Kohler — Remove the gauge driver board in the DEC 3+ controller (if equipped)
Repair & overhaul
From a Kohler service manual covering: APM402, APM603, APM802, Decision-Maker 550, GM32644-KP1, GM62466-KP1, GM91356, KPC 1000, MPAC 1000, MPAC 1200, MPAC 1500, MPAC 750. Check it applies to your exact model before use.
Applies to: Kohler APM402, Kohler APM603
Procedure
- Disconnect the 10-pin cable at the P8 connector on the circuit board.
- Disconnect the 8-pin cable at the P10 connector on the circuit board.
- Remove the existing three nuts and lock washers attaching the gauge drive circuit board to the indicator panel circuit board.
- Remove existing 24-position ribbon cable 336428; it will not be reused.
- Attach the end connector (nearest the inline connector) of new ribbon cable GM32632 to indicator panel circuit board P4.
- Attach the other end connector of ribbon cable GM32632 to main circuit board P3.
Specs & values
- Replacement 24-position ribbon cable: GM32632
- Removed ribbon cable: 336428
Source: Kohler service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.