Kohler — Configure the DEC 550 and DEC 6000 controllers for the remote serial annunciator

Installation · Decision-Maker 550 / 6000 controller

From a Kohler service manual covering: APM402, APM603, APM802, Decision-Maker 550, GM32644-KP1, GM62466-KP1, GM91356, KPC 1000, MPAC 1000, MPAC 1200, MPAC 1500, MPAC 750. Check it applies to your exact model before use.

Applies to: Kohler APM402, Kohler APM603

Procedure

  1. Replace the controller cover and hardware.
  2. Press the Reset Menu key on the controller keypad.
  3. Go to Menu 14, Programming Mode; verify Programming Mode - Local, else select Local.
  4. Enter the access code (factory default is 0) and press Enter.
  5. Press the Reset Menu key. Go to Menu 6, Time and Date, and set the correct time and date.
  6. Press the Reset Menu key. Go to Menu 13, Communications, and select Protocol - Modbus.
  7. Set the controller Modbus address to #1 by entering number 1 at Address.
  8. Set Baud Rate to 19200 if not already shown.
  9. Press the Reset Menu key. Go to Menu 14, Programming Mode - Local.
  10. Select Programming Mode - Off and enter the access code.

Specs & values

Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.