Home›Engines›Cummins/Onan C35 D6

Cummins/Onan C35 D6 Engine

The Cummins/Onan C35 D6 is a 3.3 L naturally aspirated engine. It powers generator sets from Cummins/Onan.

Also known as: Cummins C35 D6

3.3 L
Displacement

Engine specifications

Displacement3.3 L
Aspirationnaturally aspirated

Troubleshooting

80

Fault codes

CodeMeaningCauseRemedy
121Loss of Speed Sense (Shutdown) — No engine speed signal detected from one of two signals: engine crankshaft speed or engine camshaft positionFaulty Magnetic Pickup (MPU) sensor connections and wiring; improper installation of the MPU sensor; faulty MPU sensor; incorrect calibrations in PowerCommand controls; faulty control board; damaged flywheel ring gearInspect the MPU sensor and the main harness connector pins: disconnect the main harness connector from the MPU sensor; inspect for corroded, bent, broken, pushed back, expanded, or loose pins
144Engine Coolant Temperature OOR Low (Warning) — Engine coolant temperature signal voltage is out of range – shorted lowFaulty coolant temperature sensor connectionsInspect the coolant temperature sensor and the main harness connector pins; Disconnect the main harness connector from the coolant temperature sensor; Inspect for corroded pins, bent or broken pins, pushed back or expanded pins; Inspect for evidence of moisture in or on the connector; Dry the connectors with Cummins electronic cleaner, Part Number 3824510; Inspect for missing or damaged connector seals; Inspect for dirt or debris in or on the connector pins
144Engine Coolant Temperature OOR Low (Warning) — Engine coolant temperature signal voltage is out of range – shorted lowFaulty coolant temperature sensorCheck the resistance of the sensor; Disconnect the main harness connector from the coolant temperature sensor; Measure the resistance between the coolant temperature signal pin and the coolant temperature sensor return pin. Sensor resistance is approximately linear over two segments: 540 Ohms at -40 °F to 1100 ohms at 100 °F, and 1100 ohms at 100 °F to 1800 ohms at 230 °F. If calculated temperature differs from unit display by more than 8 °F, replace the sensor

Symptoms & remedies

SymptomCauseRemedy
Batteries can explodeDo not dispose of the battery in a fire, because it is capable of exploding. Do not open or mutilate the battery. Do not charge frozen batteries. Batteries present the risk of high short circuit current when servicing the generator set: remove watches, rings, or other metal objects; use tools with insulated handles.
Exhaust gases are deadlyProvide an adequate exhaust system to properly expel discharged gases away from enclosed or sheltered areas, and areas where individuals are likely to congregate. Visually and audibly inspect the exhaust system daily for leaks per the maintenance schedule. Ensure that exhaust manifolds are secured and not warped. Do not use exhaust gases to heat a compartment. Make sure the unit is well ventilated.
DizzinessIF YOU OR ANYONE ELSE EXPERIENCEANY OF THESE SYMPTOMS, GET OUT INTO THE FRESH AIR IMMEDIATELY. If symptoms persist, seek medical attention. Shut down the unit and do not operate until it has been inspected and repaired.
Muscular TwitchingIF YOU OR ANYONE ELSE EXPERIENCEANY OF THESE SYMPTOMS, GET OUT INTO THE FRESH AIR IMMEDIATELY. If symptoms persist, seek medical attention. Shut down the unit and do not operate until it has been inspected and repaired.
VomitingIF YOU OR ANYONE ELSE EXPERIENCEANY OF THESE SYMPTOMS, GET OUT INTO THE FRESH AIR IMMEDIATELY. If symptoms persist, seek medical attention. Shut down the unit and do not operate until it has been inspected and repaired.
Weakness and SleepinessIF YOU OR ANYONE ELSE EXPERIENCEANY OF THESE SYMPTOMS, GET OUT INTO THE FRESH AIR IMMEDIATELY. If symptoms persist, seek medical attention. Shut down the unit and do not operate until it has been inspected and repaired.
Inability to Think CoherentlyIF YOU OR ANYONE ELSE EXPERIENCEANY OF THESE SYMPTOMS, GET OUT INTO THE FRESH AIR IMMEDIATELY. If symptoms persist, seek medical attention. Shut down the unit and do not operate until it has been inspected and repaired.
Low AC Voltage at StartupLoss of residual magnetism in the exciter stator lamination (caused by extended storage; reversed magnetic field by flashing with wrong battery polarity; exciter stator rewind; mechanical shock (replacement))Restore magnetism: attach leads to a 12 VDC battery with a diode in the positive lead; run the generator at rated speed, no load; briefly (maximum one second) connect the positive lead to PCC terminal X+ (F1: P17-1) and the negative lead to PCC terminal XX- (F2: P17-2)
Unstable Voltage (No Load)Engine governing unstableCheck for engine governor hunting with a frequency meter or tachometer, or cyclic irregularities in the engine with InPower; if any engine DTC fault codes are present, troubleshoot them using the E-Controls manual; check fuel supply pressure to ensure that it is consistent; ensure that the throttle assembly moves freely, clean it if necessary; check the spark plugs for buildup, ensure that a spark is present at each cylinder, repair or replace them if necessary; check for any exhaust restriction, clean or replace components as necessary; check for an intake leak, repair or replace components as necessary; check for proper function of the crankshaft and camshaft position sensors, and the wiring to the ECM from the sensors, repair or replace components as necessary; check the fuel mix control valve for proper operation, such that it can move freely and easily, clean or replace the valve if necessary
Unstable Voltage (No Load)Loose or corroded connectionsCheck electrical connectors on terminals on the control board; check auxiliary terminals for loose connections; repair or replace as necessary
Unstable Voltage (No Load)Intermittent ground on machineMegger test all the windings, including the exciter stator; low insulation resistance can affect the PCC (disconnect the PCC before megger test)
Unbalanced Voltage (With Load)Engine governing unstableCheck with frequency meter or tachometer for engine governor hunting, or cyclic irregularities in the engine with InPower; if any engine DTC fault codes are present, troubleshoot those using the E-Controls manual; check fuel supply pressure to ensure that it is consistent; ensure that throttle assembly moves freely, clean if necessary; check the spark plugs for buildup, ensure that spark is present at each cylinder, repair or replace if necessary; check for any exhaust restriction, clean or replace if necessary; check for an intake leak, repair or replace if necessary; check for proper function of the crankshaft and camshaft position sensors, and the wiring to the ECM from the sensors, repair or replace if necessary; check the Fuel mix control valve for proper operation, such that it can move freely and easily, clean or replace if necessary
Unstable Voltage (With Load)Engine governing unstableRefer to the engine service manual (if applicable) or E-Controls service manual
Unstable Voltage (With Load)Leading power factor load created by power factor correction capacitorsIsolate the power factor correction capacitors until sufficient motor load has been applied to counteract the leading power factor; adjust as required if corrects the issue
Unstable Voltage (With Load)Fluctuations in load current (motor starting or reciprocating loads)Check the load current on a stable supply (i.e., mains), or separately excite the machine; a variable DC supply is required for on load separate excitation tests
Unstable Voltage (With Load)Automatic voltage regulator parameters configured incorrectlyContact your local Cummins distributor
Poor Voltage Regulation (With Load)Unbalanced loadCheck voltage and load current on all phases; if unbalanced, redistribute the load more evenly across the phases
Poor Voltage Regulation (With Load)Voltage drop between alternator and load, caused by losses in supply cable (power losses)Check the voltage at both ends of the cable run at full load; large differences in voltages indicate a large volts drop along the cable; a larger diameter cable is required in severe cases
Poor Voltage Regulation (With Load)Fault on main rectifier or excitation windingCheck the no load excitation voltage across automatic voltage regulator X+ (F1) and XX- (F2); voltage should be no higher than 12 VDC
Poor Voltage Regulation (With Load)Under frequency roll-off protection activatedUnder frequency roll-off protection is activated, indicating excessive load; check that under frequency roll-off set point and slope are correct; load on generator is in excess of rated, ensure that the load on the generator set does not exceed the generator kW rating; revisit the generator set sizing process to ensure that the generator set is correctly sized for the application, especially if new loads have been introduced into the system
High Voltage (With Load)Unbalanced loadCheck voltage on all three phases; if unbalanced, re-distribute loading over the three phases
High Voltage (With Load)Leading power factorCheck for capacitive (leading) PF load (i.e. kVA correction fluorescent lights); apply motor (lagging) PF load, or switch off capacitors; a leading power factor load will give abnormally low DC excitation volts across X+ (F1) and XX-(F2)
Low Voltage (With Load)Under frequency roll-off protection activatedUnder frequency roll-off protection is activated, indicating excessive load; check that under frequency roll-off set point and slope are correct; load on generator is in excess of rated, ensure that the load on the generator set does not exceed the generator kW rating; revisit the generator set sizing process to ensure that the generator set is correctly sized for the application, especially if new loads have been introduced into the system
Low Voltage (With Load)Faulty permanent magnet generator (PMG) (if used)Start the generator set and run at rated speed; measure the voltages at the terminals P2 (J18-1) and P3 (J18-2); these should be balanced and within the range of 60 Hz generators 190 to 220 V
Low Voltage (With Load)Fault on winding or rotating diodesAny fault in this area will appear as high excitation voltage across X+ (F1) and XX- (F2); remove external leads from the alternator; use appropriate metering equipment (Wheatstone bridge or Kelvin bridge) to measure the winding resistance of the main rotor and stator; check diodes; test diodes on the main rotating rectifier assembly with a multimeter
Low Voltage (With Load)Voltage drop between alternator and load, due to power losses in the cableCheck the voltage at both ends of the cable run at full load; differences in voltage levels indicate a voltage drop along the cable; in severe cases, a larger diameter cable is required; this will be worse during current surges (motor starting, etc.)
Fault Finding: Without AVR — Test 1: Resistance from sensing leads to ground is less than 1 MΩInsulation resistance less than 1 MΩClean the main stator, allow it to dry, and repeat the test; if the same result is achieved, replace the alternator/main stator
Fault Finding: Without AVR — Test 2: Exciter stator resistance across X+ (F1) and XX- (F2) is not within 10% of the relevant value in the Windings sectionStator windings are damagedReplace the exciter stator
Fault Finding: Without AVR — Test 3: Megger from XX- (F2) to ground, resistance value is less than 1 MΩInsulation resistance less than 1 MΩClean the exciter stator, allow it to dry, and repeat the test; if the same result is achieved, replace the exciter stator
Fault Finding: Without AVR — Test 4: AC output voltage balanced between phases within 1%, but greater than 10% below nominalMain stator is functioning properly; fault in exciter rotor, rectifier, or related componentsProceed to Test 6; if Tests 6 and 7 already completed, proceed to Test 8
Fault Finding: Without AVR — Test 4: AC output voltage unbalanced by greater than 1%Main stator windings are faultyProceed to Test 5
Fault Finding: Without AVR — Test 5: Winding resistances not within 10% of the relevant value from the Windings section, or not balanced within 1%Winding resistance out of specification or unbalancedReplace the alternator
Fault Finding: Without AVR — Test 6: One or more diodes do not function properlyFaulty diode(s) on the rotating rectifierReplace all diodes, as well as the varistor; return to Test 4
Fault Finding: Without AVR — Test 7: Varistor shows signs of a thermal event or measures no resistance in one or both directionsVaristor damaged or overheatedReplace all diodes and the varistor; return to Test 4
Fault Finding: Without AVR — Test 8: Resistance across exciter rotor leads within 10% of the relevant value in the Windings sectionExciter rotor resistance within specificationReplace the exciter rotor/alternator assembly
Fault Finding: Without AVR — Test 9: Main rotor resistance more than 10% different than the relevant value from the Windings sectionMain rotor resistance out of specificationReplace the main rotor/alternator assembly
Fault Finding: Without AVR — Test 10: One or more sense leads measure "open"Open sense lead(s)Replace the sensing leads
Fault Finding: Without AVR — Test 11: Output voltage not within 10% of nominal with EBS disconnectedEBS or control board faultReplace the control board; proceed to Test 12 if the EBS/EBC service tool is available, if not, replace the EBS
Fault Finding: Without AVR — Test 12: EBS or EBC does not operate properlyFaulty EBS or EBCReplace the faulty component
Fault Finding: Without AVR — Test 13: PMG voltages not 170-220V phase to phase and/or not balanced within 1%PMG voltage out of specification or unbalancedProceed to Test 14
Fault Finding: Without AVR — Test 14: PMG stator resistance not within 10% of the relevant value in the Windings sectionPMG stator resistance out of specificationReplace the PMG stator
Fault Finding: Without AVR — Test 14: PMG stator resistance within 10% of the relevant value in the Windings sectionPMG stator resistance within specificationReplace the PMG rotor
Engine Is Difficult to Start or Does Not StartBattery voltage is low, interrupted, or openCheck the battery connections, unswitched battery supply circuit, and fuses
Engine Is Difficult to Start or Does Not StartFuel system issuesInspect fuel lines and fuel connections for leaks, repair if leaks are found; open manual fuel valves if the manual fuel shutoff valve is closed; check the fuel shutoff valve solenoid and circuit if the fuel shutoff valve solenoid or circuit is malfunctioning
Engine Is Difficult to Start or Does Not StartAir intake or exhaust issuesCheck the air intake system for restriction, clean or replace the air filter and inlet piping as necessary; check the exhaust system for restrictions
Engine Is Difficult to Start or Does Not StartStarting procedure/aidCheck for the correct operation of the starting aid
Engine Is Difficult to Start or Does Not StartEngine speed governor issueRefer to the engine service manual
Engine Is Difficult to Start or Does Not StartBase engine problemCheck the engine for high crankcase pressure, low compression, damaged pistons, camshaft, and other parts; refer to the engine service manual
Engine Experiences Low Power, Poor Acceleration, or Poor ResponseExcessive loadEnsure that the load on the generator set does not exceed the generator set kW rating; revisit the generator set sizing process to ensure that the generator set is correctly sized for the application, especially if new loads have been introduced into the system
Engine Experiences Low Power, Poor Acceleration, or Poor ResponseFuel system issuesInspect fuel lines, fuel connections, and fuel filters for leaks, repair if leaks found; check the fuel shutoff valve solenoid and circuit if the fuel shutoff valve solenoid or circuit is malfunctioning
Engine Experiences Low Power, Poor Acceleration, or Poor ResponseAir intake or exhaust issuesCheck the air intake system for restriction, clean or replace the air filter and inlet piping as necessary; inspect the air intake and exhaust systems for air leaks; check the exhaust system for restrictions
Engine Experiences Low Power, Poor Acceleration, or Poor ResponseEngine speed governor issueRefer to the engine service manual
Engine Experiences Low Power, Poor Acceleration, or Poor ResponseOther issuesGenerator set power decreases above recommended altitude, refer to the Generator Set Data Sheet for the specific generator set for specifications; verify governor settings in the control if engine calibration values set in the control are not correct; check the engine for high crankcase pressure, low compression, damaged pistons, camshaft, and other parts, refer to the engine service manual
Engine Runs Rough or MisfiresAir intake or exhaust issuesCheck the air intake system for restriction, clean or replace the air filter and inlet piping as necessary; check the exhaust system for restrictions
Engine Runs Rough or MisfiresFuel system leaksInspect fuel lines, fuel connections, and fuel filters for leaks, repair if leaks found
Engine Runs Rough or MisfiresEngine speed governor issueRefer to the engine service manual
Engine Runs Rough or MisfiresBase engine problemCheck the engine for high crankcase pressure, low compression, damaged pistons, camshaft, and other parts; refer to the engine service manual
Engine Shuts Off Unexpectedly or Dies During DecelerationEmergency Stop/Remote Emergency Stop energizedVerify that either the Emergency Stop or the Remote Emergency Stop circuit is not energized
Engine Shuts Off Unexpectedly or Dies During DecelerationFuel system issuesCheck the fuel supply for appropriate pressure and flow; verify that the fuel system valves are open if the manual fuel shutoff valve is closed
Engine Shuts Off Unexpectedly or Dies During DecelerationEngine speed governor issueRefer to the engine service manual
Engine Shuts Off Unexpectedly or Dies During DecelerationBase engine problemCheck the engine for high crankcase pressure, low compression, damaged pistons, camshaft, and other parts; refer to the engine service manual
Engine Speed Surges Under Load or in Operating RangeFuel system issuesInspect fuel lines and fuel connections for leaks, repair if leaks found; verify that the fuel system valves are open if the manual fuel shutoff valve is closed; check the engine governor actuator and circuit if the engine governor actuator or circuit is malfunctioning
Engine Speed Surges Under Load or in Operating RangeEngine speed governor issueRefer to the engine service manual
Engine Speed Surges Under Load or in Operating RangeOther issuesDry the connectors with Cummins electronic cleaner, Part Number 3824510, if moisture is in the wiring harness connectors; check the engine for high crankcase pressure, low compression, damaged pistons, camshaft, and other parts, refer to the engine service manual
Poor Engine Transient ResponseExcessive loadsMake sure that the load on the generator set does not exceed the generator set KW rating; re-visit the generator set sizing process to make sure that the generator set is correctly sized for the application, especially if new loads have been introduced into the system
Poor Engine Transient ResponseFuel system issuesInspect fuel lines, fuel connections, and fuel filters for leaks, repair if leaks found; refer to the procedures in the troubleshooting and repair manual for the specific engine
Poor Engine Transient ResponseAir intake or exhaust issuesInspect the air intake and exhaust systems for air leaks; check the air intake system for restriction, clean or replace the air filter and inlet piping as necessary; check the exhaust system for restrictions; monitor the turbocharger boost pressure if the turbocharger is malfunctioning
Poor Engine Transient ResponseOther issuesEngine power decreases above recommended altitude, refer to the Generator Set Data Sheet for the specific generator set for specifications; check engine-driven units for correct operation and check the cooling fan for correct operation and cycle time if engine parasitics are excessive; verify the governor settings in the control if the engine calibration values set in the control are not correct; check the engine for high crankcase pressure, low compression, damaged pistons, damaged camshaft, and other damaged parts
Engine Will Not Reach Rated Speed (RPM)Excessive loadsEnsure that the load on the generator set does not exceed the generator set KW rating; re-visit the generator set sizing process to ensure that the generator set is correctly sized for the application, especially if new loads have been introduced into the system
Engine Will Not Reach Rated Speed (RPM)Air intake or exhaust issuesCheck the air intake system for restriction, clean or replace the air filter and inlet piping as necessary; check the exhaust system for restrictions
Engine Will Not Reach Rated Speed (RPM)Engine speed governor issueRefer to the engine service manual
Engine Will Not Reach Rated Speed (RPM)Other issuesGenerator set power decreases above the recommended altitude, refer to the Generator Set Data Sheet for the specific generator set for specifications; check the engine for high crankcase pressure, low compression, damaged pistons, camshaft, and other parts, refer to the engine service manual
Engine Noise Is ExcessiveLubrication issue(s)Check the oil level and fill the system to the specified level if lubricating oil level is below specification; check the oil pressure if lubricating oil pressure is below specification; analyze the oil if lubricating oil is thin or diluted
Engine Noise Is ExcessiveCooling issue(s)Check the coolant level if coolant temperature is above specification; check the fan drive belt if the fan drive belt is loose, tight, or not in alignment
Engine Noise Is ExcessiveAir intake or exhaust leaksInspect the air intake and exhaust systems for air leaks
Engine Noise Is ExcessiveWorn mountsCheck the engine mounts if engine mounts are worn, damaged, or incorrect
Engine Noise Is ExcessiveBase engine problemCheck the engine for high crankcase pressure, low compression, damaged pistons, camshaft, and other parts; refer to the engine service manual

Fault codes and symptom→remedy steps extracted from this engine’s service/owner documentation; verify against the official manual before servicing. Showing the first 80 of 274 entries.

Common problems

15
  • Low Battery Voltage — Battery voltage is low 441
    Cause: Damaged battery cable connections
    Fix: Inspect the battery cable connections for loose connections and/or corrosion, and repair as necessary
  • LOW ACE VOLTAGE (SHUTDOWN) — Engine will shut down 13
    Cause: Fault simulation was enabled with a PC based service tool
    Fix: With a PC based service tool, verify that the related fault simulation is not enabled. If you do not have a PC based service tool, remove battery power from the control to disable fault simulation overrides.
  • Excitation Fault (Loss of AC Sense) — The control has lost voltage sensing or has lost zero cross sensing 2335
    Cause: Incorrect configuration
    Fix: Make sure that values for the Low of AC Voltage Threshold (85%) and Low of AC Voltage Time Delay (10 seconds) are correct in calibration
  • Engine Oil Pressure Low (Shutdown) — Engine oil pressure is below the low oil pressure shutdown threshold (35 psig) 415
    Cause: Lubricating oil level is low
    Fix: Check the oil level. Add or drain oil, if necessary
  • Engine does not crank in manual mode (no fault message) — Engine will not start
    Cause: No power supplied to control; Poor battery cable connections
    Fix: Clean the battery cable terminals and tighten all connections; Remove connector P11 and check for B+ at P11-3 & 15 and GND at P11-9 & 10. If B+ or ground missing, isolate to harness and TB BAT terminal mounted on engine block. If B+ and ground check OK, cycle power to base board by reconnecting P11 and retry operation.
  • Engine Is Difficult to Start or Does Not Start
    Cause: Battery voltage is low, interrupted, or open
    Fix: Check the battery connections, unswitched battery supply circuit, and fuses
  • LOW OIL OR PRE-LOW PRESSURE (WARNING/SHUTDOWN) OIL PRESSURE SENSOR TYPE : SENDER — Calibration-dependent. No action is taken by the Control for code 215. Engine will shut down for code 2 2/215
    Cause: Fault simulation was enabled with a PC based service tool
    Fix: With a PC based service tool, verify that the fault simulation is not enabled for the oil pressure sensor. If you do not have a PC based service tool, remove battery power from the control to disable fault simulation overrides.
  • Low Coolant Level (Warning or Shutdown) — This fault is used when an optional coolant level sensor is installed. The nature of the fault is an optional customer selection 1317
    Cause: Low coolant
    Fix: Stop the engine and allow the engine to cool down; Visually inspect and verify that the engine coolant is at the appropriate level; If the coolant level is too low, add coolant per specifications
  • HIGH AC VOLTAGE (SHUTDOWN) — Engine will shut down 12
    Cause: Fault simulation was enabled with a PC based service tool
    Fix: With a PC based service tool, verify that the related fault simulation is not enabled. If you do not have a PC based service tool, remove battery power from the control to disable fault simulation overrides.
  • Engine Noise Is Excessive
    Cause: Lubrication issue(s)
    Fix: Check the oil level and fill the system to the specified level if lubricating oil level is below specification; check the oil pressure if lubricating oil pressure is below specification; analyze the oil if lubricating oil is thin or diluted
  • Engine Experiences Low Power, Poor Acceleration, or Poor Response
    Cause: Excessive load
    Fix: Ensure that the load on the generator set does not exceed the generator set kW rating; revisit the generator set sizing process to ensure that the generator set is correctly sized for the application, especially if new loads have been introduced into the system
  • Unstable Voltage (With Load)
    Cause: Engine governing unstable
    Fix: Refer to the engine service manual (if applicable) or E-Controls service manual
  • Poor Voltage Regulation (With Load)
    Cause: Unbalanced load
    Fix: Check voltage and load current on all phases; if unbalanced, redistribute the load more evenly across the phases
  • Poor Engine Transient Response
    Cause: Excessive loads
    Fix: Make sure that the load on the generator set does not exceed the generator set KW rating; re-visit the generator set sizing process to make sure that the generator set is correctly sized for the application, especially if new loads have been introduced into the system
  • Low Voltage (With Load)
    Cause: Under frequency roll-off protection activated
    Fix: Under frequency roll-off protection is activated, indicating excessive load; check that under frequency roll-off set point and slope are correct; load on generator is in excess of rated, ensure that the load on the generator set does not exceed the generator kW rating; revisit the generator set sizing process to ensure that the generator set is correctly sized for the application, especially if new loads have been introduced into the system

Compiled from service & troubleshooting documentation across every generator set that uses the Cummins/Onan C35 D6.

Service intervals

20
ItemActionHoursMonthsNotes
Exhaust systemInspect8 hrVisually and audibly inspect the exhaust system daily for leaks per the maintenance schedule; check for corrosion, obstruction, and leaks every time you start the generator set and every eight hours when you run it continuously
Air cleaner restriction indicatorCheck24 hrIf service indicator shows red, replace air cleaner elements and reset indicator.
Coolant heaterCheck24 hrVerify power and operation; check for leaks.
Coolant level of radiator(s)Check24 hrTop up with Cummins recommended coolant mix if low.
Engine oil levelCheck24 hrTop up with recommended oil if low.
Fuel level in fuel tankCheck24 hrRefill as required.
Fuel lines and hosesCheck24 hrCheck for leaks, worn or damaged hoses.
Generator set enclosureInspect24 hrWalk-around; ensure no inlets/outlets covered.
Operator panel operationCheck24 hrCheck display; replace component if not functioning.
Air intake system for leaksInspect50 hrVisually inspect; check audibly when running.
Battery connectionsCheck50 hrVerify connections are secure.
Charge alternatorCheck50 hrCheck visually and audibly when running.
Coolant lines and radiator hosesCheck50 hrCheck for leaks, wear, and cracks.
Cooling fan bladesInspect50 hrVisually inspect through guarding.
Drive belt condition and tensionCheck50 hrCheck for wear or slippage.
Exhaust components and hardwareCheck50 hrVisually inspect; check audibly when running.
Radiator air flowInspect50 hrCheck for blockage, debris, wear or damage.
Engine oil and filtersReplace200 hrFirst service — After the initial 50 hour interval and every 200 hours thereafter (footnote 3).
Fuel filter and water separatorReplace500 hr
Cooling system coolantReplace24 mo

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

60
TypeItemValueUnitCondition
GapMPU sensor tip to ring gear teeth clearance0.5 - 0.6mm
OtherAFLEX-H (shake table test datum)<=3.200gAC156, tri-axial, 5% damping SRS
OtherAFLEX-V (shake table test datum)<=1.333gAC156, tri-axial, 5% damping SRS
OtherARIG-H (shake table test datum)<=2.400gAC156, tri-axial, 5% damping SRS
OtherARIG-V (shake table test datum)<=0.533gAC156, tri-axial, 5% damping SRS
OtherFlywheel teeth (Teeth Pulses Per Revolution)110PCC setting
OtherGlow plug preheat time5glow plug calibration
OtherGlow plug total glow plug time60glow plug calibration
OtherGround snow load limit30psfFor indoor (covered) and outdoor (exposed) installation
OtherHorizontal design seismic coefficient (z/h = 0.0)1.440gCertified seismic design level, IBC Importance IP <= 1.5, Soil Classes A-E, Risk Categories I-IV, Design Categories A-F, SDS <= 2.000 g
OtherSDS (g) at z/h=1 for C10 D6 - C60 D62.0gCertified SDS, z/h = 1
OtherSDS (g) at z/h=1 for C50 D6C - C125 D6C2.5gCertified SDS, z/h = 1
OtherSpeed/frequency mismatch threshold2.0HzPCC setting
OtherSpeed/frequency mismatch threshold time1.5secondsPCC setting
OtherZPA-H (shake table test datum)<=2.160gAC156, tri-axial, 5% damping SRS
OtherZPA-V (shake table test datum)<=0.480gAC156, tri-axial, 5% damping SRS
ResistanceBattery ground connection resistancemore than 1Ohmindicates repair needed
ResistanceCoolant heater coil resistance10 to 60ohmsclosed heater
ResistanceCoolant temperature sensor resistance540 Ohms at -40 F to 1100 Ohms at 100 F; 1100 Ohms at 100 F to 1800 Ohms at 230 FOhm
ResistanceDiode reverse direction resistance (good)above 20MOhmreverse direction at 1000 VDC
ResistanceInjection pump actuator resistance2.3ohms
ResistanceMain rotor resistance0.415Ohmswithin 10% of value
ResistanceMain rotor resistance0.437Ohmswithin 10% of value
ResistanceMain rotor resistance0.465Ohmswithin 10% of value
ResistanceMain rotor resistance0.545Ohmswithin 10% of value
ResistanceMain rotor resistance0.551Ohmswithin 10% of value
ResistanceMain rotor resistance0.657Ohmswithin 10% of value
ResistanceMain rotor resistance0.67Ohmswithin 10% of value
ResistanceMain rotor resistance0.708Ohmswithin 10% of value
ResistanceMain rotor resistance0.857Ohmswithin 10% of value
ResistanceMain rotor resistance0.89Ohmswithin 10% of value
ResistanceMain rotor resistance0.983Ohmswithin 10% of value
ResistanceMain rotor resistance0.99Ohmswithin 10% of value
ResistanceMain stator winding resistance0.3Ohms
ResistanceMain stator winding resistance0.353Ohms
ResistanceMain stator winding resistance0.51Ohms
ResistanceMain stator winding resistance0.625Ohms
ResistanceMain stator winding resistance0.95Ohms
ResistanceMain stator winding resistance1.33Ohms
ResistanceMain stator winding resistance1.908Ohms
ResistanceStarter solenoid wiring continuity (relay 87 to SW)less than 5Ohm
ResistanceStator insulation resistance1.0Meg-Ohmminimum to Earth (Ground)
ResistanceTemperature sender harness lead resistanceless than 0.5Ohmeach lead from connection to PCC
ResistanceVaristor resistance (good)greater than 100MOhm
ResistanceWinding test conditions20Cwinding temperature for insulation measurement
ResistanceWindings minimum insulation resistance (in-service)5MOhm1 minute at 500 V test voltage
ResistanceWindings minimum insulation resistance (new)10MOhm1 minute at 500 V test voltage
SpeedFrequency-to-speed gain select30RPM/HzPCC setting
SpeedOverspeed Trip Level (60 Hz)2250PCC threshold
SpeedSecondary Overspeed Trip Speed (60 Hz)2250PCC threshold
SpeedStarter Disconnect Speed400RPMInPower setting
SpeedStarter Disconnect Speed (code 5134)450RPMInPower setting
TemperatureHigh coolant temperature shutdown threshold230 F / 110Cshutdown
TemperatureHigh coolant temperature warning threshold220 F / 105Cwarning
TemperatureLow coolant temperature warning threshold70 F (21 C)4BT3.3 engines
TorqueAVR cover to NDE bracket5Nm
TorqueAVR to NDE bracket5Nm
TorqueAir cleaner strap clamp3.4 to 4.5Nm
TorqueAlternator drive disc bolt and adaptor bolt (section 12.5)52 +/- 5Nm
TorqueAlternator drive disc bolts and adaptor bolts47 to 57Nm

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Coolant50/50 coolant solution (50% pure water and 50% ethylene glycol)
Coolant50/50 coolant solution (50% water / 50% ethylene glycol)
Engine oil15W407.9 L (8.35 qt)Refer to the Engine Operator Manual
FuelASTM number 2D fuelASTM 2D
FuelNumber 2 diesel fuelDirect injection
GreaseDow Corning silicone heat sink compound type 340 or similarApply to base of replacement diode only

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

80
CodeNameMeaningSeverityAction
1HIGH COOLANT TEMPEngine has overheated; coolant temperature has risen above shutdown trip point.ShutdownAllow engine to cool. Check coolant level, airflow obstructions, fan belt, blower and circulation pumps. Reset and restart.
2LOW OIL PRESSUREEngine oil pressure has dropped below shutdown trip point.ShutdownCheck oil level, lines and filters; replenish if low; reset and restart; check oil switch.
12HIGH AC VOLTAGEOne or more phase voltages exceeded 130% of nominal for 0 second, or exceeded high AC voltage threshold for time delay.ShutdownCheck fault simulation, block load removal, threshold setting, Base board or generator, voltage sense connections.
13LOW AC VOLTAGEOne or more phase voltages dropped below low AC voltage threshold for time delay.ShutdownCheck fault simulation, threshold, overload, output connections, excitation inputs, rotating rectifier diodes, connector or Base board.
14OVER FREQUENCYFrequency is 10% above base frequency for approximately 10 seconds.ShutdownCheck threshold, fuel or air delivery, governor, connector or Base board.
15UNDER FREQUENCYEngine speed dropped below 90% of nominal for approximately 10 seconds.ShutdownCheck fuel supply, intake air supply, load, threshold, governor, connector or Base board.
27EXCITATION FAULTLoss of all three voltage sense leads or failure in excitation circuit.ShutdownCheck field wiring (X1 and X2) for shorts or opens.
31OVERSPEEDEngine exceeded normal operating speed; default thresholds 1725 RPM (50 Hz) or 2075 RPM (60 Hz).ShutdownCheck cold engine, single step large block load removal, fault simulation, threshold, MPU, governor, flywheel teeth, fuel stop settings.
38FIELD OVERLOADField AVR Duty Cycle has been at maximum for at least 15 seconds.Shutdown
45SPEED SIGNAL LOSTNo magnetic pickup pulses are sensed for Loss of Speed delay; if no MPU, speed sensing is by AC line frequency and fault cannot occur.ShutdownInspect MPU wires/connector pins; test MPU for 3.5 to 15 VAC while cranking; check P11-12 to P11-24; replace Base board if needed.
46HIGH AC CURRENTIndividual phase alternator output current exceeded high current threshold continuously for more than time delay.ShutdownCheck load and load lead connections.
61EMERGENCY STOPRemote Emergency Stop.ShutdownOpen (disable) remote emergency stop button; move rocker switch to OFF or press OFF; select desired operating mode.
71SPEED HZ MATCHMeasured speed and measured AC output frequency do not agree.ShutdownCheck genset setup for number of flywheel teeth.
72FAIL TO CRANKGenset failed to sense rotation for two start attempts; possible control, speed sensing or starting system fault.ShutdownCheck starter, K7 starter relay, Emergency Stop switch/wiring, MPU circuit or Base board.
73FAIL TO STARTEngine cranks but fails to start; possible fuel system or air induction problem.ShutdownCheck fuel tank, leaks, plugged fuel lines, fuel filter, air filter; reset and restart; check glow plugs and governor linkage.
74FAIL TO STOPGenset continues to run after receiving shutdown command from controller.Shutdown
75,76CONFIGURABLE INPUT #1 & #2Optional configurable input fault.ShutdownDisconnect signal lead from TB1 and reset control; check CUST_IN1 TB1-14 and CUST_IN2 TB1-12.
77SHUTDOWN AFTER BSA shutdown fault occurred while Battle Short mode was enabled.ShutdownCheck fault history for faults that may have been bypassed.
81,82,83ANNUNCIATOR FAULT 1,2,3Optional configurable annunciator fault.Shutdown
121Loss of Speed SenseNo engine speed signal detected from crankshaft speed or camshaft position.ShutdownInspect MPU sensor and harness; set MPU tip clearance 0.5-0.6 mm; verify calibration.
135Oil Pressure Sensor OOR - HighEngine oil pressure sensor signal out of range - shorted high.WarningInspect sensor connections; check supply 4.75-5.25 VDC and signal voltage.
135/141Oil Pressure Sensor OOR - WarningWarning
141Oil Pressure Sensor OOR - LowEngine oil pressure sensor signal out of range - shorted low.WarningInspect sensor connections; check supply and signal voltage.
143Engine Oil Pressure LowEngine oil pressure below low oil pressure warning threshold (40 psig for 5 seconds).WarningCheck oil level, external leaks, sensor accuracy, oil cooler, regulator, oil pump.
144Engine Coolant Temperature OOR LowEngine coolant temperature signal out of range - shorted low.WarningInspect sensor connections; check sensor resistance; verify calibration.
145Engine Coolant Temperature OOR HighEngine coolant temperature signal out of range - shorted high.WarningInspect sensor connections; check sensor resistance; verify calibration.
146Engine Coolant Temperature Above NormalEngine coolant temperature exceeded warning threshold (220 F / 105 C).WarningCheck ambient temperature, coolant level, cooling components, sensor, thermostat, water pump.
151Engine Coolant Temperature HighEngine coolant temperature exceeded shutdown threshold (230 F / 110 C).ShutdownCheck cooling system, coolant level, sensor, thermostat, water pump.
202PRE-HIGH COOL TMPEngine is operating near cooling system capacity.WarningReview code 1 correction list.
203LOW COOLANT TEMPEngine coolant temperature is 70F (21C) or lower.WarningCheck coolant heater power, low coolant level, heater element; check current draw.
204,205CONFIGURABLE INPUT #1,#2Optional configurable input warning.WarningDisconnect signal lead from TB1 and reset control; check CUST_IN1 TB1-14 and CUST_IN2 TB1-12.
212COOL SENSOR OORCoolant temperature sensor output is out of range (high or low).WarningCheck sender, connectors and wires.
213LOW BATTERYBattery voltage supply to control is approaching a low level.WarningCheck battery charger fuse; recharge or replace battery; clean connections; check wiring/calibration, engine DC alternator, float level.
214HIGH BATTERYBattery voltage supply to control is approaching a high level.WarningCheck float level on battery charger; check battery wiring/calibration.
215PRE-LOW OIL PRESSUREEngine oil pressure dropped below warning trip point.WarningFollow code 2 procedure.
216HIGH AC CURRENTOne or more phase currents exceeded high AC warning threshold for time delay.WarningCheck load and load lead connections.
217OIL PRESS SENSOR OOREngine oil pressure sensor output is out of range (high or low).WarningCheck sender, connectors and wires.
218BATTLE SHORT ACTIVEControl is in Battle Short mode; bypasses several fault shutdowns for emergency operation.Warning
219CHARGER FAILUREBattery charging alternator has not reached acceptable voltage range within selected period (default 120 seconds).WarningRefer to engine service manual if fault occurs; check wiring if not failed.
220FAIL TO SHUTDOWNGenset continues to run after shutdown command; Battle Short feature enabled.Warning
221WEAK BATTERYDuring cranking, battery voltage is at or below weak battery warning trip point for time >= weak battery set time.WarningSee code 213 for corrective action.
222,223,224ANNUNCIATOR FAULT 1,2,3Optional configurable annunciator fault.Warning
225ANNUNCIATOR OUTPUT CONFIGURATION ERRORMismatch in configuration of one of the annunciator relay outputs.WarningCheck network setup for duplicate use of same annunciator relay output; troubleshoot network devices.
234Engine Speed HighEngine speed signals indicate engine speed greater than shutdown threshold.ShutdownCheck MPU sensor and installation; verify overspeed trip level and flywheel teeth (110).
359Engine Fail to StartEngine failed to start after expiration of last crank time.ShutdownCheck flywheel teeth setting (110), starter disconnect speed (400 RPM), fuel supply, glow plugs.
415Engine Oil Pressure LowEngine oil pressure below low oil pressure shutdown threshold (35 psig).ShutdownCheck oil level, external leaks, sensor accuracy, oil cooler, oil pump.
441Low Battery VoltageBattery voltage is low.WarningCheck battery cables, battery condition, ground connection, DC alternator, charger.
442High Battery VoltageBattery voltage above high battery threshold (16 V for 60 seconds).WarningVerify charger set to 12 VDC; check fault threshold; check engine DC alternator.
1311Customer Input #1Configurable customer input 1 fault.WarningCheck TB1-12; check external wiring; verify fault function settings.
1312Customer Input #2Configurable customer input 2 fault.WarningCheck TB1-14; check external wiring; verify fault function settings.
1317Low Coolant LevelOptional coolant level sensor indicates low coolant level.WarningAdd coolant; check coolant level sensor connections and operation; verify calibration.
1318Low FuelOptional low fuel level switch indicates low fuel.WarningAdd fuel; verify switch operation; check wiring; verify settings.
1417Power Down FailureThe PCC has failed to go to sleep.WarningVerify calibration; cycle B+ power; replace baseboard if fault persists.
1433Local E-StopState of the Local Emergency Stop has been changed.ShutdownReset local E-Stop; check E-Stop switch and wiring.
1434Remote E-StopState of the Remote Emergency Stop has been changed.ShutdownReset remote E-Stop; install jumper TB1-16 to TB1-15; check switch and wiring.
1435Low Coolant TemperatureEngine coolant temperature below low coolant temperature warning threshold (70 F / 21 C).WarningVerify LCT threshold; check coolant heater operation; check ambient temperature.
1438Fail to CrankEngine failed to crank after the generator control received a start signal.ShutdownCheck battery, starter, starter solenoid, starter relay, CAM/Crank sense.
1442Weak BatteryBattery voltage dropped below weak battery voltage threshold (8 V for 2 seconds) while cranking.WarningCheck battery, connections, charging voltage, DC alternator, harness.
1446High AC VoltageOne or more phase voltages exceeded high AC voltage threshold (110% of nominal, 10 seconds).WarningCheck threshold, PCC AVR circuit, generator output connections, PMG, EBS.
1447Low AC VoltageOne or more phase voltages dropped below low AC voltage threshold (85%, 10 seconds).ShutdownCheck AVR settings, rotating rectifier diodes, overload, residual magnetism, connections.
1448UnderfrequencyFrequency dropped below underfrequency threshold (6 Hz) for 10 seconds.ShutdownCheck overrides, threshold, overload, engine governor.
1449OverfrequencyFrequency went above overfrequency threshold (6 Hz) for 10 seconds.ShutdownVerify overfrequency threshold and time delay; check engine governor.
1469Speed/Hz MismatchPerceived engine speed and generator set output frequency do not match.ShutdownCheck flywheel teeth (110), MPU signal, thresholds (2.0 Hz, 1.5 s), gain (30 RPM/Hz).
1471High AC CurrentGenerator output current exceeded warning limit threshold (110% for 60 seconds).WarningCheck for short, overload, CTs and CT setup, rating setup, fault override.
1472High AC CurrentGenerator output current exceeded shutdown set limit (150% for 10 seconds).ShutdownCheck for short/overload, CTs and CT setup, rating setup, fault override.
1853Annunciator Input 1 FaultCustomer fault 1 (input 1, LED 1) on the universal annunciator is active.WarningCheck condition and wiring at TB1-1; verify configuration; replace annunciator if faulty.
1854Annunciator Input 2 FaultCustomer fault 2 (input 2, LED 2) on the universal annunciator is active.WarningCheck condition and wiring at TB1-2; verify configuration; replace annunciator if faulty.
1855Annunciator Input 3 FaultCustomer fault 3 (input 3, LED 3) on the universal annunciator is active.WarningCheck condition and wiring at TB1-3; verify configuration; replace annunciator if faulty.
1944Annunciator Configuration ErrorMore than one network device configured to activate one annunciator output relay.WarningCheck network configuration and devices for duplicate use of the same relay output.
2335Excitation Fault (Loss of AC Sense)Control lost voltage sensing or lost zero cross sensing.ShutdownCheck configuration, fuse F5 (10 Amp), harness connections, residual magnetism, excitation coil, control board.
2676Alternator Frequency ConflictAlternator line frequency and alternator excitation frequency do not match.ShutdownCheck alternator line frequency gain; check J22 and J18 connections; check harness and control board.
2677Fail to StopGenerator set continues to run after receiving shutdown command from controller.ShutdownCheck stuck fuel actuator/fuel shutoff valve; check governor module and wiring.
2729IO Module LostIntermittent data link between I/O module and PCC (no input fault levels set to Shutdown).WarningCheck AUX 101 wiring to PCC 1302; verify System IO Board Enable is disabled.
2731IO Module LostIntermittent data link between I/O module and PCC (at least one input fault set to Shutdown).ShutdownCheck AUX 101 wiring to PCC 1302; verify I/O settings.
2897Factory Memory Block CorruptThe control detected a corrupted memory block.WarningConnect with InPower 10.0+; select Initial Calibration (Recover Device).
2898Periodic or Fault Memory Block CorruptThe control detected a corrupted memory block.WarningConnect with InPower 10.0+; select Initial Calibration (Recover Device).
2899User Memory Block CorruptThe control detected a corrupted memory block.WarningConnect with InPower 10.0+; select Initial Calibration (Recover Device).
2911Trim Memory Block CorruptThe control detected a corrupted memory block.WarningConnect with InPower 10.0+; select Initial Calibration (Recover Device).
2972Field OverloadField AVR Duty Cycle operated at maximum output longer than Max Field Time parameter.ShutdownCheck voltage sensing into baseboard; check AVR output; check application.
5134Unknown ShutdownPCC detected that engine RPM decreased to zero while not in run at rated mode.ShutdownCheck calibration, air intake/exhaust restriction, MPU signal, start disconnect, fuel supply.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

12
Disabling the AMF Feature adjustment

⚠ Must be performed by a qualified technician.

Tools: InPower service tool

  1. Connect to the PCC 1.1 or PCC 2.3 via InPower.
  2. Navigate to Adjustments->Features->Automatic Transfer Switch folder.
  3. Select the Auto Mains Failure Enable parameter.
  4. Double-click on Enabled in the Value field.
  5. Select Disabled from the pop-up choices.
  6. Select Device->Save Adjustments from the top menu bar.
  7. Click Save on the confirmation pop-up.
  8. Disconnect InPower from the PCC1302 after confirmation.
Fuel Injection Pump Speed Lever Adjustment adjustment
  1. Make sure the generator set is off and the battery is disconnected.
  2. If replacing pump or engine, discard speed adjust screw and tamper proof wire and seal.
  3. Replace the low idle screw; reuse throttle screw nut and acorn nut.
  4. Pull throttle lever back and screw new low idle screw until it contacts boss.
  5. Continue tightening until throttle lever is locked in place.
  6. Tighten the throttle lock nut.
  7. Install tamper proof wire and seal.
  8. Set the throttle lever as shown and lock it using seal wire.
Valves - Adjust, All adjustment
  1. Disconnect battery cables
  2. Remove valve cover
  3. Adjust valve lash
  4. Test run unit
Generator/Base Board Isolation Procedure diagnostic

⚠ Hazardous voltage

⚠ Test involves unregulated excitation; disconnect loads

Tools: 12 volt battery, Jumper leads, Voltmeter

  1. Throw line circuit breaker OFF and shutdown set.
  2. Disconnect X and XX exciter stator leads from AC harness.
  3. Prepare to measure output voltage across generator terminals.
  4. Bring two jumpers from 12V battery to X (Field +) and XX (Field -).
  5. Check polarity; correct or test inconclusive.
  6. Start set and connect battery negative to XX.
  7. If rated output voltage or higher and balanced, generator OK; troubleshoot control.
  8. If unbalanced, troubleshoot main stator; if uniformly low, troubleshoot exciter and field.
Testing Diodes diagnostic

⚠ Layers of dust can cause diodes to overheat and fail.

Tools: Ohmmeter

  1. Disconnect diode pigtails from terminal posts.
  2. Measure resistance between each diode pigtail and its plate.
  3. Reverse meter probes and repeat.
  4. Replace diode if resistance high or low in both directions.
Testing Exciter Rotor diagnostic

Tools: Wheatstone bridge, Ohmmeter

  1. Disconnect six rotor winding leads from rectifier terminal posts.
  2. Measure resistance across each pair of rotor windings U-V, V-W, W-U.
  3. Replace whole rotor shaft assembly if any winding resistance not per Table 6-1.
  4. Measure insulation resistance between winding lead and rotor laminations.
  5. Replace rotor shaft assembly if insulation resistance less than 1 megohm.
Testing Exciter Stator diagnostic

Tools: Wheatstone bridge, Digital ohmmeter, Insulation resistance meter

  1. Measure winding resistance with Wheatstone bridge or digital ohmmeter.
  2. Replace stator if resistance not as specified in Table 6-1.
  3. Disconnect X and XX leads and isolate from ground.
  4. Measure resistance between either lead and stator laminations.
  5. Replace stator if insulation resistance less than 1 megohm.
Testing Main Rotor diagnostic

Tools: Wheatstone bridge, Digital ohmmeter, Torque wrench

  1. Disconnect two main rotor leads from rotating rectifier terminals.
  2. Measure resistance between two leads with Wheatstone bridge or digital ohmmeter.
  3. Replace rotor if resistance not as specified in Table 6-1.
  4. Measure resistance between either lead and main rotor laminations.
  5. Replace rotor if insulation resistance less than 1 megohm.
  6. Torque terminals to 24 in-lbs (2.7 Nm) when reassembling.
Testing Main Stator diagnostic

Tools: Wheatstone bridge, Insulation tester

  1. Measure resistance across each pair of stator leads U1-U2, U5-U6, V1-V2, V5-V6, W1-W2, W5-W6.
  2. Use Wheatstone bridge or ohmmeter with at least 0.001 ohm precision.
  3. Replace stator if any winding resistance not as specified in Table 6-1.
  4. Disconnect AVR completely before insulation test.
  5. Disconnect Neutral to Earth and any connections.
  6. Use 500 or 1000 V insulation tester for low voltage generators up to 690V.
  7. Minimum insulation value is 1.0 Meg-Ohm to Earth; dry windings if below.
AC Load Connections (Circuit Breaker) installation

⚠ Improper installation can lead to electrocution and property damage.

Tools: Insulated wrench, Torque wrench

  1. Shut down and disable the generator set (Off then E-Stop, cool down).
  2. Turn off battery charger AC and disconnect negative battery cable.
  3. Remove enclosure side panel to access main circuit breaker box.
  4. Place circuit breaker handle in OFF position.
  5. Remove four bolts holding circuit breaker cover.
  6. Connect conductors to load-side terminals, neutral lug, and grounding lug.
  7. Torque circuit breaker terminals per breaker label.
  8. Torque neutral lug to 31.1 Nm (275 in-lb).
  9. Torque equipment grounding lug to 13.8 Nm (120 in-lb).
  10. Fill stub-up openings with duct seal or mastic tape.
  11. Install circuit breaker cover.
Connect Battery installation

⚠ Do not connect battery cables until installation is complete to prevent accidental startup.

  1. Connect the positive battery terminal.
  2. Connect the negative battery terminal.
  3. Make sure black and red battery cable boots are in place.
Connecting the Battery installation

⚠ Accidental or remote starting of the generator set can cause severe personal injury or death.

  1. Press the generator set's O (Off) button and allow it to cool.
  2. Turn off and disconnect the battery charger from the AC source before disconnecting battery cables.
  3. Disconnect the negative (-) cable from the battery.
  4. Connect the positive battery terminal.
  5. Connect the negative battery terminal.
  6. Make sure black and red battery cable boots are in place.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
above 300 volts L-LX1 & X2CT secondariesCTs have dual secondaries (3 pins marked X1, X2 & X3).
below 300 volts L-LX1 & X3CT secondariesCTs have dual secondaries (3 pins marked X1, X2 & X3).

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What is the displacement of the Cummins/Onan C35 D6?

The Cummins/Onan C35 D6 has a displacement of 3.3 liters.

Which generators use the Cummins/Onan C35 D6 engine?

The Cummins/Onan C35 D6 powers 1 generator set(s), including Cummins/Onan C35 D6.

What is a common problem with the Cummins/Onan C35 D6 engine?

A commonly reported issue on generators using the Cummins/Onan C35 D6 is: Low Battery Voltage — Battery voltage is low. Cause: Damaged battery cable connections. Fix: Inspect the battery cable connections for loose connections and/or corrosion, and repair as necessary.