Kohler — Resetting After Fault Shutdown (Microcomputer Controller)

Operation

From a Kohler service manual covering: CSG-649, Cummins 4B, Cummins 6B, Ford CSG-649, Ford LSG-423, Ford LSG-875, LSG-423, lsg-875. Check it applies to your exact model before use.

Applies to: Ford CSG-649, Cummins/Onan LSG-423, Cummins/Onan lsg-875

Procedure

  1. Move Generator Master Switch to OFF/RESET position.
  2. Disconnect generator set from load with line circuit breaker or automatic transfer switch.
  3. Correct cause of fault shutdown. See Safety Precautions.
  4. Move Generator Master Switch to TEST position for start-up.
  5. Verify that cause of shutdown has been corrected.
  6. Reconnect to load.
  7. Move Generator Master Switch to necessary position (AUTO or TEST) for start-up.

Full service-parts list: Ford CSG-649 →, Cummins/Onan lsg-875 →

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.