering.

Specifications

FuelNatural Gas
Frequency60.0 Hz
Standby power70 kW
Standby kVA87
Prime power60 kW
ControllerUR 15
Oil capacity6.2 L
Alternator15
Voltage options120/240 V, 120/208 V, 127/220 V, 139/240 V, 240/416 V, 254/440 V, 277/480 V, 347/600 V
Phase3
Rated current210 A
Power factor0.8
Circuit breaker15 A
Battery groupSEE
Battery cranking259 CCA
Battery voltage12 V
Battery quantity1
Coolant capacity28 L
Dimensions (L×W×H)1940×880×1940 mm
Dry weight901 kg

Engine

Ford LSG-875-6005A
Oil capacity6.2 L
Coolant capacity28.0 L
Displacement7.5 L
AspirationNatural Gas
Rated speed1800 rpm

Maintenance & consumables

for the Ford LSG-875-6005A
ItemSpecCapacityPart #Interval
Air filter—500 hr
Fuel filter—7 hr
Oil filter—500 hr
Battery—500 hr
BeltM-1702500 hr Amazon eBay
CoolantCoolant28.0 L—
Coolant filter—
Oil6.2—7 hr
Spark plug—1000 hr

Service specifications

52
TypeItemValueUnitCondition
GapSpeed sensor air gap0.020in. (0.508 mm)
GapSpeed sensor air gap0.36- 0.71mm
OtherExciter current delivery time (Fast-Response II)0.05secondschange in load demand
OtherOvervoltage shutdown threshold15% or more over nominalshutdown after approximately one second
PressureBattery equalizer input voltage (24 volts nominal)20- 35volts
PressureBattery equalizer output voltage(input voltage/2) ±2%volts
PressureLow oil pressure shutdown (diesel models)5.5 to 10.5psi (38 to 72 kPa)
PressureLow oil pressure shutdown (gasoline models)11.5 to 18.5psi (79 to 126 kPa)
PressurePressure switch 364345483 ±14kPa
ResistanceCR relay coil resistanceapproximately 125Ohms12-Volt coil; measure between terminals A and B
ResistanceCR relay normally closed contacts (continuity)1-7, 2-8, 3-9
ResistanceExciter armature low resistance reading (faulty if below)under 0.1-0.2ohms
ResistanceGenerator field F3-F4 continuity2-3.75ohms, +5%
ResistancePhoto transistor board reading (covered)300Kohms or highercovered
ResistancePhoto transistor board reading (lit)5Kohms or lowerbright flashlight on board
ResistancePressure sender 264390 value A240 +17/- 15ohms at 0 psi
ResistancePressure sender 264390 value B153 +12/- 15ohms at 25 psi
ResistancePressure sender 264390 value C33.5ohms at 100 psi
ResistancePressure sender 365624 value A241 ±16ohms at 0 psi
ResistancePressure sender 365624 value B152 ±13ohms at 50 psi
ResistancePressure sender 365624 value C33.5ohms at 200 psi
ResistanceTemperature sender 226717 value A123.8 +7.2/- 7.8ohms at 90.6 C (195 F)
ResistanceTemperature sender 226717 value B35.6 +3.4/- 3.6ohms at 137.8 C (280 F)
ResistanceTemperature sender 226919 value A942 ±22ohms at 37.7 C (100 F)
ResistanceTemperature sender 226919 value B35ohms at 115.6 C (240 F)
SpeedGoverned speed (50 Hz models)1500rpm
SpeedGoverned speed (60 Hz models)1800rpm
SpeedGovernor speed droop3 Hz or 90 rpmbetween no load and full load
SpeedNo-load frequency (50 Hz operation)53Hzno load
SpeedNo-load frequency (60 Hz operation)63Hzno load
SpeedOverspeed shutdown70Hz60 Hz models
SpeedOverspeed shutdown (50 Hz sets)60Hz
SpeedOverspeed shutdown (60 Hz sets)70Hz
TemperatureBattery equalizer operating temperature- 40 to 71C (- 40 F to 160 F)
TemperatureLow water temperature start-up thresholdbelow 70°F (21°C)10-second start-up
TemperatureTemperature switch 241308107 ±4C (225 F ±7 F)normally open to close on temp. rise
TemperatureTemperature switch 290090/GM5170516 ±3C (60 F ±5 F)normally open to close on temp. fall
TorqueDrive disc mounting bolts50ft. lbs. (108.48 Nm)
TorqueFR Activator mounting screws20-26in. lbs. (2.8-2.8 Nm)
TorqueFR Activator terminal screws A and F20-25in. lbs. (2.3-2.8 Nm)
TorqueFan bolts260in. lbs. (29.4 Nm)
Voltage1CR relay test voltage at P5 pin 10 to ground0.5 to 1.0voltson-crank cycle
VoltageBattery high volts lamp setpoint (12-volt systems)15volts
VoltageBattery high volts lamp setpoint (24-volt systems)30volts
VoltageBattery low volts lamp setpoint (12-volt systems)10volts
VoltageBattery low volts lamp setpoint (24-volt systems)20volts
VoltageCR relay test voltage at P5 pin 9 to ground0.5 to 1.0voltsGenerator Master Switch in TEST position
VoltageHigh voltage test (exciter armature A1 or A2 to rotor shaft)4,100volts ACnot more than one second
VoltageHigh voltage test (generator field F3 or F4 to shaft)1,100volts ACnot more than one second; do not repeat test
VoltageLED board output at 3B(+) and 5B(-)1-2Volts DCgenerator set running
VoltageSpeed sensor voltage, wire 2 (black) & 16 (white)3- 6volts DC
VoltageSpeed sensor voltage, wire 2 (black) & 24 (red)8- 10volts DC

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Bosch Electronic Governor Stability and Gain Adjustment adjustment
  1. Check that the stability control is in its extreme counterclockwise position.
  2. Start engine. Allow the governor to control the engine. If engine is unstable, turn the gain control counterclockwise until stability is obtained. Adjust speed screw to proper engine speed.
  3. Turn the gain control clockwise until the engine becomes just unstable. Back the gain control slightly counterclockwise until the engine is again stable.
  4. Turn the stability control clockwise until the engine becomes just unstable. Back the stability control slightly counterclockwise until the engine is again stable.
Diesel Mechanical Governor Frequency Adjustment adjustment

Tools: Frequency meter

  1. Start the generator set, observe the frequency meter.
  2. Loosen the fuel pump high speed screw locknut to make the adjustments.
  3. To increase or decrease the frequency (at no load), rotate the screw clockwise or counterclockwise respectively.
  4. Tighten the locknut.
  5. Loaded droop frequency may alternately be adjusted to the operating frequency at full load.
Gas/Gasoline Mechanical Governor Speed and Sensitivity Adjustment adjustment

Tools: Hand tachometer, Frequency meter

  1. With the set running at full or rated load, check speed with hand tachometer or frequency meter.
  2. Loosen locking nut on speed adjusting screw; turn clockwise to increase speed (and frequency) or counterclockwise to decrease; lock nut at new setting.
  3. For sensitivity, loosen the nut at bottom of adjusting eyebolt and tighten the top nut to draw the head of the eyebolt closer to the governor arm pivot point (more sensitive).
  4. To make governor control less sensitive, loosen the top nut and tighten the bottom nut to move the head away from the pivot point.
  5. Recheck speed after sensitivity adjustment since changing this will also affect speed.
Generator Frequency Change (60 Hz to 50 Hz) adjustment

Tools: Frequency meter

  1. On Microcomputer equipped generators, snip the jumper indicated in Figure A1 to convert from 60 Hz to 50 Hz.
  2. Check frequency meter for a no load reading of 63 Hz for 60 Hz operation and 53 Hz for 50 Hz operation.
  3. If equipped with isochronous governor, check for 60 and 50 Hz operation at no load.
  4. If no frequency meter, connect meter across VO and V7 on control board terminal strip (set must not be running while making connection).
High and Low Battery Voltage Indicator Adjustment adjustment

Tools: DC power supply

  1. Move Generator Master Switch to AUTO position. SYSTEM READY lamp should go on.
  2. Rotate potentiometers R42 (High Batt. Volts) and R25 (Low Batt. Volts) fully counterclockwise.
  3. Set DC power supply at 10 volts (20 volts for 24-volt units). Slowly rotate pot R25 clockwise until BAT. LOW VOLTS lamp lights.
  4. Set DC power supply at 15 volts (30 volts for 24-volt units). Slowly rotate pot R42 clockwise until BAT. HIGH VOLTS lamp lights.
  5. Set DC power supply between 10 to 15 volts (20 to 30 volts for 24-volt units). SYSTEM READY lamp should be on.
  6. Seal pots after settings have been established.
Overfrequency Adjustment (Over/Underfrequency Relay, Decision-Maker 3+) adjustment
  1. Turn the overfrequency adjustment potentiometer fully clockwise (CW).
  2. Place master switch in RUN to start the generator set.
  3. Adjust governor per engine operation manual, engine service manual, or governor section of this manual.
  4. Slowly turn overfrequency potentiometer counterclockwise (CCW) until the LED starts flashing; after about 10 seconds the set shuts down on auxiliary fault.
  5. Place master switch to OFF/RESET to reset the controller.
  6. Place master switch to RUN to start the generator set.
  7. Readjust the governor to the desired frequency as required.
  8. Place master switch to OFF/RESET to stop the generator set.
Overvoltage Feature Testing and Adjustment (Decision-Maker 3+) adjustment

⚠ Hazardous voltage. Moving parts. Will cause severe injury or death. Operate the generator set only when all guards and electrical enclosures are in place.

⚠ Disconnecting the electrical load. Hazardous voltage will cause severe injury or death.

  1. Disconnect generator set from load by opening line circuit breaker or disconnecting and taping output leads.
  2. Determine overvoltage shutdown value based on user requirement; factory setting is 15% above nominal line-to-neutral voltage.
  3. Remove the controller cover.
  4. Place master switch in RUN to start the generator set.
  5. Observe AC voltmeter; turn voltage adjustment potentiometer CW until generator set shuts down.
  6. If the shutdown point is correct, go to step 12; otherwise continue.
  7. Turn controller circuit board R42 adjustment potentiometer fully CW.
  8. Place master switch to OFF/RESET to reset; then to RUN to start.
  9. Observe AC voltmeter while turning voltage adjustment potentiometer to desired overvoltage shutdown point.
  10. Turn R42 adjustment potentiometer slowly CCW until the generator set shuts down.
  11. Turn controller voltage adjustment potentiometer slightly CCW.
  12. Place master switch OFF/RESET then RUN to start; adjust for correct voltage and phase.
  13. Place master switch OFF/RESET to stop.
  14. Disconnect battery negative lead first; reconnect generator set to load; reconnect battery negative lead last.
Reactive Droop Compensator Adjustment Procedure adjustment

Tools: Voltmeter, Wattmeter

  1. Remove any load; start each generator set with master switch in RUN.
  2. Set reactive droop compensator rheostat on generator set no. 1 to minimum CCW; record rpm/frequency and voltage at 1/4 load steps to full load.
  3. Repeat for generator set no. 2.
  4. Compare readings; adjust voltage within 1 volt and speed within 3 rpm (or 0.1 Hz) at each load step.
  5. Check droop compensation on each unit with an inductive load 1/2 to full load.
  6. Adjust rheostat to approximately 4% below rated voltage at full load.
  7. Repeat for unit no. 2.
Reactive Droop Compensator Alternate Adjustment Procedure adjustment

Tools: Voltmeter

  1. Turn reactive droop compensator rheostat on generator set no. 1 to minimum setting.
  2. Remove controller cover; move voltage sensing lead from V7 to V9 at the AC fuse terminal block.
  3. Remove any load connected to the generator set.
  4. Start the generator set with master switch in RUN.
  5. Use controller or remote voltage adjusting potentiometer to fine adjust voltage.
  6. Apply resistive load (1.0 power factor) until reaching rated current.
  7. Adjust reactive droop compensator rheostat to achieve a 4% droop in voltage.
  8. Remove the resistive load and stop the generator set.
  9. Return voltage sensing lead from V9 to V7 at the AC fuse terminal block.
  10. Replace the controller cover and repeat for generator set no. 2.
Underfrequency Adjustment (Over/Underfrequency Relay, Decision-Maker 3+) adjustment
  1. Turn underfrequency adjustment potentiometer fully clockwise (CW).
  2. Place master switch in RUN to start the generator set.
  3. Adjust governor per engine operation manual, engine service manual, or governor section of this manual.
  4. Slowly turn underfrequency potentiometer counterclockwise (CCW) until LED starts flashing; after about 10 seconds the set shuts down on auxiliary fault.
  5. Place master switch to OFF/RESET to reset the controller.
  6. Place master switch to RUN to start the generator set.
  7. Readjust the governor to the desired frequency as required.
  8. Place master switch to OFF/RESET to stop the generator set.
2-Wire Low Water Level Sender Test diagnostic

⚠ Hot engine and exhaust system can cause severe injury or death. Do not work on the generator set until it cools.

⚠ Hazardous voltage. Moving parts. Will cause severe injury or death. Operate the generator set only when all guards and electrical enclosures are in place.

Tools: DC voltmeter

  1. Measure DC voltage between lead 31A (+) and ground (- ) with sender submerged in coolant; voltmeter indicates approximately 12.5 VDC.
  2. Measure DC voltage between lead 31A (+) and ground (- ) with sender removed from coolant for at least 5-15 seconds; voltmeter indicates a drop to approximately 7 VDC.
3-Wire Low Water Level Sender Test diagnostic

⚠ Hot engine and exhaust system can cause severe injury or death. Do not work on the generator set until it cools.

⚠ Hazardous voltage. Moving parts. Will cause severe injury or death.

Tools: Ohmmeter

  1. Measure resistance between lead 31 and ground with sender submerged in coolant; ohmmeter indicates a high resistance reading.
  2. Measure resistance between lead 31 and ground with sender removed from coolant for at least 5-15 seconds; ohmmeter indicates a low resistance reading.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
120/208 or 139/2403-Phase4-Wire Low Wye60Hz, 120/208-Volt or 139/240-Volt 3-Phase, 4-Wire Low Wye; 50Hz, 120/208-Volt or 110/190-Volt 3-Phase, 4-Wire Low Wye
120/2401-Phase3-Wire60Hz, 120/240-Volt, 1-Phase, 3-Wire; 50Hz, 110/220-Volt, 1-Phase, 3-Wire
120/2403-Phase4-Wire Delta60Hz, 120/240-Volt, 3-Phase, 4-Wire, Delta; 50Hz, 110/220-Volt, 3-Phase, 4-Wire, Delta. CT3 - Not Used
277/4803-Phase4-Wire High Wye60Hz, 277/480-Volt, 3-Phase, 4-Wire High Wye; 50Hz, 220/380-Volt, 3-Phase, 4-Wire High Wye

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What is the power rating of the Cummins/Onan lsg-875?

The Cummins/Onan lsg-875 is rated 70 kW standby (87.5 kVA).

What engine does the Cummins/Onan lsg-875 use?

The Cummins/Onan lsg-875 is powered by the Ford LSG-875-6005A engine.

What fuel does the Cummins/Onan lsg-875 use?

The Cummins/Onan lsg-875 runs on Natural Gas.

What's the oil capacity on a Cummins/Onan lsg-875?

The Ford LSG-875-6005A engine in the Cummins/Onan lsg-875 has an oil capacity of 6.2 liters.

What is the cooling system capacity of the Cummins/Onan lsg-875?

The Cummins/Onan lsg-875 cooling system holds 28 liters (7.4 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.

What is the continuous rating of the Cummins/Onan lsg-875?

The Cummins/Onan lsg-875 is rated 60 kW prime (87 kVA), against 70 kW standby.

How much does the Cummins/Onan lsg-875 weigh?

The Cummins/Onan lsg-875 has a dry weight of 901 kg (1986 lb).

What voltages is the Cummins/Onan lsg-875 available in?

The Cummins/Onan lsg-875 is offered in 120/240 V, 120/208 V, 127/220 V, 139/240 V, 240/416 V, 254/440 V, 3-phase.

What size battery does the Cummins/Onan lsg-875 need?

The Cummins/Onan lsg-875 uses 1 battery, 12 V each, 259 CCA, group SEE, per the manufacturer specification sheet.

What alternator does the Cummins/Onan lsg-875 use?

The Cummins/Onan lsg-875 uses a 15 alternator.

Troubleshooting

6

Symptoms & remedies

SymptomRemedy
Engine stops cranking and fault lamp lights, after cranking approximately 75 seconds.See engine service manual for troubleshooting fuel system, ignition system, etc. After correcting problem, reset engine monitor relay by placing Run-Stop/Reset-Remote switch to Stop/Reset, then back to the required running position.
Fault lamp lights immediately after engine starts.Check for: Overspeed condition as engine starts.
Fault lamp lights and engine shuts down after running for a period.A. Oil level. Engine will shut down if sensor is closed. b. Check engine manual for troubleshooting oil system. c. High engine temperature. Check coolant level; check water flow (city water cooled systems); check radiator for free air flow, and fan belts for tightness. See engine manual for troubleshooting cooling system. d. Check for faulty oil pressure sensor or faulty high engine temperature sensor.
Engine runs, shuts down and cranks for 75 seconds. Cranking cycle stops; fault lamp lights.Check fuel supply. Check ignition system.
Fault lamp lights, no fault exists.To check a no-fault condition, disconnect leads from TB11 terminals 29, 30 and 31. If fault lamp lights with leads disconnected, replace engine monitor board. Reconnect leads.
Overcrank fault lamp lights and engine stops cranking after approximately 75 seconds.See engine service manual for troubleshooting fuel system, ignition system, etc. After correcting fault, reset engine monitor relay by placing Run-Stop/Reset-Remote switch to Stop/Reset position, depressing Reset button, then to the required running position.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing. Full Cummins/Onan lsg-875 troubleshooting guide (16 entries) →

Parts

5
Part #DescriptionQtySystem
C20E-6734-Aold drain plug sealSeal Amazon eBay
EQEE-6734-AAmetric drain plug sealSeal Amazon eBay
ESAE-6734-AAdrain plug sealSeal Amazon eBay
DZAE-6730-AAoil pan drain plugService part / kit Amazon eBay
E5AE-6730-AAmetric drain plugService part / kit Amazon eBay

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Fuel consumption

RatingLoadL/hgal/h
Prime100%1000.037.25
Standby100%7.88.2

Available documents

Spec sheet — tp6356es (Unknown (TP-6356-ES))Owner's manual — 928-0121 Onan EN ENT Genset Operator's manual (10-1986) (Cummins/Onan)Owner's manual — tt589 (Kohler)Parts manual — pb31 (Various (Cummins, Ford, John Deere, DDC))Parts manual — tp5614 (Kohler)Parts manual — tp5704 (Kohler)Service manual — 194-208 Ford LSG875 460CID Engine Service manual Apr1992 (Power Products)Service manual — 928-0612 Onan GGHB GGHC GGHD InstallationManual (11-1998) (Cummins/Onan)Service manual — TP-6356 (Kohler)Service manual — sb575Service manual — tp5149 (Kohler)Service manual — tp6356 (Kohler)

This page was generated from the 12 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.

Other sets with this engine