Specifications
| Controller | APM402 |
|---|
Service specifications
20| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Gap | Speed sensor air gap | 0.36- 0.71 | mm | |
| Pressure | Battery equalizer input voltage (24 volts nominal) | 20- 35 | volts | |
| Pressure | Battery equalizer output voltage | (input voltage/2) ±2% | volts | |
| Pressure | Pressure switch 364345 | 483 ±14 | kPa | |
| Resistance | Pressure sender 264390 value A | 240 +17/- 15 | ohms at 0 psi | |
| Resistance | Pressure sender 264390 value B | 153 +12/- 15 | ohms at 25 psi | |
| Resistance | Pressure sender 264390 value C | 33.5 | ohms at 100 psi | |
| Resistance | Pressure sender 365624 value A | 241 ±16 | ohms at 0 psi | |
| Resistance | Pressure sender 365624 value B | 152 ±13 | ohms at 50 psi | |
| Resistance | Pressure sender 365624 value C | 33.5 | ohms at 200 psi | |
| Resistance | Temperature sender 226717 value A | 123.8 +7.2/- 7.8 | ohms at 90.6 C (195 F) | |
| Resistance | Temperature sender 226717 value B | 35.6 +3.4/- 3.6 | ohms at 137.8 C (280 F) | |
| Resistance | Temperature sender 226919 value A | 942 ±22 | ohms at 37.7 C (100 F) | |
| Resistance | Temperature sender 226919 value B | 35 | ohms at 115.6 C (240 F) | |
| Speed | Overspeed shutdown | 70 | Hz | 60 Hz models |
| Temperature | Battery equalizer operating temperature | - 40 to 71 | C (- 40 F to 160 F) | |
| Temperature | Temperature switch 241308 | 107 ±4 | C (225 F ±7 F) | normally open to close on temp. rise |
| Temperature | Temperature switch 290090/GM51705 | 16 ±3 | C (60 F ±5 F) | normally open to close on temp. fall |
| Voltage | Speed sensor voltage, wire 2 (black) & 16 (white) | 3- 6 | volts DC | |
| Voltage | Speed sensor voltage, wire 2 (black) & 24 (red) | 8- 10 | volts DC |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Procedures
12Overfrequency Adjustment (Over/Underfrequency Relay, Decision-Maker 3+) adjustment
- Turn the overfrequency adjustment potentiometer fully clockwise (CW).
- Place master switch in RUN to start the generator set.
- Adjust governor per engine operation manual, engine service manual, or governor section of this manual.
- Slowly turn overfrequency potentiometer counterclockwise (CCW) until the LED starts flashing; after about 10 seconds the set shuts down on auxiliary fault.
- Place master switch to OFF/RESET to reset the controller.
- Place master switch to RUN to start the generator set.
- Readjust the governor to the desired frequency as required.
- Place master switch to OFF/RESET to stop the generator set.
Overvoltage Feature Testing and Adjustment (Decision-Maker 3+) adjustment
⚠ Hazardous voltage. Moving parts. Will cause severe injury or death. Operate the generator set only when all guards and electrical enclosures are in place.
⚠ Disconnecting the electrical load. Hazardous voltage will cause severe injury or death.
- Disconnect generator set from load by opening line circuit breaker or disconnecting and taping output leads.
- Determine overvoltage shutdown value based on user requirement; factory setting is 15% above nominal line-to-neutral voltage.
- Remove the controller cover.
- Place master switch in RUN to start the generator set.
- Observe AC voltmeter; turn voltage adjustment potentiometer CW until generator set shuts down.
- If the shutdown point is correct, go to step 12; otherwise continue.
- Turn controller circuit board R42 adjustment potentiometer fully CW.
- Place master switch to OFF/RESET to reset; then to RUN to start.
- Observe AC voltmeter while turning voltage adjustment potentiometer to desired overvoltage shutdown point.
- Turn R42 adjustment potentiometer slowly CCW until the generator set shuts down.
- Turn controller voltage adjustment potentiometer slightly CCW.
- Place master switch OFF/RESET then RUN to start; adjust for correct voltage and phase.
- Place master switch OFF/RESET to stop.
- Disconnect battery negative lead first; reconnect generator set to load; reconnect battery negative lead last.
Reactive Droop Compensator Adjustment Procedure adjustment
Tools: Voltmeter, Wattmeter
- Remove any load; start each generator set with master switch in RUN.
- Set reactive droop compensator rheostat on generator set no. 1 to minimum CCW; record rpm/frequency and voltage at 1/4 load steps to full load.
- Repeat for generator set no. 2.
- Compare readings; adjust voltage within 1 volt and speed within 3 rpm (or 0.1 Hz) at each load step.
- Check droop compensation on each unit with an inductive load 1/2 to full load.
- Adjust rheostat to approximately 4% below rated voltage at full load.
- Repeat for unit no. 2.
Reactive Droop Compensator Alternate Adjustment Procedure adjustment
Tools: Voltmeter
- Turn reactive droop compensator rheostat on generator set no. 1 to minimum setting.
- Remove controller cover; move voltage sensing lead from V7 to V9 at the AC fuse terminal block.
- Remove any load connected to the generator set.
- Start the generator set with master switch in RUN.
- Use controller or remote voltage adjusting potentiometer to fine adjust voltage.
- Apply resistive load (1.0 power factor) until reaching rated current.
- Adjust reactive droop compensator rheostat to achieve a 4% droop in voltage.
- Remove the resistive load and stop the generator set.
- Return voltage sensing lead from V9 to V7 at the AC fuse terminal block.
- Replace the controller cover and repeat for generator set no. 2.
Underfrequency Adjustment (Over/Underfrequency Relay, Decision-Maker 3+) adjustment
- Turn underfrequency adjustment potentiometer fully clockwise (CW).
- Place master switch in RUN to start the generator set.
- Adjust governor per engine operation manual, engine service manual, or governor section of this manual.
- Slowly turn underfrequency potentiometer counterclockwise (CCW) until LED starts flashing; after about 10 seconds the set shuts down on auxiliary fault.
- Place master switch to OFF/RESET to reset the controller.
- Place master switch to RUN to start the generator set.
- Readjust the governor to the desired frequency as required.
- Place master switch to OFF/RESET to stop the generator set.
2-Wire Low Water Level Sender Test diagnostic
⚠ Hot engine and exhaust system can cause severe injury or death. Do not work on the generator set until it cools.
⚠ Hazardous voltage. Moving parts. Will cause severe injury or death. Operate the generator set only when all guards and electrical enclosures are in place.
Tools: DC voltmeter
- Measure DC voltage between lead 31A (+) and ground (- ) with sender submerged in coolant; voltmeter indicates approximately 12.5 VDC.
- Measure DC voltage between lead 31A (+) and ground (- ) with sender removed from coolant for at least 5-15 seconds; voltmeter indicates a drop to approximately 7 VDC.
3-Wire Low Water Level Sender Test diagnostic
⚠ Hot engine and exhaust system can cause severe injury or death. Do not work on the generator set until it cools.
⚠ Hazardous voltage. Moving parts. Will cause severe injury or death.
Tools: Ohmmeter
- Measure resistance between lead 31 and ground with sender submerged in coolant; ohmmeter indicates a high resistance reading.
- Measure resistance between lead 31 and ground with sender removed from coolant for at least 5-15 seconds; ohmmeter indicates a low resistance reading.
Battery Equalizer Troubleshooting diagnostic
⚠ To prevent reverse polarity damage to the battery equalizer, remove the ground (GND) connection first and attach the ground connection last when disconnecting the battery equalizer.
Tools: 12-volt test light with alligator clips, Voltmeter with 0.01 volt resolution, Battery load tester
- Remove the ground (GND) connections from the battery equalizer; do not allow contact with other connections.
- Verify a differential of 12 volts between the +12 volt and +24 volt terminals using a 12-volt test light; the light will illuminate on a functional unit. Remove the test light.
- Connect the test light between the +12 volt and GND terminals; the light will illuminate on a functional unit.
- With the test light connected, measure and record the voltage between the +12 volt and +24 volt terminals.
- With the test light connected, measure and record the voltage between the +12 volt and GND terminals.
- Remove the test light.
- Compare the values from steps 4 and 5; the difference should be - 0.5 and +0.13 volts on a functional unit.
Oil Pressure Sender Testing diagnostic
Tools: Ohmmeter, Mechanical oil pressure gauge
- Disconnect the oil pressure sender lead 7C.
- Check the sender resistance with an ohmmeter.
- Compare resistance values when the generator set is shut down and when running at operating temperature to Section 1, Specifications.
- Use a mechanical oil pressure gauge to further verify correct readings.
Overcrank Test (Typical) diagnostic
- On gas-fueled sets, disconnect the coil wire at the distributor cap and ground it or disconnect the ignition system.
- On diesel-fueled sets, unplug the fuel injector harness from ECM or disconnect wire no. 70 from the injector pump solenoid.
- Place unit in RUN mode; observe 15-second on-off cranking cycles and maximum 75-second elapsed time to overcrank shutdown.
- Observe controller fault lamp and display for an overcrank shutdown.
- Place unit in OFF/RESET mode.
- Reconnect the ignition coil wire/ignition system, or reconnect the fuel injector harness/wire no. 70.
Speed Sensor Test with Generator Set Running diagnostic
⚠ Keep leads connected to the speed sensor terminals during the test; do not disconnect the leads.
Tools: DC voltmeter
- Connect a DC voltmeter between positive (+) lead (wire 24) at the speed sensor and ground (wire 2) with master switch OFF/RESET; read approximately 8- 12 volts DC.
- Place master switch in RUN to start the generator set.
- Connect DC voltmeter negative probe to 0 terminal (wire 16 white) and positive probe to positive (+) terminal (wire 24 red); read approximately 7- 12 volts DC.
- Place master switch in OFF/RESET to stop the generator set.
- If sensor emits a signal, check continuity of speed sensor leads (wires 2, 16, 24) between controller P1 connector and sensor terminals.
Speed Sensor Test with Separate 12 VDC Source diagnostic
Tools: DC voltmeter, 12-volt battery or DC power supply, Flat piece of iron or steel
- Place master switch in OFF/RESET position.
- Disconnect the speed sensor leads.
- Connect speed sensor, DC voltmeter, and DC voltage source as shown.
- Touch sensing surface with a flat piece of iron or steel at least 4.1 cm (1/4 cu. in.) in size.
- DC voltmeter reading should equal the source voltage, approximately 12 VDC.
- Remove the iron or steel piece and observe a voltmeter reading of 0 VDC.
- If the sensor passes, it is functional; replace if it fails.
- Connect the speed sensor leads and adjust the air gap.
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Voltage reconnection
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| APM402 and Decision-Maker 3000 P21 | P21-1 GND Shield; P21-2 (+) White; P21-3 (-) Black | Connect shield at either end but not at both ends. | ||
| APM603 customer connection terminal block | (+) White; (-) Black; Shield — do not connect at the customer connection terminal block; tape to insulate unused end | Connect shield at the RSA III P27 connection but not at the APM603 customer connection terminal block. | ||
| APM802 TB10 | TB10-7 (-) Blue; TB10-8 (+) Green; Shield — do not connect at TB10 or base module; tape to insulate unused end | 120 ohm resistor located on the base module; connect shield at the RSA III P27 connection only. | ||
| Communication module board TB5 (DEC 3+) | TB5-3 ATS Position Input Return; TB5-4 User 1 Input Return; TB5-5 User 2 Input Return; TB5-6 User 3 Input Return; TB5-9 ATS Position Input; TB5-10 User 1 Input; TB5-11 User 2 Input; TB5-12 User 3 Input | Terminals 1, 2, 7, and 8 not used. User 3 Input reserved for high battery volts (HBV) on DEC 3+ controllers. | ||
| Decision-Maker 3+ P21 | P21-1 - Black; P21-2 + White; P21-3 GND Shield | Connect shield at either end but not at both ends. | ||
| Decision-Maker 3500 TB12 | COM (+) (+) White; COM (-) (-) Black; Shield — do not connect at TB12 or DEC 3500, tape to insulate unused end | Connect shield at the RSA III P27 connection only. | ||
| Decision-Maker 550 and 6000 P20 | P20-1 GND Shield; P20-2 + White; P20-3 - Black | Connect shield at either end but not at both ends. | ||
| Decision-Maker 8000 RS-485 | A terminal: blue wire, High (H) or Positive (+); B terminal: green wire, Low (L) or Negative (-) | 120 ohm resistor located on the controller base box; connect shield at the RSA III P27 connection only. | ||
| P27 connector on RSA III slave | P27-1 (-) Black (from master or previous slave); P27-2 (+) White (from master or previous slave); P27-3 Shield (from master or previous slave); P27-4 (-) Black (to next slave or terminating resistor); P27-5 (+) White (to next slave or terminating resistor); P27-6 Shield (to next slave or open) | RS-485 daisy chain from master to slave. | ||
| P27 connector on master RSA III | P27-1 (-) Black (from controller); P27-2 (+) White (from controller); P27-3 Shield (from controller); P27-4 (-) Black (to slave or terminating resistor); P27-5 (+) White (to slave or terminating resistor); P27-6 Shield (to slave or open) | RS-485 communication from controller to RSA III master. Connect shield at either end but not both ends. | ||
| P27-1 (Controller to RSA III master) | (-) Black (from controller) | RS-485 communication; use Belden #9841 or equivalent. | ||
| P27-2 (Controller to RSA III master) | (+) White (from controller) | RS-485 communication. | ||
| P27-3 (Controller to RSA III master) | Shield (from controller) | Connect the shield wire at either end but not at both ends. | ||
| P27-4 (Master to slave) | (-) Black (to slave or terminating resistor) | RS-485 communication. | ||
| P27-5 (Master to slave) | (+) White (to slave or terminating resistor) | RS-485 communication. | ||
| P27-6 (Master to slave) | Shield (to slave or open) | RS-485 communication. | ||
| P37 power connections | P37-1 Ground; P37-2 12/24 VDC battery input1 (not polarity sensitive); P37-3 12/24 VDC battery input2 (not polarity sensitive) | Requires 12/24-volt, 200 mA (min.) DC power source; voltage should match generator set starting system. | ||
| P37-1 | Ground | Power/CAN connections. | ||
| P37-2 | 12/24 VDC battery input1 (not polarity sensitive) | Attach battery positive (+) at the starter solenoid. | ||
| P37-3 | 12/24 VDC battery input2 (not polarity sensitive) | Attach battery negative (-) at the engine ground. | ||
| P40 output connections | P40-1 Common fault relay normally closed; P40-2 Common fault relay common; P40-3 Common fault relay normally open; P40-4 Horn relay normally closed; P40-5 Horn relay common; P40-6 Horn relay normally open | Dry contacts rated at 220 VAC @ 0.8 amps and 30 VDC @ 2 amps. | ||
| P41 input connections | P41-1 Local ATS emergency on input (EPS); P41-2 Local ATS emergency on input return (EPS); P41-3 User-Defined Digital input 1; P41-4 User-Defined Digital input 1 return; P41-5 User-Defined Digital Input 2; P41-6 User-Defined Digital Input 2 return; P41-7 User-Defined Digital Input 3; P41-8 User-Defined Digital Input 3 return | EPS and user-defined digital inputs typically supplied via remote Modbus RS-485 but may be hardwired locally. | ||
| P42 connections | P42-1 User-defined digital input 4; P42-2 User-defined digital input 4 return; P42-3 User-defined digital input 5; P42-4 User-defined digital input 5 return | Local user-defined digital inputs 4 and 5. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Troubleshooting
7Fault codes
| Code | Meaning | Remedy |
|---|---|---|
| 32 | High Coolant Temperature | |
| 32A | Emergency Stop | Reset the emergency stop switch. |
| 40 | Pre High Coolant Temp. | |
| 41 | Pre Low Oil Pressure | Check and adjust oil level or replace oil pump. |
| 62 | Low Battery Volts | |
| 63 | Low Fuel | Refuel the generator set. |
| 48 | Emergency Stop |
Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.
Repair guides
13- Complete the RSA III final installation
- Configure the APM402 controllers for the remote serial annunciator
- Configure the DEC 3+ controller for the remote serial annunciator
- Configure the DEC 550 and DEC 6000 controllers for the remote serial annunciator
- Configure the DEC 8000 controllers for the remote serial annunciator
- Configure the Decision-Maker 3000 and 3500 controllers for the remote serial annunciator
- Mount the communication module board in the DEC 3+ controller
- Remove the gauge driver board in the DEC 3+ controller (if equipped)
- Remove the Generator Set from Service
- Restore the Generator Set to Service
- Select a Mounting Location for the RSA III
- Wire the communication module board in the DEC 3+ controller
- Wire the RSA III
Step-by-step procedures compiled from the Kohler service manual for this model.
Parts
1| Part # | Description | Qty | System | |
|---|---|---|---|---|
| APM402 | APM402 Controller | 1 | Controller | Amazon eBay $875.00 |
Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.