Kohler — Configure the DEC 550 and DEC 6000 controllers for the remote serial annunciator
Installation · Decision-Maker 550 / 6000 controller
From a Kohler service manual covering: APM402, APM603, APM802, Decision-Maker 550, GM32644-KP1, GM62466-KP1, GM91356, KPC 1000, MPAC 1000, MPAC 1200, MPAC 1500, MPAC 750. Check it applies to your exact model before use.
Applies to: Kohler APM402, Kohler APM603
Procedure
- Replace the controller cover and hardware.
- Press the Reset Menu key on the controller keypad.
- Go to Menu 14, Programming Mode; verify Programming Mode - Local, else select Local.
- Enter the access code (factory default is 0) and press Enter.
- Press the Reset Menu key. Go to Menu 6, Time and Date, and set the correct time and date.
- Press the Reset Menu key. Go to Menu 13, Communications, and select Protocol - Modbus.
- Set the controller Modbus address to #1 by entering number 1 at Address.
- Set Baud Rate to 19200 if not already shown.
- Press the Reset Menu key. Go to Menu 14, Programming Mode - Local.
- Select Programming Mode - Off and enter the access code.
Specs & values
- Factory default access code: 0
- Modbus address: 1
- Baud rate: 19200 Amazon eBay $30.84
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.