Kohler — Generator Reconnection (Voltage Change)

Installation · Generator Output Connections

From a Kohler service manual covering: CSG-649, Cummins 4B, Cummins 6B, Ford CSG-649, Ford LSG-423, Ford LSG-875, LSG-423, lsg-875. Check it applies to your exact model before use.

Applies to: Ford CSG-649, Cummins/Onan LSG-423, Cummins/Onan lsg-875

Before you start

  • ELECTRICAL SHOCK! Remove rings, watches and jewelry. Disconnect ground lead first and reconnect it last.
  • EQUIPMENT DAMAGE! Be sure line circuit breakers, transfer switch and other accessories using line voltage are properly sized for the voltage selected.

Procedure

  1. Move controller Master Switch to OFF/RESET or OFF position.
  2. Disconnect engine starting battery, negative (-) lead first.
  3. Select desired voltage connection from Figure 5-1.
  4. Route leads through current transformers and connect leads per diagram for desired voltage.
  5. If controller is equipped with meters, reposition meter scale lamp jumper to match proper position for desired voltage.
  6. Turn phase selector switch to L1-L2 position (1/12 or 3/36 depending on generator connection); if no meters, connect voltmeter across L1-L2.
  7. Reconnect starting battery. Move controller master switch to TEST position to start; check voltmeter for proper voltage; adjust with voltage adjust/regulator rheostat.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Full service-parts list: Ford CSG-649 →, Cummins/Onan lsg-875 →

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.