Home›Repair guides›Kohler›Configure the Decision-Maker 3000 and 3500 controllers for the remote serial annunciator

Kohler — Configure the Decision-Maker 3000 and 3500 controllers for the remote serial annunciator

Installation · Decision-Maker 3000 / 3500 controller

From a Kohler service manual covering: APM402, APM603, APM802, Decision-Maker 550, GM32644-KP1, GM62466-KP1, GM91356, KPC 1000, MPAC 1000, MPAC 1200, MPAC 1500, MPAC 750. Check it applies to your exact model before use.

Applies to: Kohler APM402, Kohler APM603

Procedure

  1. Verify the controller defaults to a 19200 baud rate and Modbus address #1.
  2. If Modbus settings need altering, use SiteTech software to make the configuration changes.
  3. Verify the RS-485 address on the controller matches the address on the RSA III master.

Specs & values

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Kohler repair guides →