Kohler — Generator Frequency Change (60 Hz to 50 Hz)

Adjustments · Microcomputer Circuit Board

From a Kohler service manual covering: CSG-649, Cummins 4B, Cummins 6B, Ford CSG-649, Ford LSG-423, Ford LSG-875, LSG-423, lsg-875. Check it applies to your exact model before use.

Applies to: Ford CSG-649, Cummins/Onan LSG-423, Cummins/Onan lsg-875

Procedure

  1. On Microcomputer equipped generators, snip the jumper indicated in Figure A1 to convert from 60 Hz to 50 Hz.
  2. Check frequency meter for a no load reading of 63 Hz for 60 Hz operation and 53 Hz for 50 Hz operation.
  3. If equipped with isochronous governor, check for 60 and 50 Hz operation at no load.
  4. If no frequency meter, connect meter across VO and V7 on control board terminal strip (set must not be running while making connection).

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • 63 Hz (60 Hz no load)
  • 53 Hz (50 Hz no load)

Full service-parts list: Ford CSG-649 →, Cummins/Onan lsg-875 →

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.